- 2071 Bhadra · 8 marks
Efficiency of 25 kVA transformer at half load and overload
Short answer
Assuming unity power factor, the equivalent resistance referred to primary is 2 Ω, full-load copper loss is 258.26 W, and iron loss is 206 W. Efficiency at half load is 97.88% and at 50% overload is 97.94%.
A 25 kVA single phase 2200/220 V transformer has primary winding resistance of 1 Ω, secondary winding resistance 0.01 Ω, primary leakage reactance of 1.5 Ω and secondary leakage reactance of 0.015 Ω. The iron loss of the transformer is 206 W. Calculate the efficiency of the transformer at: (i) Half load (ii) 50% Overload.
Transformation ratio . Power factor is not given, so unity power factor is assumed.
Equivalent resistance and full-load copper loss
Iron loss W (constant). Leakage reactances cause no power loss and are not needed.
(i) Half load ()
(ii) 50% overload ()
| Load | Output | Iron loss | Cu loss | Efficiency |
|---|---|---|---|---|
| Half load | 12.5 kW | 206 W | 64.57 W | 97.88% |
| 50% overload | 37.5 kW | 206 W | 581.10 W | 97.94% |
Answer (upf): (i) 97.88%, (ii) 97.94%.
Maximum efficiency would occur at of full load, which is why the two values on either side are close. At another pf (say 0.8), multiply the outputs by 0.8 and recompute.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Primary current and efficiency of 11 kV/380 V Δ/Y transformer · Electrical Machines I, chapter 2 · asked 3×
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- 20 kVA transformer iron loss, efficiency · Electrical Machine, chapter 2