- 2069 Asar · 10 marks
Six-stepped core area and turns (1000 kVA)
Short answer
Using the given ratio 1.62×10⁻⁴ Wb/AT, net iron area Ai = 0.314 m², circumscribing circle diameter d = 0.724 m. LV turns = 2, HV turns =53.
A 3 phase core type power transformer has the following design specification: 1000 kVA, 50 Hz, 6600/433 volt, delta/star connected. Estimate: i) Net iron area of the core (with 6 steps core) ii) Diameter of the circumscribing circle iii) Number of HV and LV turns. Assume: Ratio magnetic loading (φm) / electrical loading (AT) = 1.62×10⁻⁴ Wb/AT; Flux density = 1.57 T; Net iron area = 0.6 × Gross iron area (for 6 stepped); Stacking factor = 0.89
Data: 1000 kVA, 3-phase, 50 Hz, 6600 V (delta) / 433 V (star), Wb/AT, = 1.57 T, 6-stepped core, stacking factor 0.89.
Reading of the data: the net iron area of a 6-stepped core is taken as , where is the diameter of the circumscribing circle (the factor 0.6 already includes the stacking factor; the gross stepped area is ).
Flux from the loading ratio
Per phase kVA:
With :
i) Net iron area
Gross area of the stepped core m².
ii) Diameter of circumscribing circle
iii) Turns
LV phase voltage (star) V; HV phase voltage (delta) = 6600 V.
Answer (with the ratio as printed): ≈ 0.314 m², ≈ 0.724 m, LV 2 turns, HV 53 turns.
Note on the data
The printed ratio gives about 110 V per turn, far above normal for 1000 kVA ( with gives ≈ 19 V). The ratio was most likely meant to be Wb/AT. The same steps then give:
| Quantity | |
|---|---|
| 0.0493 Wb | |
| 10.95 V | |
| Net iron area | 0.0314 m² (314 cm²) |
| Circle diameter | 229 mm |
| LV turns | 22.8 → 23 |
| HV turns | 607 |
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 25 kVA 11000/433 V distribution transformer · Electric Machine Design, chapter 3
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Core, turns and conductors of 5 kVA transformer · Electric Machine Design, chapter 3
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- Number of turns of iron-core inductor · Basic Electrical Engineering, chapter 4