- 2073 Shrawan · 12 marks
Core, turns and conductors of 5 kVA transformer
Short answer
Core area 73.2 cm², square limb side 90.2 mm (diameter 127.6 mm), window 85.6×256.7 mm. HV winding: 6765 turns, 0.325 mm²; LV winding: 246 turns, 8.93 mm².
Determine the main dimensions of the core, the number of turns and the cross sections of the conductors for a 5 kVA, 11000/400 V, 50 Hz, single phase core type distribution transformer. The net conductor area in the window is 0.6 times the net cross section of iron in the core. Assume a square cross-section for core, a flux density 1 Wb/m², a current density 1.4 A/mm², and window space factor 0.2. The height of window is 3 times its width.
Data: = 5 kVA, = 50 Hz, = 1 Wb/m², = 1.4 A/mm², = 0.2, , square core, and copper area in window .
Core area
Single-phase output equation:
With :
Core dimensions (square core)
For a square core with stacking factor 0.9: , side .
Window
Turns
Conductor sections
The HV conductor ≈ 0.33 mm² (about 0.65 mm diameter round wire); the LV conductor ≈ 8.9 mm² (round wire about 3.4 mm diameter, or a small strip).
| Quantity | Value |
|---|---|
| Net core area | 73.2 cm² |
| Core circle dia / side | 127.6 mm / 90.2 mm |
| Window | 85.6 × 256.7 mm |
| Turns HV / LV | 6765 / 246 |
| Conductor area HV / LV | 0.325 / 8.93 mm² |
Answer: ≈ 73.2 cm², square limb 90.2 mm (circle 127.6 mm), window 85.6 × 256.7 mm; HV 6765 turns of 0.325 mm², LV 246 turns of 8.93 mm².
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 25 kVA 11000/433 V distribution transformer · Electric Machine Design, chapter 3
- Design: 100 kVA single phase, square core · Electric Machine Design, chapter 3
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Six-stepped core area and turns (1000 kVA) · Electric Machine Design, chapter 3
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Number of turns of iron-core inductor · Basic Electrical Engineering, chapter 4
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2
- Single phase vs 3-phase distribution transformer · Transmission and Distribution System Design, chapter 7 · asked 2×
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×