Skip to main content

Chapter 4 · 8 hours

Substation Equipments

IOE past exam questions

Past questions and answers

27 questions set from this chapter, 6 of them more than once. Most asked first.

  • Asked 5 times
  • 2073 Shrawan · 5 marks
  • 2082 Baisakh · 5 marks
  • 2081 Baisakh · 4 marks
  • 2080 Bhadra · 6 marks
  • 2073 Chaitra · 4 marks

Describe the fire fighting system used in power station with necessary diagram.

Answer

The fire fighting system of a power station detects a fire early, raises an alarm and puts it out quickly, so that costly equipment (transformers, generators, cable galleries, oil stores) is saved and people are safe.

Main fire risks

  • Transformer and switchgear insulating oil
  • Generator windings (insulation, hydrogen in large units)
  • Cable trenches and galleries
  • Fuel oil and coal stores, battery rooms

Components of the system

 +--------+   +-------------+   +-----------------+
 | Fire   |-->| Fire alarm  |-->| Alarm (bells,   |
 |detector|   | control pnl |   | lamps) + trip   |
 +--------+   +------+------+   +-----------------+
                     | opens deluge valve
 +-------+  +------+ v  +-------+   +-----------+
 | Water |->|Pumps |--->|Deluge |-->| Spray     |
 | tank  |  |(el+DG)|    | valve |   | nozzles   |
 +-------+  +------+    +-------+   | (on xfmr) |
                                     +-----------+
  1. Detection: smoke, heat (rate-of-rise) and flame detectors; for transformers, quartz bulb or linear heat detectors placed around the tank.
  2. Alarm panel: receives detector signals, sounds alarm, shows the zone, trips the equipment and starts the extinguishing system.
  3. Extinguishing systems:
    • Hydrant system: ring main of pipes with hydrant points and hoses, kept pressurised by jockey pump; main electric pump and diesel standby pump.
    • Water spray (deluge) / mulsifire system: for transformers; high-velocity water spray forms an emulsion on the oil surface, cools it and cuts oxygen.
    • CO2_2 flooding system: for generators, control rooms and cable vaults; CO2_2 cylinders discharge automatically and dilute oxygen. Used where water would damage equipment.
    • Foam system: for oil tanks and fuel stores.
    • Portable extinguishers: CO2_2, dry chemical powder and foam types near equipment.
  4. Passive measures: oil soak pits filled with gravel under transformers, fire walls between transformers, fire-resistant cable coating and fire barriers.

Requirements

  • Automatic operation with manual back-up.
  • Reliable, separate water supply and standby diesel pump.
  • Regular testing of detectors, pumps and cylinders.
  • Asked 4 times
  • 2070 Asar · 8 marks
  • 2081 Bhadra · 6 marks
  • 2080 Baisakh · 4 marks
  • 2074 Chaitra · 4 marks

Describe how a SCADA system can be implemented in a power system.

Answer

SCADA (Supervisory Control And Data Acquisition) is a computer-based system that collects real-time data from power stations and substations, shows it to operators at a control centre, and lets them control equipment remotely.

Architecture

      +-------------------------------+
      | Master station (control ctr)  |
      | SCADA/EMS servers, HMI, data  |
      | historian, alarm printer      |
      +---------------+---------------+
                      | communication
       (fibre, PLCC, microwave, radio, GSM)
         +------------+------------+
         |            |            |
     +---+---+    +---+---+    +---+---+
     | RTU 1 |    | RTU 2 |    | RTU 3 |
     +---+---+    +---+---+    +---+---+
         |            |            |
   CT, PT, relays, CB aux contacts, OLTC,
   transducers in plant / substations

Components

  1. Field devices: CTs, PTs, transducers, breaker status contacts, tap-position indicators, intelligent electronic devices (IEDs, numerical relays).
  2. Remote Terminal Unit (RTU): installed at each substation/plant; acquires analog values (V, I, MW, MVAr, f) and digital status (CB open/closed, alarms), converts them to digital data and executes control commands from the master.
  3. Communication system: carries data between RTUs and master using protocols such as IEC 60870-5-101/104, DNP3, Modbus, IEC 61850. Media: optical fibre (OPGW), PLCC, microwave, radio.
  4. Master station: servers and software that poll RTUs, process data, raise alarms, store history and run applications.
  5. HMI: operator consoles with single-line diagrams, trends and alarm lists.

