Short answer

Frame overall dimensions: H = 535.5 mm, W = 622.7 mm, depth = 114.4 mm. Per-unit voltage regulation at 0.8 pf lag is 0.0442 (4.42%). Minimum number of 50 mm diameter, 1.35 m long tubes required to maintain oil temperature within limit is 2.

For the design of a 25 kVA, 50 Hz, 11/0.433 kV, delta/star, 3-phase, core type, oil immersed, naturally cooled distribution transformer, the mean temperature of oil is not to exceed 35°C. The following parameters are chosen: Bm = 1.0 Wb/m², δ = 2.3 A/mm², constant for volt per turn = 0.45, type of core - cruciform, Kw = 0.18, Hw/Ww = 2.5, total loss at full load = 1.2 kW. Winding dimensions:

Inside diameter (mm)Outside diameter (mm)Conductor area (mm²)
LV138156.214.9
HV186.22390.312

Lc = 253 mm, ρ = 0.021 Ω-mm²/m. Take dimension: Ht = 950 mm, Wt = 840 mm, Lt = 350 mm. i) Calculate overall dimensions of frame. ii) Calculate per unit regulation at full load and 0.8 pf (lag). iii) Calculate the minimum number of tubes of diameter 50 mm with average length of 1.35 m required for maintaining the mean temperature within the permissible limit. The rate of heat dissipation from plain wall is 6.5 and 6 W/m²-°C for convection and radiation respectively. The provision of tube improves the rate of heat dissipation by 35%.

Design follows the standard method (A.K. Sawhney): Et=KQE_t = K\sqrt{Q}, output equation for AwA_w, yoke 20% larger than core (hot-rolled steel assumed), ρ=0.021 Ω\rho = 0.021\ \Omega-mm²/m.

Core and window

Voltage per turn, Et=KQE_t = K\sqrt{Q} (QQ in kVA, total for 3 phases):

Et=0.4525=2.250 Vϕm=Et4.44f=2.2504.44×50=0.01014 WbAi=ϕmBm=0.010141=0.01014 m2=101.4 cm2\begin{aligned} E_t &= 0.45\sqrt{25} = 2.250\ \text{V}\\ \phi_m &= \frac{E_t}{4.44f} = \frac{2.250}{4.44\times50} = 0.01014\ \text{Wb}\\ A_i &= \frac{\phi_m}{B_m} = \frac{0.01014}{1} = 0.01014\ \text{m}^2 = 101.4\ \text{cm}^2 \end{aligned}

For a cruciform (two-stepped) core with stacking factor 0.9, Ai=0.56d2A_i = 0.56d^2 (standard ratio, Sawhney):

d=Ai0.56=0.010140.56=0.1345 m=134.5 mma=0.85d=114.4 mmb=0.53d=71.3 mm\begin{aligned} d &= \sqrt{\frac{A_i}{0.56}} = \sqrt{\frac{0.01014}{0.56}} = 0.1345\ \text{m} = 134.5\ \text{mm}\\ a &= 0.85d = 114.4\ \text{mm}\\ b &= 0.53d = 71.3\ \text{mm} \end{aligned}

Gross core area Agi=Ai/0.9=0.01126A_{gi} = A_i/0.9 = 0.01126 m².

Output equation (three phase): Q=3.33fBmδKwAwAi×10−3Q = 3.33fB_m\delta K_wA_wA_i\times10^{-3}

Aw=Q3.33fBmδKwAi×10−3=253.33×50×1×2.3×106×0.18×0.01014×10−3=0.03578 m2Ww=Aw2.5=119.6 mm,Hw=2.5Ww=299.1 mmD=d+Ww=254.2 mm (distance between adjacent limb centres)\begin{aligned} A_w &= \frac{Q}{3.33fB_m\delta K_wA_i\times10^{-3}}\\ &= \frac{25}{3.33\times50\times1\times2.3\times10^6\times0.18\times0.01014\times10^{-3}}\\ &= 0.03578\ \text{m}^2\\ W_w &= \sqrt{\frac{A_w}{2.5}} = 119.6\ \text{mm},\quad H_w = 2.5W_w = 299.1\ \text{mm}\\ D &= d + W_w = 254.2\ \text{mm (distance between adjacent limb centres)} \end{aligned}

Check: HV outside diameter (239 mm) < DD (254.2 mm), so adjacent HV coils have about 15 mm clearance. LV inside diameter 138 mm > dd, so the windings fit.

