OC and SC tests to build transformer equivalent circuit

Short answer

Perform OC test on LV side at rated voltage to obtain R0 and X0 (shunt branch). Perform SC test on HV side at rated current to obtain R01 and X01 (series branch). Refer shunt parameters to primary by multiplying by (6600/220)^2 = 900. The equivalent circuit: shunt branch (R0' || X0') across primary, then series R01+jX01.

Describe no load test and short circuit test of a single phase transformer having following ratings: 10 kVA, 6600 V/220 V. How the results obtained from the tests can be utilized to develop the equivalent circuit of the transformer referred to primary side?

The no-load (open-circuit) test and short-circuit test find the equivalent-circuit parameters and losses of the 10 kVA, 6600/220 V transformer without loading it. Rated currents: HV =10000/6600=1.515= 10000/6600 = 1.515 A; LV =10000/220=45.45= 10000/220 = 45.45 A.

No-load (OC) test

  0-220 V  +--(A)--[W]--+------+     +-----o
  variac   |            |  LV  | ||  |  HV  open
  50 Hz   (V)           | 220V | ||  | 6600 V
           +------------+------+     +-----o
  • Done on the LV (220 V) side, HV open. The LV side is used because 220 V is safe and easy to supply and measure; the HV terminals still have 6600 V on them and must be guarded.
  • Apply rated voltage, 220 V, at rated frequency. Read V0V_0, I0I_0, P0P_0.
  • I0I_0 is small (about 2-5% of 45.45 A, i.e. 1-2 A), so copper loss is negligible and P0P_0 = iron loss.

Calculations:

cos⁡ϕ0=P0V0I0,Iw=I0cos⁡ϕ0,Iμ=I0sin⁡ϕ0,R0=V0Iw,X0=V0Iμ\cos\phi_0 = \frac{P_0}{V_0I_0}, \quad I_w = I_0\cos\phi_0, \quad I_\mu = I_0\sin\phi_0, \quad R_0 = \frac{V_0}{I_w}, \quad X_0 = \frac{V_0}{I_\mu}

These are on the LV side.

Short-circuit test

  low V    +--(A)--[W]--+------+     +-----+
  variac   |            |  HV  | ||  |  LV | thick
  50 Hz   (V)           | 6600V| ||  | 220V| short
           +------------+------+     +-----+
  • Done on the HV (6600 V) side, LV shorted by a thick link. The HV side is used because rated current there is only 1.515 A and the needed voltage (5-10% of 6600 V, i.e. about 330-660 V) is easy to measure; on the LV side we would need 45 A at only 11-22 V.
  • Raise voltage slowly from zero until rated current 1.515 A flows. Read VscV_{sc}, IscI_{sc}, PscP_{sc}.
  • Flux is very low, so iron loss is negligible and PscP_{sc} = full-load copper loss.

Calculations (HV side, which is the primary here):

Z01=VscIsc,R01=PscIsc2,X01=Z012−R012Z_{01} = \frac{V_{sc}}{I_{sc}}, \quad R_{01} = \frac{P_{sc}}{I_{sc}^2}, \quad X_{01} = \sqrt{Z_{01}^2 - R_{01}^2}

Developing the equivalent circuit referred to primary (6600 V)

  1. R01R_{01} and X01X_{01} come directly from the SC test because it was on the HV (primary) side.
  2. R0R_0 and X0X_0 from the OC test are on the LV side, so refer them to the primary by multiplying by
(6600220)2=302=900\left(\frac{6600}{220}\right)^2 = 30^2 = 900

i.e. R0′=900R0R_0' = 900R_0, X0′=900X0X_0' = 900X_0. 3. Draw the approximate equivalent circuit: shunt branch (R0′∥X0′R_0' \parallel X_0') across the 6600 V input, followed by R01+jX01R_{01} + jX_{01} in series, and load referred to primary ZL′=900ZLZ_L' = 900Z_L.

 o---+---------+---[ R01 ]---[ jX01 ]---o
     |         |                        +
  [ R0' ]   [ jX0' ]               V2' = 30 V2
     |         |                        -
 o---+---------+------------------------o

Example: if the OC test gives 220 V, 1.2 A, 90 W, then cos⁡ϕ0=0.341\cos\phi_0 = 0.341, Iw=0.409I_w = 0.409 A, R0=538 ΩR_0 = 538\ \Omega (LV), so R0′=484 kΩR_0' = 484\ \text{k}\Omega on the 6600 V side.

From the same results: iron loss and full-load copper loss give efficiency at any load, and R01R_{01}, X01X_{01} give voltage regulation.