- 2081 Bhadra · 7+7+4 marks
Design: 150 kVA 11000/440 V transformer with tubes
Short answer
Frame: H=676.7 mm, W=825.5 mm, depth=157.6 mm. Core d=175.1 mm, three-stepped; window 158.9×365.4 mm; yoke depth 157.6 mm height 155.6 mm. Regulation and tube count not fully provided.
The design parameters for a 150 kVA, 50 Hz, 11000/440 V, 3-phase, delta/star, core type, oil immersed natural cooled distribution transformer are given below. Constant for output voltage per turn = 0.45; Maximum flux density in the core = 1.35 Wb/m²; Current density in conductor = 2.5 A/mm²; Take 5% more current density in HV winding; Core type = three stepped; Window space factor = 0.25; Stacking factor = 0.9; Ratio of window height to width = 2.3; Take hot rolled steel and area of yoke is 20% greater than gross area of core; Width of LV winding = 20 mm; Width of HV winding = 25 mm; Width of duct between HV and LV winding = 15 mm; Mean height of coil = 231.25 mm; Resistivity of copper = 0.021 Ω-mm²/m; Height of tank = 1150 mm; Width of tank = 425 mm; Length of tank = 1050 mm; Total losses = 2850 W. Assuming all other required parameters, calculate: (i) Overall dimension of frame. (ii) Per unit voltage regulation at 0.85 pf. (iii) The minimum number of tubes of diameter 50 mm with average length of 1.05 m required for maintaining the mean temperature within the permissible limit. The mean temperature of the oil should not exceed 35°C. The rate of heat dissipation from plain wall is 6.5 and 6 W/m²-°C for convection and radiation respectively. The provision of tubes improves the rate of heat dissipation by 35%.
Standard method (A.K. Sawhney, A Course in Electrical Machine Design): , net core area ratio for the core type, output equation for the window, yoke depth = width of largest stamping. Assumed: clearance between core and LV = 5 mm (not given), A/mm².
Core and window
Voltage per turn, ( in kVA, total for 3 phases):
For a three-stepped core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Yoke (20% more than gross core area):
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(i) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
(ii) Per unit voltage regulation at 0.85 pf lagging
Turns and conductors
Phase voltages: LV (star) V; HV (delta) V.
Phase currents: A; A.
Winding build
Radial build (assumed clearance between core and LV = 5 mm):
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 185.1 | 225.1 |
| HV winding | 255.1 | 305.1 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length mm (given mean coil height).
Mean lengths of turn:
Check: HV outside diameter 305 mm vs = 334 mm. Adjacent HV coils have about 29 mm clearance, so the coils fit.
Resistance
Resistance referred to HV, with (copper at about 75 °C):
Reactance
Leakage reactance (per unit), with per limb and axial winding length mm:
Regulation
(iii) Number of cooling tubes
Total loss = 2850 W, tank 1.15 m × 0.425 m × 1.05 m (H × W × L), mean oil rise 35 °C, tubes 50 mm diameter, 1.05 m long.
Tank walls (top and bottom neglected), dissipation 12.5 W/m²°C (6 radiation + 6.5 convection):
This exceeds 35 °C, so tubes are needed. Tubes improve convection by 35%: W/m²°C.
Answer: frame 677 × 825 × 158 mm; regulation ≈ 4.67% ( = 0.0149, = 0.0647); 27 tubes.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 150 kVA 11000/420 V distribution transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 25 kVA 11000/433 V distribution transformer · Electric Machine Design, chapter 3
- Design: 25 kVA transformer frame, regulation, tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- 150 kVA transformer: max efficiency load · Electrical Machines, chapter 2
- Delta capacitor per phase for 50 kW motor · Basic Electrical Engineering, chapter 8