- Asked 2/21
- 2071 Magh (old course) · 8 marks
25 kVA 250/2500 V tests, equivalent circuit
Short answer
Referred to primary: R0=595.2 Ω, X0=187.2 Ω, R01=0.05 Ω, X01=0.1414 Ω.
A 25 kVA, 250 V/2500 V, 50 Hz single phase transformer gave the following test results: No load test (on L.V. side): 250 V, 1.4 A, 105 watts Short circuit test (on H.V. side): 120 V, 8 A, 320 watts Calculate the equivalent circuit parameters referred to primary side and draw the equivalent circuit.
Given: 25 kVA, 250 V/2500 V. Primary = LV (250 V), secondary = HV (2500 V), , .
Open-circuit test (on the LV side)
The no-load power is almost entirely core loss, so the shunt branch is found from it.
Short-circuit test (on the HV side)
At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.
Referring to the LV side
The turns ratio is , so . Impedances are multiplied by when moved from LV to HV, and divided by when moved from HV to LV.
Equivalent circuit referred to the LV side
Req=0.05 ohm Xeq=0.141 ohm
o--+-----/\/\/\-----UUUU------o
|
[R0=595.2] [X0=187.2] Load
| (in parallel)
o--+---------------------------o
, (), shunt branch in parallel with .
Answer (referred to primary): , , , .
Note: the 25 kVA rating is not needed for the parameters. The SC test current of 8 A is the rated HV current only for a 20 kVA unit (a 25 kVA unit has 10 A on the HV side), so the test is below full load. The equivalent circuit parameters are the same, because they do not depend on the test current if the transformer is linear. The copper loss at the true full load would be W.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 20 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×
- Equivalent circuit of 20 kVA 250/2500 V transformer from tests · Electrical Machines I, chapter 2 · asked 3×
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- 8 kVA 400/120 V tests, parameters on HV side · Electrical Machines, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- 10 kVA 250/1000 V tests, equivalent circuit · Electrical Machines, chapter 2
- 20 kVA 250/2500 V test parameters · Electrical Machine, chapter 2 · asked 2×
- 8 kVA 400/120 V tests, half-load efficiency · Electrical Machine, chapter 2
- OC and SC tests to build transformer equivalent circuit · Electrical Machines I, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×