- 2071 Magh · 8 marks
8 kVA 400/120 V tests, parameters on HV side
Short answer
Referred to HV side: shunt branch R0=2133 Ω, X0=337.5 Ω; series branch Req=0.275 Ω, Xeq=0.3873 Ω. Efficiency at half load, 0.8 pf lag: η=96.90%.
The following test results were obtained for open circuit and short circuit tests on a 8 kVA, 400/120 V, 50 Hz transformer: Open-circuit Test (LV Side): 120 V, 4 A, 75 W Short-circuit Test (HV Side): 9.5 V, 20 A, 110 W Calculate the equivalent circuit parameters referred to high voltage side. Also calculate the efficiency at half full load and 0.8 power factor lagging load.
Given: 8 kVA, 400/120 V. HV = 400 V, LV = 120 V, , . Rated HV current A, so the SC test is at full load.
Open-circuit test (on the LV side)
The no-load power is almost entirely core loss, so the shunt branch is found from it.
Short-circuit test (on the HV side)
At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.
Referring to the HV side
The turns ratio is , so . Impedances are multiplied by when moved from LV to HV, and divided by when moved from HV to LV.
Equivalent circuit referred to the HV side
Req=0.275 ohm Xeq=0.387 ohm
o--+-----/\/\/\-----UUUU------o
|
[R0=2133] [X0=337.5] Load
| (in parallel)
o--+---------------------------o
, (), shunt branch in parallel with .
Efficiency at half load, 0.8 pf lagging
Answer (referred to HV): , , , ; efficiency at half load
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- 10 kVA 200/400 V tests, parameters on LV side · Electrical Machines, chapter 2
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 250/2500 V transformer from tests · Electrical Machines I, chapter 2 · asked 3×
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 20 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×
- 8 kVA 400/120 V tests, half-load efficiency · Electrical Machine, chapter 2
- 10 kVA 200/400 V LV-side parameters · Electrical Machine, chapter 2
- 20 kVA 2200/220 V, LV-side circuit · Electrical Machine, chapter 2
- 20 kVA 250/2500 V test parameters · Electrical Machine, chapter 2 · asked 2×