Full-load efficiency of 500 kVA transformer
Short answer
Half-load output 250 kW, input 277.78 kW, so copper loss 25.78 kW. Full-load copper loss = 4×25.78 = 103.11 kW. Iron loss 2 kW. Full-load output 500 kW. Efficiency = 500/(500+2+103.11) = 82.63%.
A single phase 500 kVA transformer working at unity power factor has an efficiency of 90% at half load and iron loss of 2000 watt. Determine efficiency at full load.
Efficiency ; copper loss varies with the square of load.
Step 1: Losses at half load (upf)
Step 2: Copper loss at half and full load
Step 3: Efficiency at full load (upf)
| Load | Output | Iron loss | Cu loss | Efficiency |
|---|---|---|---|---|
| Half | 250 kW | 2 kW | 25.78 kW | 90.00% |
| Full | 500 kW | 2 kW | 103.11 kW | 82.63% |
Answer: Full-load efficiency at unity pf = 82.63%.
(The efficiency falls at full load because copper loss, which grows as the square of load, is much larger than iron loss here. The data are as given in the question; a real 500 kVA transformer would have far higher efficiency.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Half-load efficiency of 200 kVA transformer · Electrical Machines I, chapter 2
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- 100 kVA transformer efficiency at full and half load · Electrical Machines, chapter 2
- 20 kVA transformer iron loss, efficiency · Electrical Machine, chapter 2