Design: 125 kVA single phase transformer
Short answer
Core diameter 223.5 mm, limb 190.0×118.5 mm; window 137.5×300.6 mm (adjusted for coil clearance); yoke depth 190.0 mm, height 196.3 mm. Overall frame 693.3×551.0×190.0 mm. Leakage reactance calculation is not fully provided.
Design a 125 kVA, 50 Hz, 6600/400 V, 1-phase, core type oil immersed natural cooled distribution transformer. Given that: Maximum flux density in the core = 1.35 Wb/m²; Current density = 2.75 A/mm²; Core type = cruciform two stepped; Window space factor = 0.30; Stacking factor = 0.9; Ratio of window height to width 2.5; Take hot rolled steel sheet and area of yoke is 20% greater than area of core; Axial depth of L.V. winding = 268 mm; Axial depth of H.V. winding = 276 mm; Inside diameter of LV winding = 255 mm; Radial depth of LV winding = 14 mm; Radial depth of HV winding = 18 mm; Width of insulation between LV and HV = 11 mm; Outside diameter of LV winding = 293 mm; Inside diameter of HV winding = 314 mm; Outside diameter of HV winding = 351 mm. Calculate: i) Dimension of the core, window and yoke ii) Overall dimension of the frame iii) Leakage reactance of the transformer. Appropriate values for additional data required may be assumed if necessary.
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. In a single-phase core type transformer half of each winding is on each limb, so the ampere-turns per limb are . = 0.75 assumed (single-phase core type), -mm²/m. Winding data are given: LV 255/293 mm (inside/outside diameter), HV 314/351 mm, radial depths = 14 mm, = 18 mm, gap = 11 mm. Axial length taken as the mean of 268 and 276 mm, = 272 mm.
i) Dimensions of core, window and yoke
Voltage per turn, ( in kVA):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (single phase):
Check: = 224 mm fits inside the LV (255 mm) and coil height 276 mm < . But HV outside diameter 351 mm > = 344 mm, so the window is widened (10 mm between the HV coils on the two limbs):
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
ii) Overall dimensions of frame
+-----------------------+ ---
| top yoke | ^
+-----+-----------+-----+ |
|limb | window |limb | H
| | Ww x Hw | | |
+-----+-----------+-----+ |
| bottom yoke | v
+-----------------------+ ---
|<--------- W --------->|
|<----- D ----->|
iii) Leakage reactance
Currents: A; A.
Radial depths: mm (LV), mm (HV), duct mm.
Mean lengths of turn:
Leakage reactance (per unit), with per limb and axial winding length mm:
Answer: = 224 mm; window 137 × 301 mm; yoke 196 × 190 mm; frame 693 × 551 × 190 mm; leakage reactance ≈ 9.39 Ω referred to HV (2.69%).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 150 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 100 kVA single phase, square core · Electric Machine Design, chapter 3