Implementation steps

  1. Survey the plants/substations and list the points (analog, digital, control) to be monitored.
  2. Install transducers/IEDs and RTUs in each station and wire them to CTs, PTs, CBs and isolators.
  3. Build the communication network (e.g. OPGW fibre with PLCC as back-up) and choose the protocol.
  4. Set up the master station with redundant servers, database of all points and HMI displays.
  5. Test point-to-point, then commission and train operators.

Functions in a power system

  • Data acquisition: voltage, current, power, frequency, energy.
  • Supervisory control: open/close CBs, change transformer taps, start/stop units.
  • Alarm and event recording with time stamps (sequence of events).
  • Trend and historical data for analysis.
  • EMS applications: automatic generation control (load–frequency), economic dispatch, state estimation, load shedding.
  • Distribution automation: fault location, isolation and restoration.

Advantages

  • Fast, accurate information and quick fault response.
  • Fewer staff at unmanned substations.
  • Better reliability, economy and security of supply.

In Nepal, the NEA Load Dispatch Centre at Siuchatar uses SCADA to monitor and control the integrated grid.

  • Asked 3 times
  • 2076 Chaitra · 2 marks
  • 2078 Bhadra · 2 marks
  • 2073 Chaitra · 2 marks

What is main function of reactor in power system network?

Answer

A reactor is a coil of large inductive reactance and very small resistance. Its main function in a power network is to limit the short-circuit (fault) current to a value that circuit breakers and equipment can safely handle.

  • It raises the reactance between the source and the fault, so If=V/XI_f = V/X falls and the fault MVA falls.
  • It localises the fault so that the voltage on healthy parts of the system does not collapse.
  • Shunt reactors also absorb reactive power on long lightly loaded lines to control over-voltage (Ferranti effect).
  • Asked 2 times
  • 2081 Bhadra · 8 marks
  • 2075 Chaitra · 5+5 marks

Two generators each of capacities 40 MVA, 11 kV having their sub transient reactance of 5% and 4% respectively operating in parallel and supplying to a common load by single feeder of reactance 2 Ω. Calculate the fault level when 3-phase to ground fault occurs on the outgoing feeder. Also calculate the value of reactor to be connected in series with 2 Ω reactor to reduce the fault level by 40 %.

Answer

Work in per unit on a common base. Fault level =Base MVAXpu= \dfrac{\text{Base MVA}}{X_{pu}} and a reactor of XX ohms has Xpu=X⋅MVAbkVb2X_{pu} = X\cdot\dfrac{\text{MVA}_b}{\text{kV}_b^2}.

Base: 40 MVA, 11 kV.

Zbase=11240=3.025 ΩZ_{base} = \frac{11^2}{40} = 3.025\ \Omega
 G1 40MVA,5%   G2 40MVA,4%
     |             |
 ====+=====+=======+==== 11 kV bus
           |
          X=2 ohm feeder
           |
           F  (3-ph fault)

Fault level

XG1=0.05 pu,XG2=0.04 puXG1∥XG2=0.05×0.040.05+0.04=0.02222 puXfeeder=23.025=0.66116 puXeq=0.02222+0.66116=0.68338 puFault MVA=400.68338=58.53 MVA\begin{aligned} X_{G1} &= 0.05\ \text{pu},\quad X_{G2} = 0.04\ \text{pu} \\ X_{G1}\parallel X_{G2} &= \frac{0.05\times0.04}{0.05+0.04} = 0.02222\ \text{pu} \\ X_{feeder} &= \frac{2}{3.025} = 0.66116\ \text{pu} \\ X_{eq} &= 0.02222 + 0.66116 = 0.68338\ \text{pu} \\ \text{Fault MVA} &= \frac{40}{0.68338} = 58.53\ \text{MVA} \end{aligned}

Fault current: Ibase=40×1063×11×103=2099.5 AI_{base} = \dfrac{40\times10^6}{\sqrt3\times 11\times10^3} = 2099.5\ \text{A}, so If=2099.5/0.68338=3072 AI_f = 2099.5/0.68338 = 3072\ \text{A}.

