- 2071 Magh · 8 marks
8 kVA 400/120 V tests, half-load efficiency
Short answer
Referred to HV side: Ro=2133 Ω, Xo=337.5 Ω, R01=0.275 Ω, X01=0.387 Ω. At half load and 0.8 pf lagging, efficiency = 96.9%.
The following test results were obtained for open circuit and short circuit tests on a 8 kVA, 400/120 V, 50 Hz transformer: Open-circuit Test (LV Side): 120 V, 4 A, 75 W Short-circuit Test (HV Side): 9.5 V, 20 A, 110 W Calculate the equivalent circuit parameters referred to high voltage side. Also calculate the efficiency at half full load and 0.8 power factor lagging load.
Given: 8 kVA, 400/120 V, 50 Hz. OC test (LV): 120 V, 4 A, 75 W. SC test (HV): 9.5 V, 20 A, 110 W. HV side is 400 V; K = 120/400 = 0.3.
Shunt branch
On the LV side:
cos φ0 = 75/(120 × 4) = 0.15625
Iw = 4 × 0.15625 = 0.625 A ; Iμ = √(4² − 0.625²) = 3.951 A
Ro = 120/0.625 = 192 Ω ; Xo = 120/3.951 = 30.37 Ω
Refer to the HV side (× 1/K² = 11.11):
Ro(HV) = 192 × 11.11 = 2133 Ω
Xo(HV) = 30.37 × 11.11 = 337.5 Ω
Series branch (SC test is on the HV side)
Z01 = 9.5/20 = 0.475 Ω
R01 = 110/20² = 0.275 Ω
X01 = √(0.475² − 0.275²) = 0.387 Ω
Equivalent circuit (HV side)
R=0.275Ω X=0.387Ω
o──┬────┬───/\/\/───────(((────────o
│ │
2133Ω 337.5Ω load
│ │ V2'
o──┴────┴───────────────────────────o
Efficiency at half load, 0.8 pf lagging
Rated HV current = 8000/400 = 20 A, the same as the SC test current, so the full-load copper loss is 110 W.
Output = 0.5 × 8000 × 0.8 = 3200 W
Iron loss = 75 W
Cu loss = 0.5² × 110 = 27.5 W
η = 3200/(3200 + 75 + 27.5) = 96.9 %
Answer: Ro = 2133 Ω, Xo = 337.5 Ω, R01 = 0.275 Ω, X01 = 0.387 Ω (HV side); η at half load, 0.8 pf = 96.9 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 8 kVA 400/120 V tests, parameters on HV side · Electrical Machines, chapter 2
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- 20 kVA 2200/220 V, LV-side circuit · Electrical Machine, chapter 2
- 10 kVA 200/400 V tests, parameters on LV side · Electrical Machines, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2
- 25 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×