25 kVA 250/2500 V tests, equivalent circuit

Short answer

Referred to primary: R0=595.2 Ω, X0=187.2 Ω, R01=0.05 Ω, X01=0.1414 Ω.

A 25 kVA, 250 V/2500 V, 50 Hz single phase transformer gave the following test results: No load test (on L.V. side): 250 V, 1.4 A, 105 watts Short circuit test (on H.V. side): 120 V, 8 A, 320 watts Calculate the equivalent circuit parameters referred to primary side and draw the equivalent circuit.

Given: 25 kVA, 250 V/2500 V. Primary = LV (250 V), secondary = HV (2500 V), K=10K = 10, K2=100K^2 = 100.

Open-circuit test (on the LV side)

The no-load power is almost entirely core loss, so the shunt branch is found from it.

cos⁡ϕ0=P0V0I0=105250×1.4=0.3Iw=I0cos⁡ϕ0=0.42 A,Iμ=I02−Iw2=1.336 AR0=V0Iw=595.2 Ω,X0=V0Iμ=187.2 Ω(on the LV side)\begin{aligned} \cos\phi_0 &= \frac{P_0}{V_0I_0} = \frac{105}{250\times1.4} = 0.3 \\ I_w &= I_0\cos\phi_0 = 0.42\ \text{A},\qquad I_\mu = \sqrt{I_0^2 - I_w^2} = 1.336\ \text{A} \\ R_0 &= \frac{V_0}{I_w} = 595.2\ \Omega,\qquad X_0 = \frac{V_0}{I_\mu} = 187.2\ \Omega\quad(\text{on the LV side}) \end{aligned}

Short-circuit test (on the HV side)

At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.

Zsc=VscIsc=1208=15 ΩRsc=PscIsc2=32082=5 ΩXsc=Zsc2−Rsc2=14.14 Ω(on the HV side)\begin{aligned} Z_{sc} &= \frac{V_{sc}}{I_{sc}} = \frac{120}{8} = 15\ \Omega \\ R_{sc} &= \frac{P_{sc}}{I_{sc}^2} = \frac{320}{8^2} = 5\ \Omega \\ X_{sc} &= \sqrt{Z_{sc}^2 - R_{sc}^2} = 14.14\ \Omega\quad(\text{on the HV side}) \end{aligned}

Referring to the LV side

The turns ratio is K=2500/250=10K = 2500/250 = 10, so K2=100K^2 = 100. Impedances are multiplied by K2K^2 when moved from LV to HV, and divided by K2K^2 when moved from HV to LV.

Req=5÷100=0.05 ΩXeq=14.14÷100=0.1414 Ω\begin{aligned} R_{eq} &= 5 \div 100 = 0.05\ \Omega \\ X_{eq} &= 14.14 \div 100 = 0.1414\ \Omega \end{aligned}

Equivalent circuit referred to the LV side

   Req=0.05 ohm   Xeq=0.141 ohm
 o--+-----/\/\/\-----UUUU------o
    |                          
   [R0=595.2] [X0=187.2]   Load
    |      (in parallel)
 o--+---------------------------o

Req=0.05 ΩR_{eq} = 0.05\ \Omega, Xeq=0.1414 ΩX_{eq} = 0.1414\ \Omega (Zeq=0.15 ΩZ_{eq} = 0.15\ \Omega), shunt branch R0=595.2 ΩR_0 = 595.2\ \Omega in parallel with X0=187.2 ΩX_0 = 187.2\ \Omega.

Answer (referred to primary): R0=595.2 ΩR_0 = 595.2\ \Omega, X0=187.2 ΩX_0 = 187.2\ \Omega, R01=0.05 ΩR_{01} = 0.05\ \Omega, X01=0.1414 ΩX_{01} = 0.1414\ \Omega.

Note: the 25 kVA rating is not needed for the parameters. The SC test current of 8 A is the rated HV current only for a 20 kVA unit (a 25 kVA unit has 10 A on the HV side), so the test is below full load. The equivalent circuit parameters are the same, because they do not depend on the test current if the transformer is linear. The copper loss at the true full load would be 320×(10/8)2=500320\times(10/8)^2 = 500 W.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Electrical Machines chapter 2 questions →