- Asked 2/22
- 2071 Shrawan · 8 marks
Bus-bar reactor scheme: 30 MVA and 50 MVA
Short answer
On 50 MVA base, G1 reactance is 0.16667 pu, G2 is 0.1 pu, bus reactor 0.08264 pu. Equivalent reactance is 0.087145 pu, so fault current is 30.11 kA and fault MVA is 573.76 MVA; G1 supplies 15.75 kA and G2 supplies 14.37 kA.
Figure below shows a bus-bar reactor scheme. If a 3 phase to ground fault occurs on the outgoing feeder, calculate the fault current (in kA) supplied by each generator and fault MVA required for the circuit breaker (CB) on the feeder. Rating of generators are given as follow: G1: 30MVA, 11kV, Xg1" = 0.1 pu; G2: 50MVA, 11kV, Xg2" = 0.1 pu. [Figure: G1 (0.1 pu) and G2 (0.1 pu) on two bus-bar sections joined by a bus-bar reactor X = 0.2 ohm; the feeder leaves the G1 section through the CB]
G1 and G2 are on two bus sections joined by a bus-bar reactor. The feeder is on the G1 section; its reactance is not given, so the fault is taken just beyond the CB. G1 feeds directly; G2 feeds through the bus reactor. Fault MVA .
Base: 50 MVA, 11 kV; ; .
G1 30MVA,0.1 G2 50MVA,0.1
| |
===[Sec 1]====[X=0.2 ohm]====[Sec 2]===
|
CB
|--- F
Reactances on 50 MVA base
Fault current and fault MVA
Current from each generator
Answer: G1 supplies ≈ 15.75 kA, G2 ≈ 14.37 kA (total 30.11 kA); the feeder CB must be rated for about 574 MVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Bus-bar reactor scheme with four generators · Power Plant Equipment, chapter 4 · asked 2×
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Feeder reactor: 40 and 30 MVA, 50% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Feeder reactor: 40 and 30 MVA, 40% reduction · Power Plant Equipment, chapter 4 · asked 4×
- Fault current: two 50 MW generators, reactor inductance · Power Plant Equipment, chapter 4
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5