Delta capacitor per phase for 50 kW motor
Short answer
Reactive power reduction from 48.19 to 24.21 kVAR, requiring 23.98 kVAR total. Delta-connected capacitors see 415 V; capacitance per phase is 147.7 μF.
A 415 V, 3 phase, 50 HZ induction motor takes 50 KW power from supply mains at 0.72 power factor lagging. A bank of capacitors is connected in delta across the line to improve the overall power factor. Calculate the capacitance per phase in order to raise the power factor to 0.9 lagging.
Given P = 50 kW, V_L = 415 V, f = 50 Hz, cos φ₁ = 0.72 lagging, cos φ₂ = 0.9 lagging. The capacitors are delta connected.
Reactive power
- tan φ₁ = tan(cos⁻¹ 0.72) = 0.9638, so Q₁ = 50 × 0.9638 = 48.19 kVAR
- tan φ₂ = tan(cos⁻¹ 0.9) = 0.4843, so Q₂ = 50 × 0.4843 = 24.21 kVAR
- Capacitor reactive power: Q_c = 48.19 − 24.21 = 23.98 kVAR
Per phase: Q_c/3 = 7.99 kVAR.
Capacitance per phase (delta)
Voltage across each capacitor = line voltage = 415 V.
Q_phase = ω C V² ⟹ C = 7992 / (314.16 × 415²) = 7992 / (5.411 × 10⁷)
C = 147.7 μF per phase
(Check of line current: 50 000/(√3 × 415 × 0.72) = 96.6 A before and 77.3 A after correction.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitor bank for 3-phase motor pf · Basic Electrical Engineering, chapter 8
- Delta connected coils line current and power · Basic Electrical Engineering, chapter 8
- Capacitor for power factor correction of lamp · Basic Electrical Engineering, chapter 7
- Delta load phase currents, power, line currents · Basic Electrical Engineering, chapter 8
- Capacitor for single-phase motor pf correction · Basic Electrical Engineering, chapter 7
- Delta load (15+j20) phase and line currents · Basic Electrical Engineering, chapter 8
- Capacitor bank for 340 kW induction motor · Utilization of Electrical Energy, chapter 6 · asked 2×
- Line pf of 35 kW induction motor with capacitors · Utilization of Electrical Energy, chapter 6 · asked 3×
- Three coils in delta, 415 V · Basic Electrical and Electronics Engineering, chapter 1
- 2.2 kW cage motor designed for best power factor · Electric Machine Design, chapter 4 · asked 2×