- Asked 5/20
- 2069 Bhadra (old course) · 6 marks
Capacitor size, feeder with 500 kVA end load
Short answer
Optimum capacitor size is the resistance-weighted average of section reactive flows: Q_c = (∑R_i Q_i)/(∑R_i). For the given feeder, Q_c = 519.5 kVAR, approximately 520 kVAR.
For an 11 kV radial primary distribution feeder shown in figure below, determine the size of the capacitor at the stated location in the feeder to achieve the maximum loss reduction. For simplifying the analysis assume voltage at each node is 1 p.u.
[Figure: radial feeder from a 1000 kVA, 33/11 kV source substation S to node A through 3+j2, A to B through 2+j4, B to C through 1+j2. Loads through distribution transformers: 200 kVA at 0.8 p.f. lag at A, 100 kVA at 0.7 p.f. lag at B, 500 kVA at 0.6 p.f. lag at C. The capacitor is placed at node C.]
Method (optimum single capacitor)
With all node voltages taken as 1 p.u., the reactive current in a section equals its reactive power flow (p.u.). A shunt capacitor at the end node reduces the reactive flow in every section between the source and that node from to . The loss reduction is
For maximum loss reduction, , so
i.e. the optimum capacitor equals the resistance-weighted average of the reactive flows in the sections it relieves. The ratio does not depend on whether is in ohms or p.u., so kVAR can be used directly.
S --(3+j2)-- A --(2+j4)-- B --(1+j2)-- C
| | |
200 kVA 100 kVA 500 kVA
0.8 lag 0.7 lag 0.6 lag [Qc]
Reactive loads
| Node | S (kVA) | p.f. | Q (kVAR) | |
|---|---|---|---|---|
| A | 200 | 0.8 | 0.6 | 120.00 |
| B | 100 | 0.7 | 0.7141 | 71.41 |
| C | 500 | 0.6 | 0.8 | 400.00 |
Section flows
| Section | R | Q flow (kVAR) | R × Q |
|---|---|---|---|
| S–A | 3 | 591.41 | 1774.24 |
| A–B | 2 | 471.41 | 942.83 |
| B–C | 1 | 400.00 | 400.00 |
| Total | 6 | 3117.07 |
Optimum capacitor
Because the largest resistance (S–A) carries the largest reactive flow, the optimum capacitor exceeds the 400 kVAR load at C; it slightly over-compensates section B–C but gives the largest total loss reduction.
Answer: Capacitor at node C ≈ 519.5 kVAR (≈ 520 kVAR).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitor size, four-node 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size for maximum loss reduction (variant) · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size for maximum loss reduction · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size, feeder with three equal loads · Transmission and Distribution System Design, chapter 7
- Loss and drop, 15 km 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Power loss, 10 km 11 kV UDL feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
All Transmission and Distribution System Design chapter 7 questions →