Primary current and efficiency of 11 kV/380 V Δ/Y transformer
Short answer
Total load is 40 kW at 0.8 pf, so apparent power = 50 kVA. Primary line current = 50000/(√3×11000) = 2.624 A. Copper losses total 345.31 W, iron loss 1 kW, efficiency = 40000/(40000+1345.31) = 96.75%.
An 11 kV/380 V delta/star 3-phase transformer has balanced star connected 3-phase load of 40 kW at p.f. of 0.8 lagging per phase. Calculate the primary line current. If the transformer has iron loss of 1.0 kW, calculate the approximate efficiency of the transformer. Given that primary winding resistance and leakage reactance are 25 Ω per phase and 40 Ω per phase respectively. Secondary winding resistance and leakage reactance are 0.01 Ω per phase and 0.02 Ω per phase respectively.
Primary is delta (phase voltage = 11 kV, phase current = line current/); secondary is star (phase current = line current). Winding resistances are per phase.
Load apparent power:
Primary line current
Neglecting no-load current, input VA = output VA:
Secondary current
Check by turns ratio: , A.
Copper losses
(Leakage reactances cause no power loss.)
Efficiency
| Quantity | Value |
|---|---|
| Primary line current | 2.624 A |
| Primary phase current | 1.515 A |
| Secondary line/phase current | 75.97 A |
| Copper loss | 345.31 W |
| Efficiency | 96.75% |
Answer: Primary line current = 2.624 A; approximate efficiency = 96.75%.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Rotor copper loss, frequency, current and efficiency of 11 kW motor · Electrical Machines I, chapter 5
- No-load current components, iron loss and core flux · Electrical Machines I, chapter 2
- Efficiency and loading of 50 kVA transformer at 40 kW · Electrical Machines I, chapter 2
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Star load (8+j6) line, phase current · Basic Electrical Engineering, chapter 8
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2