Yoke

Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:

Ay=1.2Ai=0.01216 m2,Agy=Ay0.9=0.01351 m2Dy=a=114.4 mmHy=AgyDy=0.013510.1144=118.2 mm\begin{aligned} A_y &= 1.2A_i = 0.01216\ \text{m}^2,\quad A_{gy} = \frac{A_y}{0.9} = 0.01351\ \text{m}^2\\ D_y &= a = 114.4\ \text{mm}\\ H_y &= \frac{A_{gy}}{D_y} = \frac{0.01351}{0.1144} = 118.2\ \text{mm} \end{aligned}

i) Overall dimensions of frame

H=Hw+2Hy=299.1+2(118.2)=535.5 mmW=2D+a=2(254.2)+114.4=622.7 mmDepth=Dy=a=114.4 mm\begin{aligned} H &= H_w + 2H_y = 299.1 + 2(118.2) = 535.5\ \text{mm}\\ W &= 2D + a = 2(254.2) + 114.4 = 622.7\ \text{mm}\\ \text{Depth} &= D_y = a = 114.4\ \text{mm} \end{aligned}
 +-----------------------------+  ---
 |          top yoke           |   ^
 +-----+-----+-----+-----+-----+   |
 |limb |     |limb |     |limb |   |
 |  R  | Ww  |  Y  | Ww  |  B  |   H
 |     |     |     |     |     |   |
 +-----+-----+-----+-----+-----+   |
 |         bottom yoke         |   v
 +-----------------------------+  ---
 |<------------ W ------------>|
    |<--- D --->|<--- D --->|

ii) Per unit regulation at full load, 0.8 pf lagging

Turns and currents

Phase voltages: LV (star) VLV=250.0V_{LV} = 250.0 V; HV (delta) VHV=11000.0V_{HV} = 11000.0 V.

Phase currents: ILV=Q3VLV=33.33I_{LV} = \frac{Q}{3V_{LV}} = 33.33 A; IHV=0.758I_{HV} = 0.758 A.

TLV=VLVEt=250.02.250=111.11≈111Et (revised)=250.0111=2.252 VTHV=TLVVHVVLV=4884.1≈4884aLV=ILVδ=14.49 mm2,aHV=IHVδHV=0.329 mm2\begin{aligned} T_{LV} &= \frac{V_{LV}}{E_t} = \frac{250.0}{2.250} = 111.11 \approx 111\\ E_t\ (\text{revised}) &= \frac{250.0}{111} = 2.252\ \text{V}\\ T_{HV} &= T_{LV}\frac{V_{HV}}{V_{LV}} = 4884.1 \approx 4884\\ a_{LV} &= \frac{I_{LV}}{\delta} = 14.49\ \text{mm}^2,\quad a_{HV} = \frac{I_{HV}}{\delta_{HV}} = 0.329\ \text{mm}^2 \end{aligned}

(The given conductor areas, 14.9 mm² and 0.312 mm², match these values.)

Resistance

Radial depths: b1=9.1b_1 = 9.1 mm (LV), b2=26.4b_2 = 26.4 mm (HV), duct a=15a = 15 mm. Axial length Lc=253L_c = 253 mm (given).

