500 kVA transformer efficiency, full and half load
Short answer
Full load copper loss is 3858.2 W, iron loss 3 kW. Efficiency at full load is 98.65% and at half load is 98.44%, both at unity power factor.
A 500 kVA, 50 Hz, 6600 V/400 V, 1-phase transformer has primary and secondary winding resistances and respectively. If the iron loss is 3.0 kW, calculate the efficiency at (a) full load (b) half full load.
Efficiency is output divided by input. Output = kVA p.f., and losses = iron loss + full-load copper loss, where is the fraction of full load.
The power factor is not given, so unity is assumed first (values for 0.8 lagging are added at the end).
Full-load currents
Full-load copper loss
Iron loss W (constant at all loads).
(a) Full load (unity p.f.)
(b) Half load (unity p.f.)
Copper loss at half load W.
Answer: efficiency at full load and at half load (unity p.f.). At 0.8 p.f. lagging the values are 98.31% (full load) and 98.06% (half load).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- 100 kVA transformer efficiency at full and half load · Electrical Machines, chapter 2
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- 20 kVA transformer iron loss, efficiency · Electrical Machine, chapter 2
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×