Design: 150 kVA 6600/400 V distribution transformer
Short answer
Core d=181.2 mm, cruciform (a=154.0, b=96.0 mm); window 139.8×349.5 mm; yoke depth 154.0 mm height 159.2 mm; frame H=667.9 mm, W=796.1 mm, depth 154.0 mm. Per-unit R and X drops partially computed; regulation not finalized.
The design parameters for a 150 kVA, 50 Hz, 6600/400 V, 3-phase, delta/star, core type, oil immersed natural cooled distribution transformer are given below. Max. flux density in core = 1.35 Wb/m²; Current density in conductor = 2.75 A/mm²; Constant for output voltage per turn = 0.45; Core type = cruciform two stepped; Window space factor = 0.27; Stacking factor = 0.9; Ratio of window height to width = 2.5; Take hot rolled steel and area of yoke is 20% greater than gross area of core; Width of LV, HV winding and duct between them are 20 mm, 25 mm and 15 mm respectively. Assuming all other required parameters, calculate: (i) Dimension of the core, window and yoke (ii) Overall dimension of the frame (iii) Per unit resistance and leakage reactance drop (iv) Per unit voltage regulation at 0.85 pf
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. Assumed: core-to-LV clearance 5 mm, end clearance 20 mm, -mm²/m.
(i) Dimensions of core, window and yoke
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Yoke:
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(ii) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
(iii) Per unit resistance and leakage reactance drop
Turns and conductors
Phase voltages: LV (star) V; HV (delta) V.
Phase currents: A; A.
Winding build
Radial build (assumed clearance between core and LV = 5 mm):
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 191.2 | 231.2 |
| HV winding | 261.2 | 311.2 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length mm.
Mean lengths of turn:
Check: HV outside diameter 311 mm vs = 321 mm. Adjacent HV coils have about 10 mm clearance, so the coils fit.
Resistance referred to HV, with (copper at about 75 °C):
Leakage reactance (per unit), with per limb and axial winding length mm:
(iv) Per unit regulation at 0.85 pf lagging
Answer: = 181 mm, window 140 × 350 mm, yoke 159 × 154 mm; frame 668 × 796 × 154 mm; = 0.0164, = 0.0499; regulation ≈ 4.02%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 150 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- 150 kVA transformer: max efficiency load · Electrical Machines, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2