Transformer size for given industry (figure)
Short answer
For an assumed industry with 5 motors (11 kW each) and lighting/heating loads, compute motor kVA = 11/(0.88×0.85)=14.71 kVA. Apply Ku (0.75 motors, 1.0 others), then Ks per board (0.8, 0.9) and MDB (0.9). Demand = 62.39 kVA, with 20% margin = 74.87 kVA, select 100 kVA transformer.
Calculate the size of transformer for the given industry (attached figure) considering factor of maximum utilization Ku and factor of simultaneity Ks. [The attached figure is not included in the source scans.]
The figure is not available, so the method is shown on an assumed industry with two sub-distribution boards; the same steps apply to any given layout.
Assumed loads
- SDB-A: 5 motors, each 11 kW, η = 0.88, pf = 0.85
- SDB-B: lighting 8 kVA, two heaters of 10 kVA each
Factors used (IEC / Schneider Electric guide)
- Ku (factor of maximum utilization): motors 0.75; lighting and heating 1.0.
- Ks (factor of simultaneity) for a board with n circuits: 2–3 → 0.9, 4–5 → 0.8, 6–9 → 0.7, 10 and above → 0.6.
Step 1: rated kVA of each motor
kVA = kW / (η × pf) = 11 / (0.88 × 0.85) = 14.71 kVA
Step 2: utilized power with Ku
| Load | Rated kVA | Ku | Utilized kVA |
|---|---|---|---|
| Motor (each, 5 nos) | 14.71 | 0.75 | 11.03 |
| Total motors | 73.53 | - | 55.15 |
| Lighting | 8 | 1.0 | 8.0 |
| Heaters 2 × 10 | 20 | 1.0 | 20.0 |
Step 3: apply Ks at each board
SDB-A = 55.15 × Ks(5 circuits = 0.8) = 44.12 kVA
SDB-B = (8 + 20) × Ks(3 circuits = 0.9) = 25.20 kVA
MDB = (44.12 + 25.20) × Ks(2 = 0.9) = 69.32 × 0.9
= 62.39 kVA
Step 4: future expansion and selection
Required = 62.39 × 1.2 (20 % margin) = 74.87 kVA
Answer: select a 100 kVA, 11/0.4 kV transformer (next standard rating above 74.87 kVA; standard sizes 50, 100, 160, 200, 250 kVA ...).
Remarks
- Connected load is 101.5 kVA but maximum demand is only about 62 kVA; sizing on connected load would over-size the transformer and lower its efficiency.
- If the figure gives Ku and Ks values directly, use those instead of the typical values.
- Check that the largest motor's starting kVA does not cause an excessive dip (usually < 10–15 %) on the chosen transformer.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Selecting distribution transformer size using Ku and Ks · Industrial Power Distribution and Illumination, chapter 4 · asked 3×
- Short note: Factor of maximum utilization Ku · Industrial Power Distribution and Illumination, chapter 1
- Short note: Factor of simultaneity Ks · Industrial Power Distribution and Illumination, chapter 1
- Maximum demand and need to calculate it · Industrial Power Distribution and Illumination, chapter 1
- Transformer size for four blocks · Industrial Power Distribution and Illumination, chapter 4
All Industrial Power Distribution and Illumination chapter 4 questions →