Design: 500 kVA single phase transformer with tubes
Short answer
Core diameter 309.7 mm, window 173.5 × 433.8 mm, yoke 263.3 mm square. Overall frame 960.4 × 746.5 × 263.3 mm. Plain tank temperature rise 79.7 °C; 42 tubes of 50 mm diameter, 1.5 m long keep mean oil rise within 35 °C (14 per long side, 7 per short side).
For a 500 kVA, 50 Hz, 6600/400 V, single phase core type, oil immersed, natural cooled power transformer, the design parameters are: Constant for output voltage per turn = 0.8; Resistivity of copper = 0.021 Ω-mm²/m; Maximum flux density in the core = 1.5 Wb/m²; Current density = 2.75 A/mm²; Core type = Cruciform; Window space factor = 0.27; Stacking factor = 0.9; Ratio of window height to width = 2.5; Ratio of yoke height to width = 1; Axial depth of LV winding = 402 mm; Axial depth of HV winding = 377.5 mm; Inside diameter of LV winding = 310 mm; Outer diameter of LV winding = 348 mm; Inside diameter of HV winding = 360 mm; Outside diameter of HV winding = 418 mm. Calculate: i) Dimension of the core, window and yoke ii) Overall dimension of the frame iii) Per unit regulation at 0.8 pf lagging iv) Taking iron loss = 1460 W, copper loss = 3865 W at full load, height of tank = 1.6 m, length of tank = 1.05 m, width of tank = 0.62 m, find the temperature rise. If the mean temperature rise of oil is not to rise 35°C, find the necessary number of tubes and also show its arrangement.
Standard method (A.K. Sawhney). Half of each winding is on each limb, so ampere-turns per limb are . Yoke: with depth equal to the largest stamping width. Axial length for reactance = mean of 402 and 377.5 mm = 389.75 mm.
i) Dimensions of core, window and yoke
Voltage per turn, ( in kVA):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (single phase):
Check: HV outside diameter 418 mm < = 483 mm and coil height 402 mm < = 434 mm, so the windings fit. The LV inside diameter (310 mm) only just clears the core circle (309.7 mm), so the LV is wound directly on a thin insulating cylinder over the core.
Yoke
Yoke height equal to its depth (), with depth equal to the largest stamping width:
ii) Overall dimensions of frame
+-----------------------+ ---
| top yoke | ^
+-----+-----------+-----+ |
|limb | window |limb | H
| | Ww x Hw | | |
+-----+-----------+-----+ |
| bottom yoke | v
+-----------------------+ ---
|<--------- W --------->|
|<----- D ----->|
iii) Per unit regulation at 0.8 pf lagging
Currents: A; A.
Radial depths: mm (LV), mm (HV), duct mm. = 389.75 mm.
Mean lengths of turn:
Resistance referred to HV, with (copper at about 75 °C):
Leakage reactance (per unit), with per limb and axial winding length mm:
iv) Temperature rise and cooling tubes
Total loss W. Tubes assumed 50 mm in diameter and 1.5 m long (tank height 1.6 m).
Tank walls (top and bottom neglected), dissipation 12.5 W/m²°C (6 radiation + 6.5 convection):
This exceeds 35 °C, so tubes are needed. Tubes improve convection by 35%: W/m²°C.
Arrangement of tubes: with 50 mm tubes at 75 mm centre-to-centre spacing, one row round the tank can hold about tubes on each long side and on each short side. So 42 tubes are placed in a single row: 14 on each long side and 7 on each short side ().
o o o o o o o o o o o o o o (14)
+-------------------------------+
o | | o
o | | o
o | TANK (top view) | o
(7)o | 1.05 m x 0.62 m | o (7)
o | | o
o | | o
o | | o
+-------------------------------+
o o o o o o o o o o o o o o (14)
o = cooling tube, 50 mm dia, 75 mm pitch
Answer: = 310 mm; window 174 × 434 mm; yoke 263 × 263 mm; frame 960 × 747 × 263 mm; regulation ≈ 1.73%; plain tank rise ≈ 79.7 °C; 42 tubes needed.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Temperature rise and tubes for 500 kVA transformer · Electric Machine Design, chapter 3 · asked 2×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2