10 kVA 200/400 V tests, parameters on LV side
Short answer
Referred to LV side: shunt branch R0=333.3 Ω, X0=173.4 Ω; series branch Req=0.0556 Ω, Xeq=0.1747 Ω.
A 10 kVA, 200/400 V, 50 Hz, 1 phase, transformer gave the following test results: OC test (HV open): 200 V, 1.3 A, 120 W SC test (LV short): 22 V, 30 A, 200 W Determine shunt and series branch parameters referred to Low Voltage Side and hence draw equivalent circuit diagram also.
Reading of the tests: "HV open" means the OC test is done on the LV winding at its rated 200 V. "LV short" means the LV winding is short-circuited while the supply is applied to the HV (400 V) winding, so the SC readings are on the HV side. Hence , .
Open-circuit test (on the LV side)
The no-load power is almost entirely core loss, so the shunt branch is found from it.
Short-circuit test (on the HV side)
At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.
Referring to the LV side
The turns ratio is , so . Impedances are multiplied by when moved from LV to HV, and divided by when moved from HV to LV.
Equivalent circuit referred to the LV side
Req=0.0556 ohm Xeq=0.175 ohm
o--+-----/\/\/\-----UUUU------o
|
[R0=333.3] [X0=173.4] Load
| (in parallel)
o--+---------------------------o
, (), shunt branch in parallel with .
Answer (referred to LV side): shunt branch , ; series branch ,
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 8 kVA 400/120 V tests, parameters on HV side · Electrical Machines, chapter 2
- OC/SC test of 2200/110 V, 40 kVA transformer · Electrical Machines I, chapter 2
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2
- Why iron loss neglected in SC test; parameters · Electrical Machines, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 10 kVA 200/400 V LV-side parameters · Electrical Machine, chapter 2
- 10 kVA 200/400 V test parameters · Electrical Machine, chapter 2
- 8 kVA 400/120 V tests, half-load efficiency · Electrical Machine, chapter 2
- 4 kVA 200/400 V test parameters · Electrical Machine, chapter 2