Design: 150 kVA 11000/420 V distribution transformer
Short answer
Core: cruciform, d=181.2 mm, window 152.4×381 mm, limb centres 333.6 mm, yoke depth 154.0 mm, height 159.2 mm. Frame overall: 821.3 mm wide, 699.4 mm high, 154 mm deep. Per-unit resistance, leakage reactance drop, and regulation were not completed in the provided solution.
Calculate (i) Overall dimension of core (ii) Overall dimension of frame (iii) Per unit resistance and leakage reactance drop and (iv) Per unit voltage regulation at 0.85 power factor, for a 150 kVA, 11000/420 V, 50 Hz, 3-phase, Δ/Y core type, oil immersed natural cooled distribution transformer from the following data: Maximum flux density = 1.35 Wb/m², constant for output voltage per turn = 0.45, current density in conductors = 2.5 A/mm², core type = cruciform, window space factor = 0.25, stacking factor = 0.9, ratio of height of window to width = 2.5, width of LV winding, HV winding and duct in between = 20 mm, 25 mm, 15 mm respectively.
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. Assumed: yoke area 1.2 × core area (hot-rolled steel), core-to-LV clearance 5 mm, end clearance 20 mm, -mm²/m.
(i) Overall dimensions of core
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Yoke:
Yoke area is 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(ii) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
(iii) Per unit resistance and leakage reactance drop
Phase voltages: LV (star) V; HV (delta) V.
Phase currents: A; A.
Radial build (assumed clearance between core and LV = 5 mm). Each radial gap or depth appears on both sides of the diameter, so it is added twice:
- LV inside diameter mm
- LV outside diameter mm
- HV inside diameter mm
- HV outside diameter mm
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 191.2 | 231.2 |
| HV winding | 261.2 | 311.2 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length mm.
Mean lengths of turn:
Check: HV outside diameter 311 mm vs = 334 mm. Adjacent HV coils have about 22 mm clearance, so the coils fit.
Resistance referred to HV, with (copper at about 75 °C):
Leakage reactance (per unit), with per limb and axial winding length mm:
(iv) Per unit regulation at 0.85 pf lagging
Answer: = 181 mm, window 152 × 381 mm; frame 699 × 821 × 154 mm; = 0.0149, = 0.0451; regulation ≈ 3.64%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 25 kVA 11000/433 V distribution transformer · Electric Machine Design, chapter 3
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Design: 25 kVA transformer frame, regulation, tubes · Electric Machine Design, chapter 3 · asked 2×
- Per unit resistance drop of core type transformer · Electric Machine Design, chapter 3
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Distribution loss and voltage drop, four LT feeders · Transmission and Distribution System Design, chapter 7
- 150 kVA transformer: max efficiency load · Electrical Machines, chapter 2
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2
- Salient pole generator phasor diagram in per unit · Electric Machines II, chapter 1