- 2074 Bhadra · 8 marks
Induction motor improving power factor
Short answer
Motor supplies 302.9 kVAR leading. Its kVA rating is 319 kVA, operating at 0.313 leading power factor.
An induction motor improves the power factor of a load of 500 KW from 0.707 lagging to 0.95 lagging. Simultaneously the motor carries a load of 100 KW. Find: a) The leading KVAR supplied by motor b) KVA rating of the motor and c) Power factor at which the motor operates
Note: an induction motor always draws lagging kVAR, so it cannot improve the power factor. The machine that does this while also driving a mechanical load is an over-excited synchronous motor; the solution below treats the motor as such.
Given: load P1 = 500 kW at 0.707 lag; motor load Pm = 100 kW; final pf = 0.95 lag.
Reactive power of the original load:
tan(cos⁻¹0.707) = 1.0003
Q1 = 500 × 1.0003 = 500.15 kVAR (lagging)
Combined load after adding motor:
P = 500 + 100 = 600 kW
tan(cos⁻¹0.95) = 0.3287
Q = 600 × 0.3287 = 197.21 kVAR (lagging)
a) Leading kVAR supplied by motor
Qm = Q1 − Q = 500.15 − 197.21 = 302.94 kVAR (leading)
b) kVA rating of the motor
Sm = √(Pm² + Qm²) = √(100² + 302.94²)
= √(10 000 + 91 773) = 319.02 kVA
c) Power factor of the motor
cos φm = Pm / Sm = 100 / 319.02 = 0.313 (leading)
Phasor (power triangle) picture:
Q (kVAR)
load ↑ 500.15 lag
|
motor ↓ 302.94 lead
-----------------------
total 197.21 lag → pf 0.95 at 600 kW
Answer: (a) 302.9 kVAR leading, (b) about 319 kVA, (c) about 0.31 leading.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- kVAr and techno-economic analysis for 1000 kVA transformer · Industrial Power Distribution and Illumination, chapter 10
- Capacitor kVAR to bring cable current to rating · Industrial Power Distribution and Illumination, chapter 10 · asked 2×
- PF correction for 1250 kVA generator (+150 kW) · Industrial Power Distribution and Illumination, chapter 10
- Optimum pf under two-part tariff (200 kW) · Industrial Power Distribution and Illumination, chapter 10
- PF improvement of 490 kW load with demand charge · Industrial Power Distribution and Illumination, chapter 10 · asked 2×
- Leading kVAR supplied by synchronous motor · Electric Machines II, chapter 2
- Capacitor bank for 340 kW induction motor · Utilization of Electrical Energy, chapter 6 · asked 2×
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2
- kW, kVA, kVAR in parallel impedances · Basic Electrical Engineering, chapter 7 · asked 2×
All Industrial Power Distribution and Illumination chapter 10 questions →