Design: 25 kVA transformer frame, regulation, tubes
Short answer
Frame overall dimensions: H = 535.5 mm, W = 622.7 mm, depth = 114.4 mm. Per-unit voltage regulation at 0.8 pf lag is 0.0442 (4.42%). Minimum number of 50 mm diameter, 1.35 m long tubes required to maintain oil temperature within limit is 2.
For the design of a 25 kVA, 50 Hz, 11/0.433 kV, delta/star, 3-phase, core type, oil immersed, naturally cooled distribution transformer, the mean temperature of oil is not to exceed 35°C. The following parameters are chosen: Bm = 1.0 Wb/m², δ = 2.3 A/mm², constant for volt per turn = 0.45, type of core - cruciform, Kw = 0.18, Hw/Ww = 2.5, total loss at full load = 1.2 kW. Winding dimensions:
| Inside diameter (mm) | Outside diameter (mm) | Conductor area (mm²) | |
|---|---|---|---|
| LV | 138 | 156.2 | 14.9 |
| HV | 186.2 | 239 | 0.312 |
Lc = 253 mm, ρ = 0.021 Ω-mm²/m. Take dimension: Ht = 950 mm, Wt = 840 mm, Lt = 350 mm. i) Calculate overall dimensions of frame. ii) Calculate per unit regulation at full load and 0.8 pf (lag). iii) Calculate the minimum number of tubes of diameter 50 mm with average length of 1.35 m required for maintaining the mean temperature within the permissible limit. The rate of heat dissipation from plain wall is 6.5 and 6 W/m²-°C for convection and radiation respectively. The provision of tube improves the rate of heat dissipation by 35%.
Design follows the standard method (A.K. Sawhney): , output equation for , yoke 20% larger than core (hot-rolled steel assumed), -mm²/m.
Core and window
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Check: HV outside diameter (239 mm) < (254.2 mm), so adjacent HV coils have about 15 mm clearance. LV inside diameter 138 mm > , so the windings fit.
Yoke
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
i) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
ii) Per unit regulation at full load, 0.8 pf lagging
Turns and currents
Phase voltages: LV (star) V; HV (delta) V.
Phase currents: A; A.
(The given conductor areas, 14.9 mm² and 0.312 mm², match these values.)
Resistance
Radial depths: mm (LV), mm (HV), duct mm. Axial length mm (given).
Mean lengths of turn:
Using the given conductor areas:
Reactance
Leakage reactance (per unit), with per limb and axial winding length mm:
Regulation
iii) Number of cooling tubes
Total loss W, allowed mean oil rise C, tube diameter 50 mm, length 1.35 m.
Tank walls (top and bottom neglected), dissipation 12.5 W/m²°C (6 radiation + 6.5 convection):
This exceeds 35 °C, so tubes are needed. Tubes improve convection by 35%: W/m²°C.
Answer: frame 535 mm high × 623 mm wide × 114 mm deep; regulation ≈ 4.42%; minimum 4 tubes (50 mm dia, 1.35 m).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 25 kVA 11000/433 V distribution transformer · Electric Machine Design, chapter 3
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2