Generator-reactor system fault MVA
Short answer
On 20 MVA base, Thevenin reactance at F is 0.0984 pu. Fault current = 10.16 pu = 10.67 kA at 11 kV. Fault MVA = 20 / 0.0984 = 203 MVA.
An interconnected generator reactor system has been shown in figure below. The base values for the given % reactance are the rating of individual pieces of equipments. Determine the fault current and fault MVA for a 3-phase short circuit fault at F. Assume bus bar voltage as 11 kV. [Figure: G1 10 MVA, 10% connected at the faulted bus F; reactor 10 MVA, 5% between bus F and the bus of G2 (20 MVA, 15%); reactor 8 MVA, 4% between the G2 bus and G3 (20 MVA, 15%)]
The fault MVA is found by converting every reactance to one common MVA base, reducing the network to a single Thevenin reactance seen from F, and using with prefault voltage 1 pu.
Step 1: Choose base and convert reactances
Base: MVA, kV. Use (same voltage, so no voltage correction).
| Element | Rating | Given X | X on 20 MVA (pu) |
|---|---|---|---|
| G1 | 10 MVA | 10% | |
| Reactor R1 (F to G2 bus) | 10 MVA | 5% | |
| G2 | 20 MVA | 15% | 0.15 |
| Reactor R2 (G2 bus to G3) | 8 MVA | 4% | |
| G3 | 20 MVA | 15% | 0.15 |
Step 2: Reactance diagram
All generator EMFs are equal (1 pu) and their neutral is the reference, so for a 3-phase fault every source branch ends on the reference bus.
F (G1 bus) R1=0.1 B (G2 bus) R2=0.1
---o----------------/\/\/\---------o-------/\/\/\---+
| | |
G1 0.2 G2 0.15 G3 0.15
| | |
===+=========== reference =======+================+===
Step 3: Reduce the network as seen from F
Step 4: Fault current and fault MVA
Check: MVA.
The fault MVA does not depend on the base chosen. With a 10 MVA base every pu reactance is halved, so pu and MVA, the same result.
Answer: Fault current ≈ 10.67 kA (10.16 pu on 20 MVA base); fault MVA ≈ 203.2 MVA.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- HV bus fault and limiting reactor · Power System Analysis II, chapter 3
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Bus-bar reactor scheme with four generators · Power Plant Equipment, chapter 4 · asked 2×