8 kVA 400/120 V tests, parameters on HV side

Short answer

Referred to HV side: shunt branch R0=2133 Ω, X0=337.5 Ω; series branch Req=0.275 Ω, Xeq=0.3873 Ω. Efficiency at half load, 0.8 pf lag: η=96.90%.

The following test results were obtained for open circuit and short circuit tests on a 8 kVA, 400/120 V, 50 Hz transformer: Open-circuit Test (LV Side): 120 V, 4 A, 75 W Short-circuit Test (HV Side): 9.5 V, 20 A, 110 W Calculate the equivalent circuit parameters referred to high voltage side. Also calculate the efficiency at half full load and 0.8 power factor lagging load.

Given: 8 kVA, 400/120 V. HV = 400 V, LV = 120 V, K=400/120=3.333K = 400/120 = 3.333, K2=11.11K^2 = 11.11. Rated HV current =8000/400=20= 8000/400 = 20 A, so the SC test is at full load.

Open-circuit test (on the LV side)

The no-load power is almost entirely core loss, so the shunt branch is found from it.

cos⁡ϕ0=P0V0I0=75120×4=0.1562Iw=I0cos⁡ϕ0=0.625 A,Iμ=I02−Iw2=3.951 AR0=V0Iw=192 Ω,X0=V0Iμ=30.37 Ω(on the LV side)\begin{aligned} \cos\phi_0 &= \frac{P_0}{V_0I_0} = \frac{75}{120\times4} = 0.1562 \\ I_w &= I_0\cos\phi_0 = 0.625\ \text{A},\qquad I_\mu = \sqrt{I_0^2 - I_w^2} = 3.951\ \text{A} \\ R_0 &= \frac{V_0}{I_w} = 192\ \Omega,\qquad X_0 = \frac{V_0}{I_\mu} = 30.37\ \Omega\quad(\text{on the LV side}) \end{aligned}

Short-circuit test (on the HV side)

At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.

Zsc=VscIsc=9.520=0.475 ΩRsc=PscIsc2=110202=0.275 ΩXsc=Zsc2−Rsc2=0.3873 Ω(on the HV side)\begin{aligned} Z_{sc} &= \frac{V_{sc}}{I_{sc}} = \frac{9.5}{20} = 0.475\ \Omega \\ R_{sc} &= \frac{P_{sc}}{I_{sc}^2} = \frac{110}{20^2} = 0.275\ \Omega \\ X_{sc} &= \sqrt{Z_{sc}^2 - R_{sc}^2} = 0.3873\ \Omega\quad(\text{on the HV side}) \end{aligned}

Referring to the HV side

The turns ratio is K=400/120=3.333K = 400/120 = 3.333, so K2=11.11K^2 = 11.11. Impedances are multiplied by K2K^2 when moved from LV to HV, and divided by K2K^2 when moved from HV to LV.

R0′=192×11.11=2133 ΩX0′=30.37×11.11=337.5 Ω\begin{aligned} R_0' &= 192 \times 11.11 = 2133\ \Omega \\ X_0' &= 30.37 \times 11.11 = 337.5\ \Omega \end{aligned}

Equivalent circuit referred to the HV side

   Req=0.275 ohm   Xeq=0.387 ohm
 o--+-----/\/\/\-----UUUU------o
    |                          
   [R0=2133] [X0=337.5]   Load
    |      (in parallel)
 o--+---------------------------o

Req=0.275 ΩR_{eq} = 0.275\ \Omega, Xeq=0.3873 ΩX_{eq} = 0.3873\ \Omega (Zeq=0.475 ΩZ_{eq} = 0.475\ \Omega), shunt branch R0=2133 ΩR_0 = 2133\ \Omega in parallel with X0=337.5 ΩX_0 = 337.5\ \Omega.

Efficiency at half load, 0.8 pf lagging

Pout=0.5×8000×0.8=3200 WPcu=0.52×110=27.5 W,Pi=75 Wη=32003200+27.5+75×100=96.90%\begin{aligned} P_{out} &= 0.5\times8000\times0.8 = 3200\ \text{W} \\ P_{cu} &= 0.5^2\times110 = 27.5\ \text{W},\qquad P_i = 75\ \text{W} \\ \eta &= \frac{3200}{3200 + 27.5 + 75}\times100 = 96.90\% \end{aligned}

Answer (referred to HV): R0=2133 ΩR_0 = 2133\ \Omega, X0=337.5 ΩX_0 = 337.5\ \Omega, Req=0.275 ΩR_{eq} = 0.275\ \Omega, Xeq=0.3873 ΩX_{eq} = 0.3873\ \Omega; efficiency at half load =96.90%= 96.90\%