Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer
Short answer
Iron loss = V1^2/R0 = 250^2/600 = 104.17 W. Maximum efficiency occurs when I1^2 R01 equals iron loss, giving I1 = sqrt(104.17/0.05) = 45.64 A. At unity pf output is 11410.9 W, losses 208.33 W, so maximum efficiency is 98.21%.
A 20 kVA, 250 V / 2500 V, 50 Hz single phase transformer has the following parameters: Ro = 600 ohm, Xo = 180 ohm, R01 = 0.05 ohm and X01 = 0.15 ohm. i) Calculate the iron loss of the transformer. ii) Calculate the primary current at which the efficiency of the transformer will be maximum and also calculate the maximum efficiency.
Given (referred to the 250 V primary): , , , ; V.
(i) Iron loss
Only the core-loss resistance absorbs real power in the shunt branch, so at rated voltage:
(ii) Primary current for maximum efficiency
Maximum efficiency occurs when copper loss = iron loss:
Full-load primary current A, so this is , i.e. about 57% of full load.
Maximum efficiency
Taking unity power factor (not stated; maximum efficiency is normally quoted at upf):
Answer: Iron loss = 104.17 W; maximum efficiency at a primary current of 45.64 A; 98.21% (upf).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 20 kVA 250/2500 V transformer from tests · Electrical Machines I, chapter 2 · asked 3×
- Efficiency and loading of 50 kVA transformer at 40 kW · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 5 kVA transformer at 2 kW load · Electrical Machines I, chapter 2
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- 20 kVA transformer iron loss, efficiency · Electrical Machine, chapter 2
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2
- 20 kVA 250/2500 V test parameters · Electrical Machine, chapter 2 · asked 2×
- 20 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×