Capacitor size, feeder with 500 kVA end load

Short answer

Optimum capacitor size is the resistance-weighted average of section reactive flows: Q_c = (∑R_i Q_i)/(∑R_i). For the given feeder, Q_c = 519.5 kVAR, approximately 520 kVAR.

For an 11 kV radial primary distribution feeder shown in figure below, determine the size of the capacitor at the stated location in the feeder to achieve the maximum loss reduction. For simplifying the analysis assume voltage at each node is 1 p.u.

[Figure: radial feeder from a 1000 kVA, 33/11 kV source substation S to node A through 3+j2, A to B through 2+j4, B to C through 1+j2. Loads through distribution transformers: 200 kVA at 0.8 p.f. lag at A, 100 kVA at 0.7 p.f. lag at B, 500 kVA at 0.6 p.f. lag at C. The capacitor is placed at node C.]

Method (optimum single capacitor)

With all node voltages taken as 1 p.u., the reactive current in a section equals its reactive power flow QiQ_i (p.u.). A shunt capacitor QcQ_c at the end node reduces the reactive flow in every section between the source and that node from QiQ_i to (Qi−Qc)(Q_i - Q_c). The loss reduction is

ΔPL=∑iRi[Qi2−(Qi−Qc)2]=∑iRi(2QiQc−Qc2)\begin{aligned} \Delta P_L &= \sum_i R_i\left[Q_i^2-(Q_i-Q_c)^2\right] = \sum_i R_i\left(2Q_iQ_c-Q_c^2\right) \end{aligned}

For maximum loss reduction, d(ΔPL)dQc=∑iRi(2Qi−2Qc)=0\dfrac{d(\Delta P_L)}{dQ_c} = \sum_i R_i(2Q_i-2Q_c)=0, so

Qc,opt=∑iRiQi∑iRiQ_{c,opt} = \frac{\sum_i R_iQ_i}{\sum_i R_i}

i.e. the optimum capacitor equals the resistance-weighted average of the reactive flows in the sections it relieves. The ratio does not depend on whether RR is in ohms or p.u., so kVAR can be used directly.

 S --(3+j2)-- A --(2+j4)-- B --(1+j2)-- C
              |            |            |
          200 kVA      100 kVA      500 kVA
          0.8 lag      0.7 lag      0.6 lag  [Qc]

Reactive loads

NodeS (kVA)p.f.sin⁡ϕ\sin\phiQ (kVAR)
A2000.80.6120.00
B1000.70.714171.41
C5000.60.8400.00

Section flows

SectionRQ flow (kVAR)R × Q
S–A3591.411774.24
A–B2471.41942.83
B–C1400.00400.00
Total63117.07

Optimum capacitor

Qc=1774.24+942.83+4003+2+1=3117.076=519.5 kVARQ_c = \frac{1774.24+942.83+400}{3+2+1} = \frac{3117.07}{6} = 519.5\ \text{kVAR}

Because the largest resistance (S–A) carries the largest reactive flow, the optimum capacitor exceeds the 400 kVAR load at C; it slightly over-compensates section B–C but gives the largest total loss reduction.

Answer: Capacitor at node C ≈ 519.5 kVAR (≈ 520 kVAR).