Generator-reactor system fault MVA

Short answer

On 20 MVA base, Thevenin reactance at F is 0.0984 pu. Fault current = 10.16 pu = 10.67 kA at 11 kV. Fault MVA = 20 / 0.0984 = 203 MVA.

An interconnected generator reactor system has been shown in figure below. The base values for the given % reactance are the rating of individual pieces of equipments. Determine the fault current and fault MVA for a 3-phase short circuit fault at F. Assume bus bar voltage as 11 kV. [Figure: G1 10 MVA, 10% connected at the faulted bus F; reactor 10 MVA, 5% between bus F and the bus of G2 (20 MVA, 15%); reactor 8 MVA, 4% between the G2 bus and G3 (20 MVA, 15%)]

The fault MVA is found by converting every reactance to one common MVA base, reducing the network to a single Thevenin reactance seen from F, and using Fault MVA=Base MVA/Xth\text{Fault MVA} = \text{Base MVA}/X_{th} with prefault voltage 1 pu.

Step 1: Choose base and convert reactances

Base: Sb=20S_b = 20 MVA, Vb=11V_b = 11 kV. Use Xnew=Xold SbSratedX_{new} = X_{old}\,\dfrac{S_b}{S_{rated}} (same voltage, so no voltage correction).

ElementRatingGiven XX on 20 MVA (pu)
G110 MVA10%0.10×20/10=0.200.10 \times 20/10 = 0.20
Reactor R1 (F to G2 bus)10 MVA5%0.05×20/10=0.100.05 \times 20/10 = 0.10
G220 MVA15%0.15
Reactor R2 (G2 bus to G3)8 MVA4%0.04×20/8=0.100.04 \times 20/8 = 0.10
G320 MVA15%0.15

Step 2: Reactance diagram

All generator EMFs are equal (1 pu) and their neutral is the reference, so for a 3-phase fault every source branch ends on the reference bus.

   F (G1 bus)        R1=0.1       B (G2 bus)  R2=0.1
 ---o----------------/\/\/\---------o-------/\/\/\---+
    |                               |                |
  G1 0.2                         G2 0.15          G3 0.15
    |                               |                |
 ===+===========  reference  =======+================+===

Step 3: Reduce the network as seen from F

XR2+G3=0.10+0.15=0.25XB=0.15∥0.25=0.15×0.250.40=0.09375XR1+B=0.10+0.09375=0.19375Xth=0.20∥0.19375=0.20×0.193750.39375=0.09841 pu\begin{aligned} X_{R2+G3} &= 0.10 + 0.15 = 0.25 \\ X_B &= 0.15 \parallel 0.25 = \frac{0.15 \times 0.25}{0.40} = 0.09375 \\ X_{R1+B} &= 0.10 + 0.09375 = 0.19375 \\ X_{th} &= 0.20 \parallel 0.19375 = \frac{0.20 \times 0.19375}{0.39375} = 0.09841\ \text{pu} \end{aligned}

Step 4: Fault current and fault MVA

If=1Xth=10.09841=10.16 puIb=Sb3 Vb=20×1063×11×103=1049.7 AIf=10.16×1049.7=10 667 A≈10.67 kAFault MVA=SbXth=200.09841=203.2 MVA\begin{aligned} I_f &= \frac{1}{X_{th}} = \frac{1}{0.09841} = 10.16\ \text{pu} \\ I_b &= \frac{S_b}{\sqrt{3}\,V_b} = \frac{20\times 10^6}{\sqrt{3}\times 11\times 10^3} = 1049.7\ \text{A} \\ I_f &= 10.16 \times 1049.7 = 10\,667\ \text{A} \approx 10.67\ \text{kA} \\ \text{Fault MVA} &= \frac{S_b}{X_{th}} = \frac{20}{0.09841} = 203.2\ \text{MVA} \end{aligned}

Check: 3×11×10.667=203.2\sqrt{3} \times 11 \times 10.667 = 203.2 MVA.

The fault MVA does not depend on the base chosen. With a 10 MVA base every pu reactance is halved, so Xth=0.04920X_{th} = 0.04920 pu and 10/0.04920=203.210/0.04920 = 203.2 MVA, the same result.

Answer: Fault current ≈ 10.67 kA (10.16 pu on 20 MVA base); fault MVA ≈ 203.2 MVA.