Design: 100 kVA 11/132 kV transformer with winding data
Short answer
Three-stepped core d=158 mm, stampings 142, 111, 66 mm; window 638 mm high × 213 mm wide; yoke depth 142 mm, height 141 mm; overall frame 920×884×142 mm. Leakage reactance per phase referred to LV is 179 Ω (0.0493 pu). Voltage regulation at 0.8 pf lagging is 0.0491 pu (4.91%).
Design a 100 kVA, 50 Hz, 11/132 kV, 3-phase, Δ/Y, core type oil immersed natural cooled distribution transformer. Maximum flux density in core = 1.35 Wb/m²; Core type = 3 stepped; Current density = 2.75 A/mm²; Window space factor = 0.4; Hw/Ww = 3; Take hot rolled steel sheet and area of yoke = 1.2 × area of core; Axial depth of L.V. = 268 mm; Axial depth of H.V. = 276 mm; Radial depth of L.V. = 14 mm; Radial depth of H.V. = 18 mm; Width of insulation between L.V. and H.V. = 11 mm; Outside diameter of L.V. = 293 mm, Inside diameter of L.V. = 255 mm; Inside diameter of H.V. = 314 mm, Outside diameter of H.V. = 351 mm. Calculate: (i) Dimension of core, window and yoke (ii) Overall dimension of frame (iii) Leakage reactance of transformer (iv) Voltage regulation at 0.8 pf lagging at full load.
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. is not given; = 0.45 is taken (3-phase distribution transformer). Also assumed -mm²/m. Winding data are given: LV 255/293 mm (inside/outside diameter), HV 314/351 mm, radial depths = 14 mm, = 18 mm, gap = 11 mm. Axial length taken as the mean of 268 and 276 mm, = 272 mm.
(i) Dimensions of core, window and yoke
Voltage per turn, ( in kVA, total for 3 phases):
For a three-stepped core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Check with the given windings: core = 158 mm fits inside the LV (255 mm). But the HV outside diameter (351 mm) exceeds = 253 mm, and the coil (276 mm) is almost as tall as the window (284 mm). So the window is enlarged to suit the given coils, with 20 mm between adjacent HV coils, and its height is increased to keep the given ratio :
(A real 132 kV winding would need far larger clearances; the given figures are used as stated.)
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(ii) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
(iii) Leakage reactance
Phase voltages: LV (delta) V; HV (star) V.
Phase currents: A; A.
Radial depths: mm (LV), mm (HV), duct mm.
Mean lengths of turn:
Leakage reactance (per unit), with per limb and axial winding length mm:
(iv) Regulation at 0.8 pf lagging, full load
Resistance referred to HV, with (copper at about 75 °C):
Answer: = 158 mm; window 213 × 638 mm; yoke 141 × 142 mm; frame 920 × 884 × 142 mm; ≈ 8583 Ω/phase on HV (4.93%); regulation ≈ 4.91%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 150 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- IDMT relays across 132/11 kV transformer (3500 A) · Switchgear and Protection, chapter 7