- 2073 Bhadra · 8 marks
20 kVA 2200/220 V tests, efficiency
Short answer
Referred to primary: Ro=38.72 kΩ, Xo=23.36 kΩ, R01=4.07 Ω, X01=4.78 Ω. Maximum efficiency at full load (unity pf) is 98.0% occurring at 61% load. Half-load efficiency at 0.8 pf lagging is 97.45%.
The following test results were obtained on a 20 kVA, 2200/220 V, 50 Hz single phase transformer Open circuit test: 220 V, 1.1 A, 125 W Short circuit test: 52.7 V, 8.4 A, 287 W i) Calculate the equivalent circuit parameters referred to primary side and draw the equivalent circuits ii) Calculate maximum efficiency at full load iii) Calculate the efficiency at half full load with 0.8 power factor lagging
Given: 20 kVA, 2200/220 V. OC (LV side): 220 V, 1.1 A, 125 W. SC (HV side): 52.7 V, 8.4 A, 287 W. Primary = HV side (2200 V); K = 220/2200 = 0.1.
(i) Parameters referred to the primary
Shunt branch (the OC test is on the LV side, so transfer it to the HV side with 1/K² = 100):
cos φ0 = 125/(220 × 1.1) = 0.5165
Iw = 1.1 × 0.5165 = 0.568 A ; Iμ = √(1.1² − 0.568²) = 0.942 A
On LV: Ro = 220/0.568 = 387.2 Ω ; Xo = 220/0.942 = 233.6 Ω
On HV: Ro = 387.2 × 100 = 38 720 Ω ; Xo = 233.6 × 100 = 23 357 Ω
Series branch (the SC test is on the HV side, so the values are used directly):
Z01 = 52.7/8.4 = 6.274 Ω ; R01 = 287/8.4² = 4.067 Ω
X01 = √(6.274² − 4.067²) = 4.777 Ω
Equivalent circuit (referred to primary)
o──┬──────┬──────/\/\/────(((────────o
│ │ 4.067 Ω 4.777 Ω
38 720 23 357 load
Ω Ω V2'
o──┴──────┴────────────────────────o
This is the approximate equivalent circuit: the shunt branch is moved to the input terminals, and the series branch follows it.
(ii) Maximum efficiency
Rated HV current I1 = 20 000/2200 = 9.091 A
Full-load Cu loss = 287 × (9.091/8.4)² = 336.2 W
Iron loss Pi = 125 W
x (max η) = √(Pi/Pcu) = √(125/336.2) = 0.610
Output at max η, unity pf = 0.610 × 20 000 = 12 196 W
η_max = 12 196/(12 196 + 2 × 125) = 97.99 %
(Full-load efficiency at unity pf: 20 000/(20 000 + 125 + 336.2) = 97.75 %.)
(iii) Half load, 0.8 lagging
Output = 0.5 × 20 000 × 0.8 = 8000 W
Cu loss = 0.5² × 336.2 = 84.0 W
η = 8000/(8000 + 125 + 84.0) = 97.45 %
Answer: (i) Ro = 38.72 kΩ, Xo = 23.36 kΩ, R01 = 4.07 Ω, X01 = 4.78 Ω; (ii) η_max ≈ 98.0 % (at unity pf, about 61 % load); (iii) η ≈ 97.45 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- 20 kVA 2200/220 V, LV-side circuit · Electrical Machine, chapter 2
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 100 kVA 2200/220 V transformer · Electrical Machines I, chapter 2 · asked 3×
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2
- OC and SC tests to build transformer equivalent circuit · Electrical Machines I, chapter 2
- 25 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2