- 2070 Magh · 8 marks
20 kVA 2200/220 V, LV-side circuit
Short answer
Referred to LV side: Ro=387.2 Ω, Xo=233.6 Ω, R02=0.0407 Ω, X02=0.0478 Ω (Z02=0.0627 Ω).
The following test results were obtained on a 20 kVA, 2200/220 V, 50 Hz single phase transformer: Open-circuit Test (LV Side): 220 V, 1.1 A, 125 W Short-circuit Test (HV Side): 52.7 V, 8.4 A, 287 W Calculate the equivalent circuit referred to L.V side and draw the equivalent circuit.
Given: 20 kVA, 2200/220 V. OC test on the LV side: 220 V, 1.1 A, 125 W. SC test on the HV side: 52.7 V, 8.4 A, 287 W. The turns ratio is 2200/220 = 10. The HV (2200 V) winding is the primary, so the series values on the HV side are R01, X01 and on the LV side R02, X02.
Shunt branch (the OC test is on the LV side, so no transfer is needed)
cos φ0 = 125/(220 × 1.1) = 0.5165
Iw = 1.1 × 0.5165 = 0.568 A
Iμ = √(1.1² − 0.568²) = 0.942 A
Ro = 220/0.568 = 387.2 Ω
Xo = 220/0.942 = 233.6 Ω
Series branch (the SC test is on the HV side, so refer it to the LV side by dividing by 10² = 100)
On HV: Z01 = 52.7/8.4 = 6.274 Ω
R01 = 287/8.4² = 4.067 Ω
X01 = √(6.274² − 4.067²) = 4.777 Ω
On LV: Z02 = 0.06274 Ω ; R02 = 0.04067 Ω ; X02 = 0.04777 Ω
Equivalent circuit referred to the LV side
R02=0.0407Ω X02=0.0478Ω
o──┬─────┬────/\/\/────────(((──────o
│ │
387.2Ω 233.6Ω load
│ │ V2 (LV)
o──┴─────┴───────────────────────────o
Answer: Ro = 387.2 Ω, Xo = 233.6 Ω, R02 = 0.0407 Ω, X02 = 0.0478 Ω (Z02 = 0.0627 Ω), all on the LV side.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- 20 kVA 2200/220 V tests, efficiency · Electrical Machine, chapter 2
- Equivalent circuit of 100 kVA 2200/220 V transformer · Electrical Machines I, chapter 2 · asked 3×
- 8 kVA 400/120 V tests, parameters on HV side · Electrical Machines, chapter 2
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- 20 kVA 250/2500 V tests, equivalent circuit · Electrical Machines, chapter 2 · asked 2×