Reactance diagram: 20 MVA generator, 15 kV/25 MVA base
Short answer
Using base 25 MVA, 15 kV at generator, line base 300 kV, load base 30 kV. Per-unit reactances: generator j0.0672, T1 j0.1344, line j0.05, T2 j0.1793. Load consumes 0.6 p.u. at 0.9 lag, represented as impedance 0.6667 + j0.3229 p.u.
A 20 MVA, 11 kV three-phase synchronous generator has a sub-transient reactance of 10%. It is connected through three identical single-phase Δ-Y connected transformers of 5000 kVA, 11/127.02 kV with a reactance of 15% to a high voltage transmission line having a total series reactance of j180 Ω. At the end of the HT transmission line, three identical single-phase star/star connected transformers of 5000 kVA, 127.02/12.702 kV with a reactance of 20%. The load is drawing 15 MVA at 20 kV at 0.9 pf lagging. Draw a single line diagram of the network and determine the reactance diagram. Choose a common base of 15 kV and 25 MVA.
Single line diagram
G T1 (3 x 1-ph) line T2 (3 x 1-ph)
(~)--||--[ D | Y ]----------j180----[ Y | Y ]----> Load
20 MVA 5 MVA each 5 MVA each 15 MVA
11 kV 11/127.02 kV 127.02/ 20 kV
X"=10% X=15% 12.702 kV 0.9 lag
X=20%
Transformer bank ratings
- T1 (Δ–Y): MVA. Line voltages: 11 kV / kV.
- T2 (Y–Y): 15 MVA, 220 kV / kV.
Base values
Assumption: the 15 kV base is taken in the generator circuit, with MVA.
| Section | Base kV | (Ω) |
|---|---|---|
| Generator | 15 | 9 |
| Line | ||
| Load | 36 |
Per-unit reactances
Load
15 MVA at 20 kV and 0.9 lagging: p.u., p.u.
As a series impedance:
Reactance diagram
j0.0672 j0.1344 j0.05 j0.1793
+-/\/\------/\/\------/\/\------/\/\----+
| |
(Eg) 0.6667 + j0.3229
| (load)
+----------------- reference -----------+
| Element | p.u. (25 MVA, 15 kV gen base) |
|---|---|
| Generator | j0.0672 |
| T1 | j0.1344 |
| Line | j0.0500 |
| T2 | j0.1793 |
| Load | 0.6667 + j0.3229 (0.54 + j0.2615 p.u. power) |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: three generators, 30 MVA 6.6 kV base · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- Restriking voltage numerical (11 kV, 10 mH) · Switchgear and Protection, chapter 6 · asked 2×