Mean lengths of turn:

Lmt,LV=π138.0+156.22=0.4621 mLmt,HV=π186.2+239.02=0.6679 mLmt=π138.0+239.02=0.5922 m (both windings, for reactance)\begin{aligned} L_{mt,LV} &= \pi\frac{138.0 + 156.2}{2} = 0.4621\ \text{m}\\ L_{mt,HV} &= \pi\frac{186.2 + 239.0}{2} = 0.6679\ \text{m}\\ L_{mt} &= \pi\frac{138.0 + 239.0}{2} = 0.5922\ \text{m (both windings, for reactance)} \end{aligned}

Using the given conductor areas:

rHV=0.021×4884×0.66790.312=219.6 ΩrLV=0.021×111×0.462114.9=0.0723 ΩRp=219.6+0.0723(4884111)2=359.5 Ωεr=IHVRpVHV=0.7576×359.511000=0.0248\begin{aligned} r_{HV} &= \frac{0.021\times4884\times0.6679}{0.312} = 219.6\ \Omega\\ r_{LV} &= \frac{0.021\times111\times0.4621}{14.9} = 0.0723\ \Omega\\ R_p &= 219.6 + 0.0723\left(\frac{4884}{111}\right)^2 = 359.5\ \Omega\\ \varepsilon_r &= \frac{I_{HV}R_p}{V_{HV}} = \frac{0.7576\times359.5}{11000} = 0.0248 \end{aligned}

Reactance

Leakage reactance (per unit), with ATAT per limb =3700= 3700 and axial winding length Lc=253.0L_c = 253.0 mm:

εx=2πfμ0ATLc⋅LmtEt(a+b1+b23)=2π(50)(4π×10−7)37000.2530⋅0.59222.252(15+9.1+26.43)×10−3=0.0407 p.u.\begin{aligned} \varepsilon_x &= 2\pi f\mu_0\frac{AT}{L_c}\cdot\frac{L_{mt}}{E_t}\left(a + \frac{b_1+b_2}{3}\right)\\ &= 2\pi(50)(4\pi\times10^{-7})\frac{3700}{0.2530}\cdot\frac{0.5922}{2.252}\left(15 + \frac{9.1+26.4}{3}\right)\times10^{-3}\\ &= 0.0407\ \text{p.u.} \end{aligned}

Regulation

ε=εrcos⁡ϕ+εxsin⁡ϕ=0.0248(0.8)+0.0407(0.6)=0.0442 p.u.=4.42%\begin{aligned} \varepsilon &= \varepsilon_r\cos\phi + \varepsilon_x\sin\phi = 0.0248(0.8) + 0.0407(0.6)\\ &= 0.0442\ \text{p.u.} = 4.42\% \end{aligned}

iii) Number of cooling tubes

Total loss P=1200P = 1200 W, allowed mean oil rise θ=35 ∘\theta = 35\ ^\circC, tube diameter 50 mm, length 1.35 m.

Tank walls (top and bottom neglected), dissipation 12.5 W/m²°C (6 radiation + 6.5 convection):

St=2(Wt+Lt)Ht=2.2610 m2θplain=120012.5St=42.46 ∘C\begin{aligned} S_t &= 2(W_t + L_t)H_t = 2.2610\ \text{m}^2\\ \theta_{plain} &= \frac{1200}{12.5S_t} = 42.46\ ^\circ\text{C} \end{aligned}

This exceeds 35 °C, so tubes are needed. Tubes improve convection by 35%: 6.5×1.35≈8.86.5\times1.35 \approx 8.8 W/m²°C.

Atubes=18.8(Pθ−12.5St)=18.8(120035−12.5×2.2610)=0.684 m2Area of one tube=πdtlt=π×0.05×1.35=0.2121 m2nt=0.6840.2121=3.23≈4 tubes\begin{aligned} A_{tubes} &= \frac{1}{8.8}\left(\frac{P}{\theta} - 12.5S_t\right) = \frac{1}{8.8}\left(\frac{1200}{35} - 12.5\times2.2610\right) = 0.684\ \text{m}^2\\ \text{Area of one tube} &= \pi d_tl_t = \pi\times0.05\times1.35 = 0.2121\ \text{m}^2\\ n_t &= \frac{0.684}{0.2121} = 3.23 \approx 4\ \text{tubes} \end{aligned}

Answer: frame 535 mm high × 623 mm wide × 114 mm deep; regulation ≈ 4.42%; minimum 4 tubes (50 mm dia, 1.35 m).

✓ Answer checked by Claude Sonnet 5.5