- 2068 Magh · 8 marks
500 kVA 3-phase transformer efficiency
Short answer
Full load copper loss is 4488.2 W, iron loss 3050 W. Efficiency at full load is 98.15% and at half load is 97.96% at 0.8 power factor.
A 500-kVA, 3-phase, 50 Hz transformer has a voltage ratio (line voltage) of 33/11 kV and is delta/star connected. The resistances per phase are: High voltage , low voltage and the iron loss is 3050 W. Calculate the value of efficiency at full-load and one-half of full-load respectively at 0.8 p.f.
Copper loss is found from the phase currents and phase resistances of both windings. The HV side is delta (phase current = line current ) and the LV side is star (phase current = line current).
Phase currents at full load
HV (delta), line voltage = phase voltage = 33 kV:
LV (star), line current = phase current:
Full-load copper loss
Iron loss W.
Efficiency at full load (0.8 p.f.)
Efficiency at half load (0.8 p.f.)
Copper loss W.
Answer: and at 0.8 p.f.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- CT ratio for 33/6.6 kV star/delta (400/5) · Switchgear and Protection, chapter 7
- CT ratio for 33/6.6 kV star/delta (300:5) · Switchgear and Protection, chapter 7