- 2069 Poush · 8 marks
Equivalent circuit and half-load efficiency of 50 kVA transformer
Short answer
From open-circuit test on HV: R0=20833 Ω, X0=9092 Ω, referred to secondary become 208.33 Ω and 90.92 Ω. Short-circuit test gives R01=1.25 Ω, X01=4.841 Ω, referred to secondary: R02=0.0125 Ω, X02=0.0484 Ω. At half load, copper loss=125 W, iron loss=300 W, efficiency (upf)=98.33%.
A 50 kVA, 2500V/250V, 50 Hz single phase transformer draws a current of 0.3 Amp at no load and consumes 300 Watts. When the primary winding is supplied by 100 V with secondary winding short circuited, the primary draws a current of 20 Amp and consumes 500 watts. Calculate the equivalent circuit parameters of the transformer referred to secondary side. Also calculate the efficiency of the transformer at half load.
Interpretation: the no-load test (0.3 A, 300 W) is at rated primary voltage, 2500 V, and the SC test is on the primary (HV) with the secondary shorted. Rated primary current A, so the SC test is at full load. Factor HV to LV: .
Shunt branch (no-load test on HV: 2500 V, 0.3 A, 300 W)
Referred to secondary:
Series branch (SC test on HV: 100 V, 20 A, 500 W)
Referred to secondary:
Equivalent circuit referred to secondary
I1 -> I0 I2
o-----+--------+---[ R02 ]---[ jX02 ]---o
+ | | +
[ R0 ] [ jX0 ] load
V1' | | V2
- | | -
o-----+--------+------------------------o
All values referred to secondary (250 V):
R0 = 208.33 ohm, X0 = 90.92 ohm
R02 = 0.0125 ohm, X02 = 0.0484 ohm
Efficiency at half load
Iron loss W; full-load copper loss W (test at rated current). Assuming unity pf:
Answer: Referred to secondary: , , , ; half-load efficiency (upf) = 98.33%.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- 100 kVA transformer efficiency at full and half load · Electrical Machines, chapter 2
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×