Reactor to reduce fault level by 40 %

New fault level =0.6×58.53=35.12= 0.6\times58.53 = 35.12 MVA.

Xeq,new=4035.12=0.683380.6=1.13897 puXadded=1.13897−0.68338=0.45559 puXadded(Ω)=0.45559×3.025=1.378 Ω\begin{aligned} X_{eq,new} &= \frac{40}{35.12} = \frac{0.68338}{0.6} = 1.13897\ \text{pu} \\ X_{added} &= 1.13897 - 0.68338 = 0.45559\ \text{pu} \\ X_{added}(\Omega) &= 0.45559\times3.025 = 1.378\ \Omega \end{aligned}

Answer: Fault level = 58.53 MVA (about 3.07 kA). A reactor of about 1.378 Ω (0.4556 pu on 40 MVA) in series with the 2 Ω feeder reduces it by 40 % to 35.12 MVA.

  • Asked 2 times
  • 2072 Chaitra · 6 marks
  • 2079 Baisakh · 4 marks

Explain the function of various parts of a power transformer with a neat sketch.

Answer

A power transformer transfers power between two voltage levels by mutual induction. Besides the core and windings it has many accessories for cooling, protection and voltage control.

     HV bushing   LV bushing   conservator
         |  |        |  |     +---------+--breather
         |  |        |  |     |   oil   |  (silica gel)
  vent  _|__|________|__|_____+----+----+
  ===> |      oil-filled tank      | Buchholz relay
       |  +--------------------+   |
       |  | core + HV/LV wndgs |   |=== radiators
       |  +--------------------+   |
       |   tap changer   OTI WTI   |
       +---------------------------+
          drain valve     earthing

Parts and functions

PartFunction
Core (CRGO laminations)Low-reluctance path for flux; laminated to cut eddy loss
HV and LV windings (copper)Carry current; induce voltage in ratio of turns
TankHolds core, windings and oil; mechanical protection
Transformer oilInsulation and cooling medium
ConservatorTakes up oil expansion and contraction; keeps main tank full
Breather (silica gel)Dries the air entering the conservator
Buchholz relayGas-operated relay between tank and conservator; alarms/trips for internal faults
Explosion vent / pressure relief valveReleases sudden high pressure during severe internal faults
Radiators, fans, pumpsRemove heat (ONAN, ONAF, OFAF cooling)
BushingsBring winding leads out through the tank with insulation
Tap changer (on-load/off-load)Changes turns ratio to control voltage
Oil and winding temperature indicators (OTI, WTI)Show temperature; give alarm and trip, start fans
Oil level indicatorShows oil level in conservator
Drain and filter valvesDraining, sampling and filtering oil
  • Asked 2 times
  • 2071 Chaitra · 3 marks
  • 2073 Chaitra · 4 marks

Describe how communication between two electric sub-stations can be made with Power Line Carrier Communication system.

Answer

Power Line Carrier Communication (PLCC) uses the high-voltage transmission line itself as the medium to send speech, data, telemetry and protection signals between two substations, by superimposing a high-frequency carrier (about 30–500 kHz) on the 50 Hz power.

 Substation A                           Substation B
  bus                                         bus
   |                                           |
  [WT]=========== HV line ================[WT]
   |                                           |
  [CC]                                        [CC]
   |                                           |
  [LMU]                                      [LMU]
   |                                           |
 PLC terminal                           PLC terminal
 (tx/rx: speech, data, teleprotection)

Components and working

  1. PLC terminal (transmitter/receiver): modulates the speech/data/protection signal on to an HF carrier at the sending end and demodulates it at the receiving end.
  2. Coupling capacitor (CC): high-voltage capacitor that passes the HF carrier to the line but blocks the 50 Hz power frequency.
  3. Line matching unit (LMU): matches the impedance of the coaxial cable to the line and, with the CC, forms a high-pass filter; it also provides surge protection and earthing switch.
  4. Wave trap (line trap): a parallel LC circuit in series with the line, tuned to the carrier frequency. It offers high impedance to the carrier, so the signal does not leak into the substation bus, but negligible impedance to 50 Hz power.

