- 2070 Magh · 8 marks
No-load current components, iron loss and core flux
Short answer
Working component Iw = 10×0.3 = 3 A, magnetizing component Iμ = 10×sin(arccos0.3) = 9.54 A. Iron loss = 400×10×0.3 = 1200 W. Maximum flux = 400/(4.44×50×500) = 3.604 mWb, rms flux = 2.548 mWb.
The no-load current of a transformer is 10 A at a p.f. of 0.3 lagging when connected to a 400 V, 50 Hz power supply. If the primary winding has 500 turns, calculate: (a) the magnetizing and working component of no-load current (b) iron loss (c) maximum and rms value of flux in the core.
Given: A, lagging, V, Hz, .
(a) Components of no-load current
Working (core-loss) component, in phase with :
Magnetizing component, lagging by 90°:
Check: A.
V1 ^
|
Iw=3 +- - - - - - - - - - - - -+ I0 = 10 A
| ___...--'
| ___...--'
| _..-' phi0 = 72.5 deg (between V1 and I0)
O-------------------------+----> flux
Im = 9.54 A (along flux)
(b) Iron loss
At no load the input power is almost entirely iron loss:
(c) Maximum and rms flux in the core
From the EMF equation (taking at no load):
For sinusoidal flux:
| Quantity | Value |
|---|---|
| Working component | 3 A |
| Magnetizing component | 9.54 A |
| Iron loss | 1200 W |
| Maximum flux | 3.604 mWb |
| RMS flux | 2.548 mWb |
Answer: (a) A, A; (b) iron loss = 1200 W; (c) mWb, mWb.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Reluctances and air gap flux of two-winding core · Electrical Machines I, chapter 1
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Iron core current for 1 T air-gap flux · Electrical Machine, chapter 1 · asked 2×
- No load current of single phase transformer · Electric Machine Design, chapter 3
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Flux density in circular iron core · Electrical Machines, chapter 1