Short answer

Arc resistance is 0.015 ohm, total resistance 0.0175 ohm, Z 0.0182 ohm; pf is 0.9615 lagging and power drawn is 840 kW. Heat needed for 2.5 t steel is 1,786,750 kJ; with 70% efficiency useful power is 588 kW, so time is 3039 s, about 50.6 min.

The following data relate to a 3-phase electric arc Furnace: Current drawn = 4000 A Arc Voltage = 60 V Resistance of transformer referred to Secondary = 0.0025 Ω Reactance of transformer referred to Secondary = 0.0050 Ω i) Calculate the power factor and kW drawn from the supply. ii) If the overall efficiency of the furnace is 70%, find the time required to melt 2.5 tonnes of Steel if Latent heat of Steel = 37.2 kJ/kg, Specific heat of Steel = 0.5 kJ/kg-K, Melting Point of Steel = 1370°C Initial temperature of Steel = 15°C

Each phase of the arc furnace is the arc (a pure resistance) in series with the transformer resistance and reactance.

Given (per phase): I=4000I = 4000 A, Varc=60V_{arc} = 60 V, Rt=0.0025 ΩR_t = 0.0025\ \Omega, Xt=0.0050 ΩX_t = 0.0050\ \Omega.

i) Power factor and kW drawn

Rarc=VarcI=604000=0.015 ΩRtotal=0.015+0.0025=0.0175 ΩZ=0.01752+0.0052=0.01820 Ωcos⁡ϕ=RtotalZ=0.01750.01820=0.9615 laggingP=3I2Rtotal=3×40002×0.0175=840 kW\begin{aligned} R_{arc} &= \frac{V_{arc}}{I} = \frac{60}{4000} = 0.015\ \Omega \\ R_{total} &= 0.015 + 0.0025 = 0.0175\ \Omega \\ Z &= \sqrt{0.0175^2 + 0.005^2} = 0.01820\ \Omega \\ \cos\phi &= \frac{R_{total}}{Z} = \frac{0.0175}{0.01820} = 0.9615\ \text{lagging} \\ P &= 3I^2R_{total} = 3 \times 4000^2 \times 0.0175 = 840\ \text{kW} \end{aligned}

(Arc power alone =3×60×4000=720= 3 \times 60 \times 4000 = 720 kW; the other 120 kW is transformer copper loss.)

ii) Time to melt 2.5 tonnes of steel

Heat required:

H=m[c(θm−θi)+L]=2500[0.5(1370−15)+37.2]=2500×714.7=1 786 750 kJ\begin{aligned} H &= m\left[c(\theta_m - \theta_i) + L\right] \\ &= 2500\left[0.5(1370 - 15) + 37.2\right] \\ &= 2500 \times 714.7 = 1\,786\,750\ \text{kJ} \end{aligned}

Useful power with 70% overall efficiency:

Puseful=0.7×840=588 kWP_{useful} = 0.7 \times 840 = 588\ \text{kW}

Time:

t=1 786 750588=3038.7 s=50.6 mint = \frac{1\,786\,750}{588} = 3038.7\ \text{s} = 50.6\ \text{min}

Answer: pf =0.9615= 0.9615 lagging, power drawn =840= 840 kW; time to melt 2.5 t of steel ≈3039\approx 3039 s ≈50.6\approx 50.6 minutes.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Utilization of Electrical Energy chapter 5 questions →