- 2076 Bhadra · 8 marks
kVAr and techno-economic analysis for 1000 kVA transformer
Short answer
Capacitor required is 482.23 kVAr. kVA demand reduces from 800 to 505.26 kVA (saving 294.74 kVA). Investment NRs 7.23 lakh, monthly demand saving NRs 61,895 yields payback of about 11.7 months; technically and economically justified.
In a industry transformer has following details: a) Rating of the transformer = 1000 kVA b) Average loading on transformer = 800 kVA c) Power factor = 0.6 lag d) No load loss = 1600 watt e) Full load loss = 13500 watt Calculate the kVAr require to improve p.f. to 0.95, reduction of kVA demand and techno-economic analysis, if the cost of capacitor bank with controlling switches NRs. 1500/kVAr and demand charge is NRs. 210/kVA/month.
Given: transformer 1000 kVA, average load 800 kVA at 0.6 pf (lag), no-load loss 1.6 kW, full-load loss 13.5 kW, capacitor cost NRs 1500/kVAr, demand charge NRs 210/kVA/month.
kVAr required to improve pf to 0.95
P = 800 × 0.6 = 480 kW
Q₁ = 800 × 0.8 = 640 kVAr
Q₂ = 480 × tan(cos⁻¹0.95) = 480 × 0.3287
= 157.77 kVAr
Qc = 640 − 157.77 = 482.23 kVAr
(In practice a standard 500 kVAr APFC panel would be used; the calculation uses 482.23 kVAr.)
Reduction of kVA demand
S₂ = 480 / 0.95 = 505.26 kVA
ΔS = 800 − 505.26 = 294.74 kVA
Reduction in transformer loss
No-load loss (1.6 kW) stays the same; copper loss ∝ (load/rating)²:
Cu loss before = 13.5 × (0.8)² = 8.640 kW
Cu loss after = 13.5 × (0.5053)² = 3.446 kW
Reduction = 5.194 kW
If the transformer runs all year (8760 h): 5.194 × 8760 = 45 496 kWh saved per year (extra benefit; energy rate not given).
Techno-economic analysis
Cost of capacitor bank = 482.23 × 1500 = NRs 723 347
Demand charge saving = 294.74 × 210 = NRs 61 895 / month
= NRs 742 737 / year
Simple payback = 723 347 / 61 895
= 11.7 months ≈ 0.97 year
| Item | Value |
|---|---|
| Capacitor needed | 482.23 kVAr |
| kVA demand reduced | 294.74 kVA |
| Cu loss reduced | 5.19 kW |
| Investment | NRs 7.23 lakh |
| Annual demand saving | NRs 7.43 lakh |
| Payback | ≈ 11.7 months |
The investment is recovered in less than one year from demand charge alone; the loss reduction, lower current, better voltage and released transformer capacity (about 295 kVA) are extra gains. So the pf improvement is technically and economically justified.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- PF improvement of 1020 kVA factory load · Industrial Power Distribution and Illumination, chapter 10 · asked 2×
- Capacitor kVAR to bring cable current to rating · Industrial Power Distribution and Illumination, chapter 10 · asked 2×
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- Induction motor improving power factor · Industrial Power Distribution and Illumination, chapter 10
- Transformer size for given industry (figure) · Industrial Power Distribution and Illumination, chapter 4 · asked 2×
- Transformer selection for apartment, residence, industry · Industrial Power Distribution and Illumination, chapter 4
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- 100 kVA transformer efficiency at full and half load · Electrical Machines, chapter 2
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2
All Industrial Power Distribution and Illumination chapter 10 questions →