Short answer

Full load copper loss is 3858.2 W, iron loss 3 kW. Efficiency at full load is 98.65% and at half load is 98.44%, both at unity power factor.

A 500 kVA, 50 Hz, 6600 V/400 V, 1-phase transformer has primary and secondary winding resistances 0.4 Ω0.4\ \Omega and 0.001 Ω0.001\ \Omega respectively. If the iron loss is 3.0 kW, calculate the efficiency at (a) full load (b) half full load.

Efficiency is output divided by input. Output = x×x \times kVA ×\times p.f., and losses = iron loss + x2×x^2 \times full-load copper loss, where xx is the fraction of full load.

The power factor is not given, so unity is assumed first (values for 0.8 lagging are added at the end).

Full-load currents

I1=5000006600=75.76 A,I2=500000400=1250 AI_1 = \frac{500000}{6600} = 75.76\ \text{A}, \qquad I_2 = \frac{500000}{400} = 1250\ \text{A}

Full-load copper loss

Pcu=I12R1+I22R2=(75.76)2(0.4)+(1250)2(0.001)=2295.7+1562.5=3858.2 WP_{cu} = I_1^2R_1 + I_2^2R_2 = (75.76)^2(0.4) + (1250)^2(0.001) = 2295.7 + 1562.5 = 3858.2\ \text{W}

Iron loss Pi=3000P_i = 3000 W (constant at all loads).

(a) Full load (unity p.f.)

η=500000500000+3000+3858.2×100=500000506858.2×100=98.65%\eta = \frac{500000}{500000 + 3000 + 3858.2} \times 100 = \frac{500000}{506858.2}\times 100 = 98.65\%

(b) Half load (unity p.f.)

Copper loss at half load =(0.5)2×3858.2=964.5= (0.5)^2 \times 3858.2 = 964.5 W.

η=250000250000+3000+964.5×100=250000253964.5×100=98.44%\eta = \frac{250000}{250000 + 3000 + 964.5} \times 100 = \frac{250000}{253964.5}\times 100 = 98.44\%

Answer: efficiency at full load =98.65%= 98.65\% and at half load =98.44%= 98.44\% (unity p.f.). At 0.8 p.f. lagging the values are 98.31% (full load) and 98.06% (half load).