Short note: Factor of maximum utilization Ku
Short answer
Factor of maximum utilization (ku) = actual maximum power used / rated power (ku ≤ 1). Accounts for equipment not running at full rating (e.g., motors at 0.75, lighting/heating at 1). Applied per load before simultaneity factor ks. Example: 10 kVA motor with ku=0.75 counted as 7.5 kVA for board demand calculation.
Write a short note on factor of maximum utilization (Ku).
The factor of maximum utilization (ku) is the ratio of the maximum power actually taken by a load in normal operation to its rated (installed) power:
ku = Actual maximum power used / Rated power (ku ≤ 1)
It is used in industrial load estimation (IEC method) because equipment rarely runs at full rating. For example, a motor is chosen with a margin and usually runs at about 75% of its rating.
Typical values:
- Motors in industry: ku ≈ 0.75
- Incandescent lighting and heating: ku = 1
- Socket outlets: depends on what is plugged in
Example: a 10 kVA motor with ku = 0.75 is counted as 7.5 kVA when the demand of its distribution board is worked out. ku is applied to each individual load, before the factor of simultaneity ks is applied to groups.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Selecting distribution transformer size using Ku and Ks · Industrial Power Distribution and Illumination, chapter 4 · asked 3×
- Load factor and demand factor numerical · Industrial Power Distribution and Illumination, chapter 1
- Connected load, MD, demand, diversity, load factor · Industrial Power Distribution and Illumination, chapter 1
- Demand factor and diversity factor of substation · Industrial Power Distribution and Illumination, chapter 1
- Connected load, MD, demand factor, load factor · Industrial Power Distribution and Illumination, chapter 1
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- Ku-band HEMT amplifier: stability and gains · RF and Microwave Engineering, chapter 6
- Load, capacity and utilization factors · Hydropower Engineering, chapter 3
- Arc furnace power factor and time to melt steel · Utilization of Electrical Energy, chapter 5
- Maximum speed and distance before braking (2.5 km) · Utilization of Electrical Energy, chapter 4
All Industrial Power Distribution and Illumination chapter 1 questions →