Full-load and half-load efficiency of 100 kVA transformer

Short answer

Use efficiency = output/(output + iron loss + x^2 copper loss). At full load unity pf output is 100 kW, losses 2160 W, efficiency 97.89%. At half load 0.8 pf output is 40 kW, losses 1260 W, efficiency 96.95%.

A transformer is rated at 100 kVA. At full load its copper loss is 1200 W and its iron loss is 960 W. Calculate: i) Efficiency at full load, unity power factor ii) Efficiency at half load, 0.8 power factor

η=xScos⁡ϕxScos⁡ϕ+Pi+x2Pcu,FL\eta = \frac{xS\cos\phi}{xS\cos\phi + P_i + x^2P_{cu,FL}}, with S=100S = 100 kVA, Pi=960P_i = 960 W (constant), Pcu,FL=1200P_{cu,FL} = 1200 W.

(i) Full load, unity pf (x=1x = 1)

Output=1×100×1=100 kW=100000 WLosses=960+12×1200=2160 Wη=100000100000+2160×100=97.89%\begin{aligned} \text{Output} &= 1 \times 100 \times 1 = 100\ \text{kW} = 100000\ \text{W} \\ \text{Losses} &= 960 + 1^2 \times 1200 = 2160\ \text{W} \\ \eta &= \frac{100000}{100000 + 2160}\times 100 = 97.89\% \end{aligned}

(ii) Half load, 0.8 pf (x=0.5x = 0.5)

Output=0.5×100×0.8=40 kW=40000 WPcu=0.52×1200=300 WLosses=960+300=1260 Wη=4000040000+1260×100=96.95%\begin{aligned} \text{Output} &= 0.5 \times 100 \times 0.8 = 40\ \text{kW} = 40000\ \text{W} \\ P_{cu} &= 0.5^2 \times 1200 = 300\ \text{W} \\ \text{Losses} &= 960 + 300 = 1260\ \text{W} \\ \eta &= \frac{40000}{40000 + 1260}\times 100 = 96.95\% \end{aligned}
CaseOutputIron lossCu lossEfficiency
FL, upf100 kW960 W1200 W97.89%
½ FL, 0.8 pf40 kW960 W300 W96.95%

Answer: (i) 97.89%, (ii) 96.95%.

Note: maximum efficiency occurs at x=960/1200=0.894x = \sqrt{960/1200} = 0.894, i.e. at about 89.4% of full load, where copper loss equals 960 W.