Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer
Short answer
Iron loss is V1^2/R0=96.8 W. Maximum efficiency occurs when copper loss equals iron loss, giving primary current 49.19 A, about 54% of full load, and maximum efficiency 98.24% at unity pf.
A 20 kVA, 220V/2200V, 50 Hz single phase transformer has the following parameters: R0 = 500 ohm, X0 = 160 ohm, R01 = 0.04 ohm and X01 = 0.1 ohm. (i) Calculate the iron loss of the transformer. (ii) Calculate the primary current at which the efficiency for the transformer will be maximum and also calculate the maximum efficiency.
Given (referred to the 220 V primary): , , , . Rated primary voltage V.
(i) Iron loss
Iron loss is the power taken by the core-loss resistance at rated voltage:
( only carries the magnetising current, which takes no real power.)
(ii) Current for maximum efficiency
Efficiency is maximum when copper loss equals iron loss:
Full-load primary current is A, so maximum efficiency occurs at , i.e. about 54% of full load.
Maximum efficiency
Assuming unity power factor (pf not given, and maximum efficiency is normally quoted at upf):
Answer: Iron loss = 96.8 W; maximum efficiency occurs at a primary current of 49.19 A; 98.24% at unity pf.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- Efficiency and loading of 50 kVA transformer at 40 kW · Electrical Machines I, chapter 2
- Equivalent circuit of 100 kVA 2200/220 V transformer · Electrical Machines I, chapter 2 · asked 3×
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- 20 kVA 2200/220 V tests, efficiency · Electrical Machine, chapter 2
- 20 kVA transformer iron loss, efficiency · Electrical Machine, chapter 2
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2