- Asked 2/14
- 2073 Magh · 8 marks
Sync generator terminal voltage, leading pf
Short answer
Full-load current I=1200kVA/(√3×6000V)=115.47 A/phase, Vph=3464 V. For 0.8 lagging, induced emf E=3952 V. For 0.8 leading, solve Vt from E; Vt=4288 V/phase, line voltage=7.43 kV.
A 1200 KVA, 6000 V, 3 phase star connected stator of a synchronous generator has a armature resistance of 0.4 ohms/phase and synchronous reactance of 6 ohm/phase. The generator delivers full load current at pf 0.8 lagging at normal rated voltage. Calculate the terminal voltage for the same excitation and load current at 0.8 pf leading.
Given: 1200 kVA, 6000 V (line), 3-phase, star; R_a = 0.4 Ω/phase, X_s = 6 Ω/phase; full-load current at 0.8 pf lagging at rated voltage. Find the terminal voltage for the same excitation (same E) and the same current at 0.8 pf leading.
Equivalent circuit per phase:
Ia Ra=0.4 Xs=6j
--->--/\/\/--(XXX)--+----> Vt (terminal)
E (induced emf) |
Step 1: Full-load current and phase voltage
I = S / (√3 V_L) = 1 200 000 / (√3 × 6000) = 115.47 A V_ph = 6000 / √3 = 3464.1 V
Step 2: Induced emf at 0.8 pf lagging
Take V as reference. I = 115.47 ∠−36.87° = 92.38 − j69.28 A. Z_s = 0.4 + j6 Ω.
Using components: I·R = 115.47 × 0.4 = 46.19 V; I·X = 115.47 × 6 = 692.8 V.
For a lagging load, E = V + I Z:
- E_real = V cos0 + IR cos φ + IX sin φ = 3464.1 + 46.19 × 0.8 + 692.8 × 0.6 = 3464.1 + 36.95 + 415.69 = 3916.7 V
- E_imag = IX cos φ − IR sin φ = 692.8 × 0.8 − 46.19 × 0.6 = 554.26 − 27.71 = 526.5 V
E = √(3916.7² + 526.5²) = 3952.0 V per phase (angle 7.66°).
Step 3: Terminal voltage at 0.8 pf leading, same E and same I
Now I = 115.47 ∠+36.87° = 92.38 + j69.28 A. With V_t as reference, E = V_t + I Z, whose components are
- real: V_t + IR cos φ − IX sin φ = V_t + 36.95 − 415.69 = V_t − 378.74
- imaginary: IX cos φ + IR sin φ = 554.26 + 27.71 = 581.97
E² = (Vt - 378.74)² + 581.97²
3952.0² = (Vt - 378.74)² + 581.97²
15 619 000 = (Vt - 378.74)² + 338 690
(Vt - 378.74)² = 15 280 300 -> Vt - 378.74 = 3909.0
Vt = 4287.6 V per phase
Line voltage V_L = √3 × 4287.6 = 7426 V (about 7.43 kV).
| Condition | Phase voltage | Line voltage |
|---|---|---|
| 0.8 lagging (rated) | 3464 V | 6000 V |
| 0.8 leading, same excitation | 4288 V | 7426 V |
The terminal voltage rises (about 23.8 % above rated) because the leading current gives magnetising armature reaction and a voltage rise across the reactance.
Answer: terminal voltage ≈ 7.43 kV (line), 4288 V per phase.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sync generator (6600 V) leading voltage · Electrical Machine, chapter 6 · asked 2×
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Sync motor back emf at 0.5 pf leading · Electrical Machine, chapter 6
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Starting, no-load and full-load current of slip ring motor · Electrical Machines I, chapter 5
- 25 kVA transformer: load voltage and primary current · Electrical Machines, chapter 2
- Regulation of 10 kVA round-rotor generator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Regulation and power angle of 1650 kVA generator · Electric Machines II, chapter 1