150 kVA transformer: max efficiency load

An 11000/230 V, 150 kVA, 50 Hz, single-phase transformer has a core loss of 1.4 kW and full load copper loss of 1.6 kW. Determine (i) the kVA load for maximum efficiency and the maximum efficiency (ii) the efficiency at half load and full load at 0.8 p.f. lagging.

Given: 150 kVA, 11000/230 V, core loss Pi=1.4P_i = 1.4 kW, full-load copper loss Pcu,fl=1.6P_{cu,fl} = 1.6 kW.

(i) Load for maximum efficiency

At maximum efficiency, copper loss equals core loss:

x2Pcu,fl=Pi⇒x=1.41.6=0.9354x^2P_{cu,fl} = P_i \Rightarrow x = \sqrt{\frac{1.4}{1.6}} = 0.9354 kVA at ηmax=0.9354×150=140.3 kVA\text{kVA at } \eta_{max} = 0.9354\times150 = 140.3\ \text{kVA}

The power factor is not given for this part; taking the same 0.8 lagging as in part (ii):

Pout=140.3×0.8=112.25 kWLosses=2Pi=2.8 kWηmax=112.25112.25+2.8×100=97.57%\begin{aligned} P_{out} &= 140.3\times0.8 = 112.25\ \text{kW} \\ \text{Losses} &= 2P_i = 2.8\ \text{kW} \\ \eta_{max} &= \frac{112.25}{112.25 + 2.8}\times100 = 97.57\% \end{aligned}

(At unity power factor the same load would give ηmax=140.31140.31+2.8×100=98.04%\eta_{max} = \dfrac{140.31}{140.31 + 2.8}\times100 = 98.04\%.)

(ii) Efficiency at 0.8 pf lagging

Full load (x=1x = 1):

η=150×0.8150×0.8+1.4+1.6×100=120123×100=97.56%\eta = \frac{150\times0.8}{150\times0.8 + 1.4 + 1.6}\times100 = \frac{120}{123}\times100 = 97.56\%

Half load (x=0.5x = 0.5): output =0.5×150×0.8=60= 0.5\times150\times0.8 = 60 kW, copper loss =0.25×1.6=0.4= 0.25\times1.6 = 0.4 kW.

η=6060+1.4+0.4×100=6061.8×100=97.09%\eta = \frac{60}{60 + 1.4 + 0.4}\times100 = \frac{60}{61.8}\times100 = 97.09\%

Answer: (i) 140.3 kVA, ηmax=97.57%\eta_{max} = 97.57\% (at 0.8 pf); (ii) full load 97.56%, half load 97.09%