20 kVA 2200/220 V tests, efficiency

Short answer

Referred to primary: Ro=38.72 kΩ, Xo=23.36 kΩ, R01=4.07 Ω, X01=4.78 Ω. Maximum efficiency at full load (unity pf) is 98.0% occurring at 61% load. Half-load efficiency at 0.8 pf lagging is 97.45%.

The following test results were obtained on a 20 kVA, 2200/220 V, 50 Hz single phase transformer Open circuit test: 220 V, 1.1 A, 125 W Short circuit test: 52.7 V, 8.4 A, 287 W i) Calculate the equivalent circuit parameters referred to primary side and draw the equivalent circuits ii) Calculate maximum efficiency at full load iii) Calculate the efficiency at half full load with 0.8 power factor lagging

Given: 20 kVA, 2200/220 V. OC (LV side): 220 V, 1.1 A, 125 W. SC (HV side): 52.7 V, 8.4 A, 287 W. Primary = HV side (2200 V); K = 220/2200 = 0.1.

(i) Parameters referred to the primary

Shunt branch (the OC test is on the LV side, so transfer it to the HV side with 1/K² = 100):

cos φ0 = 125/(220 × 1.1) = 0.5165
Iw = 1.1 × 0.5165 = 0.568 A ;  Iμ = √(1.1² − 0.568²) = 0.942 A
On LV:  Ro = 220/0.568 = 387.2 Ω ;  Xo = 220/0.942 = 233.6 Ω
On HV:  Ro = 387.2 × 100 = 38 720 Ω ;  Xo = 233.6 × 100 = 23 357 Ω

Series branch (the SC test is on the HV side, so the values are used directly):

Z01 = 52.7/8.4 = 6.274 Ω ;  R01 = 287/8.4² = 4.067 Ω
X01 = √(6.274² − 4.067²) = 4.777 Ω

Equivalent circuit (referred to primary)

 o──┬──────┬──────/\/\/────(((────────o
    │      │     4.067 Ω   4.777 Ω
  38 720  23 357                  load
    Ω      Ω                      V2'
 o──┴──────┴────────────────────────o

This is the approximate equivalent circuit: the shunt branch is moved to the input terminals, and the series branch follows it.

(ii) Maximum efficiency

Rated HV current I1 = 20 000/2200 = 9.091 A
Full-load Cu loss  = 287 × (9.091/8.4)² = 336.2 W
Iron loss Pi = 125 W
x (max η) = √(Pi/Pcu) = √(125/336.2) = 0.610
Output at max η, unity pf = 0.610 × 20 000 = 12 196 W
η_max = 12 196/(12 196 + 2 × 125) = 97.99 %

(Full-load efficiency at unity pf: 20 000/(20 000 + 125 + 336.2) = 97.75 %.)

(iii) Half load, 0.8 lagging

Output = 0.5 × 20 000 × 0.8 = 8000 W
Cu loss = 0.5² × 336.2 = 84.0 W
η = 8000/(8000 + 125 + 84.0) = 97.45 %

Answer: (i) Ro = 38.72 kΩ, Xo = 23.36 kΩ, R01 = 4.07 Ω, X01 = 4.78 Ω; (ii) η_max ≈ 98.0 % (at unity pf, about 61 % load); (iii) η ≈ 97.45 %.