- 2067 Mangsir (old course) · 8 marks
Synchronous motor: pf when input rises to 1500 kW
Short answer
The power factor becomes 0.95 lagging. The motor shifts from leading to lagging because excitation is fixed while load increases.
A 6.6 kV star connected, 3 phase synchronous motor works at constant voltage and constant excitation. Its synchronous reactance is /phase, when the input is 100 kW and power factor is 0.8 leading. Find the power factor when the input is increased to 1500 kW.
Given: 6.6 kV, star, per phase (resistance neglected), constant and constant excitation. Condition 1: input 100 kW at 0.8 leading. Find the power factor at 1500 kW input.
Step 1: excitation emf at 100 kW, 0.8 leading
For a motor, :
Step 2: at 1500 kW (E unchanged)
Power per phase kW:
(maximum power kW, so 1500 kW is below the pull-out limit.)
Current:
Check: kW.
Answer: power factor at 1500 kW input lagging (current 138.15 A). The motor moved from leading to lagging because the excitation was fixed while the load increased.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- 3.3 kV synchronous motor back emf · Electrical Machines, chapter 6 · asked 2×
- Effect of excitation on synchronous motor · Electrical Machines, chapter 6 · asked 5×
- Performance of 7.5 kW induction motor from equivalent circuit · Electrical Machines I, chapter 5
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×
- Current, pf, power and efficiency of 3.3 kV motor · Electric Machines II, chapter 2
- Sync motor back emf at 0.5 pf leading · Electrical Machine, chapter 6
- Current, pf and efficiency of 100 hp motor · Electric Machines II, chapter 2