Efficiency of 25 kVA transformer at half load and overload

Short answer

Assuming unity power factor, the equivalent resistance referred to primary is 2 Ω, full-load copper loss is 258.26 W, and iron loss is 206 W. Efficiency at half load is 97.88% and at 50% overload is 97.94%.

A 25 kVA single phase 2200/220 V transformer has primary winding resistance of 1 Ω, secondary winding resistance 0.01 Ω, primary leakage reactance of 1.5 Ω and secondary leakage reactance of 0.015 Ω. The iron loss of the transformer is 206 W. Calculate the efficiency of the transformer at: (i) Half load (ii) 50% Overload.

Transformation ratio K=2202200=0.1K = \frac{220}{2200} = 0.1. Power factor is not given, so unity power factor is assumed.

Equivalent resistance and full-load copper loss

R01=R1+R2K2=1+0.010.01=2 ΩI1,FL=250002200=11.364 APcu,FL=I1,FL2R01=11.3642×2=258.26 W\begin{aligned} R_{01} &= R_1 + \frac{R_2}{K^2} = 1 + \frac{0.01}{0.01} = 2\ \Omega \\ I_{1,FL} &= \frac{25000}{2200} = 11.364\ \text{A} \\ P_{cu,FL} &= I_{1,FL}^2R_{01} = 11.364^2 \times 2 = 258.26\ \text{W} \end{aligned}

Iron loss Pi=206P_i = 206 W (constant). Leakage reactances cause no power loss and are not needed.

(i) Half load (x=0.5x = 0.5)

Output=0.5×25000×1=12500 WPcu=0.52×258.26=64.57 Wη=1250012500+206+64.57×100=97.88%\begin{aligned} \text{Output} &= 0.5 \times 25000 \times 1 = 12500\ \text{W} \\ P_{cu} &= 0.5^2 \times 258.26 = 64.57\ \text{W} \\ \eta &= \frac{12500}{12500 + 206 + 64.57}\times 100 = 97.88\% \end{aligned}

(ii) 50% overload (x=1.5x = 1.5)

Output=1.5×25000×1=37500 WPcu=1.52×258.26=581.10 Wη=3750037500+206+581.10×100=97.94%\begin{aligned} \text{Output} &= 1.5 \times 25000 \times 1 = 37500\ \text{W} \\ P_{cu} &= 1.5^2 \times 258.26 = 581.10\ \text{W} \\ \eta &= \frac{37500}{37500 + 206 + 581.10}\times 100 = 97.94\% \end{aligned}
LoadOutputIron lossCu lossEfficiency
Half load12.5 kW206 W64.57 W97.88%
50% overload37.5 kW206 W581.10 W97.94%

Answer (upf): (i) 97.88%, (ii) 97.94%.

Maximum efficiency would occur at x=206/258.26=0.893x = \sqrt{206/258.26} = 0.893 of full load, which is why the two values on either side are close. At another pf (say 0.8), multiply the outputs by 0.8 and recompute.

✓ Answer checked by Claude Opus 5.5 (high effort)