- 2066 Magh (old course) · 8 marks
5 MVA alternator: regulation and pf for zero regulation
Short answer
Voltage regulation at full load 0.9 lagging is 4.30%. Zero regulation occurs at a leading power factor of 0.995.
A 3-phase star connected, 5 MVA, 11 kV synchronous generator has armature resistance of and synchronous reactance of per phase. Calculate voltage regulation if the generator delivers full load at rated terminal voltage at 0.9 lagging p.f. Also find out generator power factor at which the voltage regulation is zero.
Given: 5 MVA, 11 kV, star, , per phase, full load at 0.9 pf lagging.
Voltage regulation at 0.9 lagging
, :
Power factor for zero regulation
For zero regulation at full load current. The current must lead. Let with leading, ():
Answer: regulation at 0.9 lagging (E = 6623.9 V per phase). Regulation is zero at 0.995 leading power factor.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Voltage regulation of 2 MVA Δ-Y transformer · Electrical Machines I, chapter 2
- Star-delta starting torque ratio and full-load slip · Electrical Machines, chapter 5
- Secondary voltage, regulation, pf for max regulation · Electrical Machines, chapter 2
- Regulation of 1.5 MVA generator and zero-regulation pf · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3