500 kVA transformer efficiency full/half load
Short answer
Full-load copper loss 3858 W, iron loss 3000 W. At unity pf: η full load=500000/(500000+6858)=98.65%; η half load=250000/(250000+3965)=98.44%.
A 500 KVA, 50 Hz, 6600 V/400 V, 1-phase transformer have primary and secondary winding resistances are 0.4 Ω and 0.001 Ω respectively. If the iron loss is 3.0 kW, calculate the efficiency at (a) full load (b) half full load.
The efficiency is found from output ÷ (output + iron loss + copper loss). The power factor is not given, so unity power factor is assumed (the result at 0.8 lagging is also shown).
Rated currents
- Primary: I₁ = 500 000 / 6600 = 75.76 A
- Secondary: I₂ = 500 000 / 400 = 1250 A
Copper loss at full load
- Primary: I₁²R₁ = (75.76)² × 0.4 = 2295.7 W
- Secondary: I₂²R₂ = (1250)² × 0.001 = 1562.5 W
- Total P_cu(fl) = 3858.2 W ≈ 3.858 kW
- Iron loss P_i = 3000 W (constant, same at all loads)
(a) Full load (unity pf)
Output = 500 kVA x 1.0 = 500 000 W
Losses = 3000 + 3858.2 = 6858.2 W
Input = 500 000 + 6858.2 = 506 858.2 W
η = 500 000 / 506 858.2 = 0.9865
Efficiency at full load = 98.65 %
(b) Half load (unity pf)
Copper loss varies with (load)², so P_cu = (0.5)² × 3858.2 = 964.5 W.
Output = 250 000 W
Losses = 3000 + 964.5 = 3964.5 W
η = 250 000 / 253 964.5 = 0.9844
Efficiency at half load = 98.44 %
| Load | Power factor | Output (kW) | Cu loss (W) | Iron loss (W) | η (%) |
|---|---|---|---|---|---|
| Full | 1.0 | 500 | 3858.2 | 3000 | 98.65 |
| Half | 1.0 | 250 | 964.5 | 3000 | 98.44 |
| Full | 0.8 lag | 400 | 3858.2 | 3000 | 98.31 |
| Half | 0.8 lag | 200 | 964.5 | 3000 | 98.06 |
Answer: η(full load) ≈ 98.65 %, η(half load) ≈ 98.44 % at unity pf.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Efficiency and loading of 50 kVA transformer at 40 kW · Electrical Machines I, chapter 2
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×