Arc furnace: kW input, arc voltage, pf, kVA
Short answer
Average input power is 1702.4 kW using heat required divided by efficiency. Arc resistance is about 0.00947 ohm, arc voltage about 53.96 V, power factor 0.780 lagging, and average kVA input about 2182 kVA.
The following data related to a 3 phase arc furnace: Quantity of steel to be melted in one hour = 4.3 tonnes Specific heat of steel = 0.5 kJ/kg Latent heat of steel = 37.2 kJ/kg Melting point of steel = 1370°C Initial temperature of steel = 19.1°C Overall efficiency of steel = 50% Input Current = 5700 A Resistance of temperature referred to secondary = 0.008 Ω Reactance of temperature referred to secondary = 0.014 Ω Determine the following: (i) Average kW input to the furnace, (ii) Arc voltage (iii) Arc resistance (iv) power factor of the current drawn from the supply, and (v) Average kVA input to the furnace.
Interpretation: "resistance/reactance of temperature" means the transformer referred to the secondary, "overall efficiency of steel" means overall efficiency of the furnace, and specific heat is 0.5 kJ/kg°C. Values are per phase.
Given: kg/h, kJ/kg°C, kJ/kg, °C, °C, , A, , .
(i) Average kW input
(ii) and (iii) Arc resistance and arc voltage
Per phase, all input power is dissipated in :
(iv) Power factor
(v) Average kVA input
Answer: (i) 1702.4 kW, (ii) arc voltage V, (iii) arc resistance , (iv) pf lagging, (v) kVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arc furnace power factor and time to melt steel · Utilization of Electrical Energy, chapter 5
- Gas flames, arc welding and heat input · Manufacturing and Production Processes, chapter 12
- Synchronous motor: pf when input rises to 1500 kW · Electrical Machines, chapter 6
- PF correction for 1250 kVA generator (+170 kW) · Industrial Power Distribution and Illumination, chapter 10
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×