Capacitor bank for 3-phase motor pf
Short answer
Reactive power required to improve pf from 0.8 to 0.9 lag is 15.94 kVAR total, 5.31 kVAR per phase. Star capacitor per phase: 317 μF; delta capacitor per phase: 105.7 μF.
A 400V, 50 Hz, 3 phase induction motor takes 60 KW power from supply mains at 0.8 power factor lagging. Calculate the capacitance per phase and KVAR rating per phase of capacitor in order to improve the power factor to 0.9 lagging using (i) star connected capacitor bank and (ii) Delta connected capacitor bank.
Given P = 60 kW, V_L = 400 V, f = 50 Hz, cos φ₁ = 0.8 lag, cos φ₂ = 0.9 lag.
Reactive power
- tan φ₁ = tan(36.87°) = 0.75, so Q₁ = 60 × 0.75 = 45.0 kVAR
- tan φ₂ = tan(25.84°) = 0.4843, so Q₂ = 60 × 0.4843 = 29.06 kVAR
- Total capacitor kVAR: Q_c = 45.0 − 29.06 = 15.94 kVAR
- Per phase: 15.94/3 = 5.31 kVAR (the rating per phase is the same for star or delta bank)
(i) Star-connected bank
Voltage across each capacitor = 400/√3 = 230.9 V.
C_Y = (Q_c/3) / (ω V_ph²) = 5314 / (314.16 × 230.9²) = 5314 / (1.6753 × 10⁷)
C_Y = 317 μF per phase
(ii) Delta-connected bank
Voltage across each capacitor = 400 V.
C_Δ = 5314 / (314.16 × 400²) = 5314 / (5.0265 × 10⁷)
C_Δ = 105.7 μF per phase
(C_Y = 3 C_Δ, so the delta bank needs only one third of the capacitance.)
Line current of the motor falls from 60 000/(√3 × 400 × 0.8) = 108.3 A to 96.2 A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Delta capacitor per phase for 50 kW motor · Basic Electrical Engineering, chapter 8
- Capacitor for single-phase motor pf correction · Basic Electrical Engineering, chapter 7
- Capacitor for power factor correction of lamp · Basic Electrical Engineering, chapter 7
- Capacitor for 6 kW load pf improvement · Basic Electrical Engineering, chapter 7
- Capacitor bank for 340 kW induction motor · Utilization of Electrical Energy, chapter 6 · asked 2×
- Induction motor improving power factor · Industrial Power Distribution and Illumination, chapter 10
- 2.2 kW cage motor designed for best power factor · Electric Machine Design, chapter 4 · asked 2×
- Power/light sub-circuits and cable for 50 kW, 60 kW · Industrial Power Distribution and Illumination, chapter 5 · asked 4×