OC and SC tests to build transformer equivalent circuit
Short answer
Perform OC test on LV side at rated voltage to obtain R0 and X0 (shunt branch). Perform SC test on HV side at rated current to obtain R01 and X01 (series branch). Refer shunt parameters to primary by multiplying by (6600/220)^2 = 900. The equivalent circuit: shunt branch (R0' || X0') across primary, then series R01+jX01.
Describe no load test and short circuit test of a single phase transformer having following ratings: 10 kVA, 6600 V/220 V. How the results obtained from the tests can be utilized to develop the equivalent circuit of the transformer referred to primary side?
The no-load (open-circuit) test and short-circuit test find the equivalent-circuit parameters and losses of the 10 kVA, 6600/220 V transformer without loading it. Rated currents: HV A; LV A.
No-load (OC) test
0-220 V +--(A)--[W]--+------+ +-----o
variac | | LV | || | HV open
50 Hz (V) | 220V | || | 6600 V
+------------+------+ +-----o
- Done on the LV (220 V) side, HV open. The LV side is used because 220 V is safe and easy to supply and measure; the HV terminals still have 6600 V on them and must be guarded.
- Apply rated voltage, 220 V, at rated frequency. Read , , .
- is small (about 2-5% of 45.45 A, i.e. 1-2 A), so copper loss is negligible and = iron loss.
Calculations:
These are on the LV side.
Short-circuit test
low V +--(A)--[W]--+------+ +-----+
variac | | HV | || | LV | thick
50 Hz (V) | 6600V| || | 220V| short
+------------+------+ +-----+
- Done on the HV (6600 V) side, LV shorted by a thick link. The HV side is used because rated current there is only 1.515 A and the needed voltage (5-10% of 6600 V, i.e. about 330-660 V) is easy to measure; on the LV side we would need 45 A at only 11-22 V.
- Raise voltage slowly from zero until rated current 1.515 A flows. Read , , .
- Flux is very low, so iron loss is negligible and = full-load copper loss.
Calculations (HV side, which is the primary here):
Developing the equivalent circuit referred to primary (6600 V)
- and come directly from the SC test because it was on the HV (primary) side.
- and from the OC test are on the LV side, so refer them to the primary by multiplying by
i.e. , . 3. Draw the approximate equivalent circuit: shunt branch () across the 6600 V input, followed by in series, and load referred to primary .
o---+---------+---[ R01 ]---[ jX01 ]---o
| | +
[ R0' ] [ jX0' ] V2' = 30 V2
| | -
o---+---------+------------------------o
Example: if the OC test gives 220 V, 1.2 A, 90 W, then , A, (LV), so on the 6600 V side.
From the same results: iron loss and full-load copper loss give efficiency at any load, and , give voltage regulation.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 100 kVA 2200/220 V transformer · Electrical Machines I, chapter 2 · asked 3×
- Equivalent circuit of 10 kVA 250/1000 V transformer · Electrical Machines I, chapter 2 · asked 2×
- OC/SC test of 2200/110 V, 40 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Induction motor equivalent circuit from no-load and blocked rotor tests · Electrical Machines I, chapter 5
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- 10 kVA 250/1000 V tests, equivalent circuit · Electrical Machines, chapter 2
- 20 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×
- 25 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×