Design: 100 kVA 2200/480 V single phase transformer
Short answer
Limb diameter 224.2 mm, largest stamping 190.6 mm, window 150×300 mm. Frame dimensions: height 694 mm, width 565 mm, depth 191 mm.
Design a 100 kVA, 2,200/480 V, 50 Hz, single phase, core type oil immersed natural cooled transformer. The required data for design are given below: Voltage per turn = 7.5; Maximum flux density in the core = 1.2 Wb/m²; Core type = Cruciform; Current density = 2.5 A/mm²; Window space factor = 0.28; Stacking factor = 0.9; Ratio of window height to width = 2. And, width of duct between LV and core, LV winding, HV winding and duct between HV and LV are 5 mm, 25 mm, 30 mm, 10 mm respectively. Assuming all other required parameters, calculate: (i) Overall dimension of core. (ii) Overall dimension of frame. (iii) Per unit resistance and leakage reactance drop. (iv) Per unit regulation at 0.8 power factor.
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. In a single-phase core type transformer half of each winding is on each limb, so the ampere-turns per limb are . Assumed: yoke area 1.2 × core area (hot-rolled steel), -mm²/m, end clearance 20 mm at each end of the windings.
(i) Overall dimensions of core
Voltage per turn is given: V.
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (single phase):
Winding build (LV next to core):
Radial build (given clearance between core and LV = 5 mm):
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 234.2 | 284.2 |
| HV winding | 304.2 | 364.2 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length of coil, from the output-equation window height: mm.
Mean lengths of turn:
Check: the HV outside diameter is 364.2 mm but from the output equation is only 362.2 mm, so the coils of adjacent limbs would overlap. The window is widened so that there is 10 mm clearance between adjacent HV coils, and its height is increased to keep the given ratio . The coil height stays at = 236.0 mm.
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(ii) Overall dimensions of frame
+-----------------------+ ---
| top yoke | ^
+-----+-----------+-----+ |
|limb | window |limb | H
| | Ww x Hw | | |
+-----+-----------+-----+ |
| bottom yoke | v
+-----------------------+ ---
|<--------- W --------->|
|<----- D ----->|
(iii) Per unit resistance and leakage reactance drop
Currents: A; A.
Resistance referred to HV, with (copper at about 75 °C):
Leakage reactance (per unit), with per limb and axial winding length mm:
(iv) Per unit regulation at 0.8 pf lagging
Answer: = 224 mm, = 281.5 cm²; window 150 × 300 mm; frame 694 × 565 × 191 mm; = 0.0130, = 0.0396; regulation ≈ 3.42%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA single phase, square core · Electric Machine Design, chapter 3
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 100 kVA 2200/220 V transformer · Electrical Machines I, chapter 2 · asked 3×
- Efficiency and loading of 50 kVA transformer at 40 kW · Electrical Machines I, chapter 2
- 25 kVA ideal transformer currents, flux · Basic Electrical and Electronics Engineering, chapter 2