- 2069 Bhadra · 8 marks
Efficiency and loading of 50 kVA transformer at 40 kW
Short answer
Load kVA = 40 kW / 0.65 = 61.54 kVA, I2 = 61.54kVA/2200V = 27.97 A. Iron loss = 200^2/600 = 66.67 W, Cu loss = 27.97^2 *2 = 1564.87 W. Efficiency = 40000/(40000+66.67+1564.87)*100 = 96.08%. The transformer is overloaded by (61.54-50)/50*100 = 23.08%.
A 50 kVA, 200/2200, 50 Hz single phase transformer has the following parameters: R0 = 600 Ohms, X0 = 200 Ohm referred to primary side and R02 = 2 Ohms and X02 = 4 Ohm referred to secondary side. Calculate the efficiency of the transformer when supplying a power of 40 kW to the load with 0.65 pf lagging at rated voltage. Is the transformer over-loaded or under-loaded? Calculate the percentage by which it is over-loaded or under-loaded.
Given: , (primary, 200 V); , (secondary, 2200 V). Load: 40 kW at 0.65 pf lagging, at rated voltage 2200 V.
Load kVA and current
Rated secondary current A.
Losses
Efficiency
Over-load or under-load?
The transformer is rated 50 kVA but supplies 61.54 kVA. The power (40 kW) is below 50 kW, but what matters for heating is the kVA (current), so it is over-loaded:
Same by current: .
| Quantity | Value |
|---|---|
| Load kVA | 61.54 kVA |
| Secondary current | 27.97 A |
| Iron loss | 66.67 W |
| Copper loss | 1564.87 W |
| Efficiency | 96.08% |
| Loading | 23.08% overload |
Answer: Efficiency = 96.08%; the transformer is over-loaded by 23.08% because of the low power factor.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Efficiency of 5 kVA transformer at 2 kW load · Electrical Machines I, chapter 2
- OC/SC test of 2200/110 V, 40 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- Primary current and efficiency of 100 kVA Δ/Y transformer · Electrical Machines I, chapter 2
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- 20 kVA 2200/220 V tests, efficiency · Electrical Machine, chapter 2
- 10 kVA 200/400 V LV-side parameters · Electrical Machine, chapter 2
- 10 kVA 200/400 V tests, parameters on LV side · Electrical Machines, chapter 2