Regulation of delta connected 1600 kVA alternator
Short answer
Phase voltage = 13.5 kV (delta), phase current = 39.5 A. At 0.8 lagging pf: generated emf = 13619 V, regulation = +0.88%. At 0.8 leading pf: emf = 13477 V, regulation = –0.17%. Calculated using E = √[(Vcosφ+IR_a)² + (Vsinφ ± IX_s)²].
A 3-phase delta connected alternator is rated at 1600 kVA, 13.5 kV having per phase armature effective resistance and synchronous reactance of 1.5 Ω and 3 Ω per phase respectively. Calculate the voltage regulation for a load of 1.28 MW at (i) 0.8 pf lagging (ii) 0.8 pf leading.
Given: delta connected, so kV; , per phase; load 1.28 MW at 0.8 pf, i.e. MVA (full load).
(i) 0.8 pf lagging
(ii) 0.8 pf leading
The regulation is small because the given impedance (3 Ω) is very small compared with the phase voltage.
Answer: (i) +0.88% at 0.8 pf lagging; (ii) −0.17% at 0.8 pf leading.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Power angle and regulation of 10 kVA alternator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Regulation of 100 kVA alternator from tests · Electric Machines II, chapter 1
- Regulation of 1.5 MVA generator and zero-regulation pf · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6