Why iron loss neglected in SC test; parameters
Short answer
Short circuit test uses only 5–10% rated voltage, so flux and iron loss are negligible. Equivalent circuit parameters referred to primary (400 V): Req = 1.08 Ω, Xeq = 1.269 Ω, R0 = 1455 Ω, X0 = 573.3 Ω.
Why is iron loss neglected in short circuit test of transformer? A single phase 400/200 V, 50 Hz transformer gave the following test results: Open circuit Test: 200 V, 1.5 A, 110 W on LV side Short circuit Test: 30 V, 18 A, 350 W on HV side Calculate the equivalent circuit parameters referred to primary side and draw the equivalent circuit showing calculated parameters.
Why iron loss is neglected in the SC test
In the short-circuit test only a small voltage (about 5 to 10% of the rated value) is applied, just enough to circulate full-load current in the shorted secondary. The core flux is proportional to the applied voltage, so it is only about 5 to 10% of normal flux. Core loss varies approximately as the square of the flux, so it becomes about 0.25 to 1% of the rated core loss, which is negligible. The wattmeter therefore reads the copper loss alone. In this problem of rated voltage, so the core loss is about W against 350 W.
Equivalent circuit parameters (referred to the primary)
Primary = HV side (400 V), secondary = LV side (200 V).
Open-circuit test (on the LV side)
The no-load power is almost entirely core loss, so the shunt branch is found from it.
Short-circuit test (on the HV side)
At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.
Referring to the HV side
The turns ratio is , so . Impedances are multiplied by when moved from LV to HV, and divided by when moved from HV to LV.
Equivalent circuit referred to the HV side
Req=1.08 ohm Xeq=1.27 ohm
o--+-----/\/\/\-----UUUU------o
|
[R0=1455] [X0=573.3] Load
| (in parallel)
o--+---------------------------o
, (), shunt branch in parallel with .
The shunt branch carries referred to the primary A.
Answer (referred to primary): , , , .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 10 kVA 200/400 V tests, parameters on LV side · Electrical Machines, chapter 2
- 8 kVA 400/120 V tests, parameters on HV side · Electrical Machines, chapter 2
- OC/SC test of 2200/110 V, 40 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2
- 10 kVA 200/400 V LV-side parameters · Electrical Machine, chapter 2
- 10 kVA 200/400 V test parameters · Electrical Machine, chapter 2
- 20 kVA 2200/220 V, LV-side circuit · Electrical Machine, chapter 2
- 4 kVA 200/400 V test parameters · Electrical Machine, chapter 2