Design: 100 kVA single phase, square core
Short answer
Square limb side a=177.6 mm (d=250.1 mm), window 138×276 mm. Frame: height 699 mm, width 566 mm, depth 178 mm. HV winding: 293 turns, 18.18 mm²; LV winding: 64 turns, 83.33 mm².
Determine the (i) overall dimension of the core, (ii) overall dimension of frame and (iii) number of turns and the cross sectional area of conductors in the primary and secondary windings of a 100 kVA, 2200/480 V single phase core type transformer to operate at frequency of 50 Hz, assuming the following data: Constant for voltage per turn = 0.75; Maximum flux density = 1.2 Wb/m²; Core type = Square; Stacking factor = 0.9; Ratio of height to width of window = 2; Window space factor = 0.28; Current density = 2.5 A/mm²
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. Assumed: yoke area 1.2 × core area (hot-rolled steel).
(i) Overall dimensions of core
Voltage per turn, ( in kVA):
For a square core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (single phase):
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(ii) Overall dimensions of frame
+-----------------------+ ---
| top yoke | ^
+-----+-----------+-----+ |
|limb | window |limb | H
| | Ww x Hw | | |
+-----+-----------+-----+ |
| bottom yoke | v
+-----------------------+ ---
|<--------- W --------->|
|<----- D ----->|
(iii) Turns and conductor areas
Currents: A; A.
| Winding | Voltage (V) | Current (A) | Turns | Conductor area (mm²) |
|---|---|---|---|---|
| Primary (HV) | 2200 | 45.45 | 293 | 18.18 |
| Secondary (LV) | 480 | 208.33 | 64 | 83.33 |
The LV conductor (83.3 mm²) would be a rectangular strip (for example several strips in parallel); the HV conductor is a round or small rectangular wire.
Answer: = 250.1 mm ( = 177.6 mm), window 138 × 276 mm; frame 699 × 566 × 178 mm; HV 293 turns of 18.18 mm², LV 64 turns of 83.33 mm².
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Core, turns and conductors of 5 kVA transformer · Electric Machine Design, chapter 3
- Six-stepped core area and turns (1000 kVA) · Electric Machine Design, chapter 3
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 150 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Number of turns of iron-core inductor · Basic Electrical Engineering, chapter 4
- Air gap flux density in core with three windings · Electrical Machines I, chapter 1
- Equivalent circuit of 100 kVA 2200/220 V transformer · Electrical Machines I, chapter 2 · asked 3×
- 20 kVA 2200/220 V tests, efficiency · Electrical Machine, chapter 2