The carrier travels along the line conductors (phase-to-earth or phase-to-phase coupling) to the other substation, where it is picked up through its own CC and LMU.

Uses

  • Telephone (speech) between substations and load dispatch centre.
  • Teleprotection: carrier-aided distance and inter-tripping.
  • SCADA data and telemetering.

Merits

  • No separate communication line needed; the line is strong and reliable.
  • Economical over long distances.
  • 2082 Baisakh · 8 marks

Two generators each of capacities 50 MVA, 11 kV having their sub transient reactance of 5% and 3% respectively operating in parallel and supplying to a common load through a feeder. If a 3 phase to ground fault occurs on the outgoing feeder, calculate the fault current supplied by each generator and fault power on the outgoing feeder. Also calculate the value of reactor to be connected in series with the outgoing feeder to reduce the fault level by 40 %.

Answer

The feeder reactance is not given, so it is taken as negligible: the fault is close to the bus. Fault MVA =MVAb/Xpu= \text{MVA}_b/X_{pu}.

Base: 50 MVA, 11 kV; Zbase=112/50=2.42 ΩZ_{base} = 11^2/50 = 2.42\ \Omega; Ibase=50×1063×11×103=2624.3 AI_{base} = \dfrac{50\times10^6}{\sqrt3\times11\times10^3} = 2624.3\ \text{A}.

 G1 50MVA,5%   G2 50MVA,3%
     |             |
 ====+=====+=======+==== 11 kV bus
           |  outgoing feeder
           F

Fault current and fault power

Xeq=0.05×0.030.05+0.03=0.01875 puIf=10.01875=53.33 pu=53.33×2624.3=139,964 A≈139.96 kAFault MVA=500.01875=2666.7 MVA\begin{aligned} X_{eq} &= \frac{0.05\times0.03}{0.05+0.03} = 0.01875\ \text{pu} \\ I_f &= \frac{1}{0.01875} = 53.33\ \text{pu} = 53.33\times2624.3 = 139{,}964\ \text{A} \approx 139.96\ \text{kA} \\ \text{Fault MVA} &= \frac{50}{0.01875} = 2666.7\ \text{MVA} \end{aligned}

Current from each generator

Current divides inversely as the reactances:

IG1=IfXG2XG1+XG2=139.96×0.030.08=52.49 kAIG2=IfXG1XG1+XG2=139.96×0.050.08=87.48 kA\begin{aligned} I_{G1} &= I_f\frac{X_{G2}}{X_{G1}+X_{G2}} = 139.96\times\frac{0.03}{0.08} = 52.49\ \text{kA} \\ I_{G2} &= I_f\frac{X_{G1}}{X_{G1}+X_{G2}} = 139.96\times\frac{0.05}{0.08} = 87.48\ \text{kA} \end{aligned}

Reactor for 40 % reduction

New fault MVA =0.6×2666.7=1600= 0.6\times2666.7 = 1600 MVA.

Xeq,new=501600=0.03125 puXadded=0.03125−0.01875=0.0125 puXadded(Ω)=0.0125×2.42=0.03025 Ω\begin{aligned} X_{eq,new} &= \frac{50}{1600} = 0.03125\ \text{pu} \\ X_{added} &= 0.03125 - 0.01875 = 0.0125\ \text{pu} \\ X_{added}(\Omega) &= 0.0125\times2.42 = 0.03025\ \Omega \end{aligned}

Answer: If≈139.96I_f \approx 139.96 kA (G1: 52.49 kA, G2: 87.48 kA), fault power = 2666.7 MVA; series reactor = 0.0125 pu ≈ 0.0303 Ω (fault level becomes 1600 MVA).

  • 2081 Baisakh · 4 marks

Explain the function following parts of a power transformer. i) Conservator tank ii) Explosion vent iii) Breather

Answer

i) Conservator tank

A small cylindrical tank mounted above the main tank and connected to it by a pipe (with the Buchholz relay in between).

  • Oil expands and contracts with load and temperature; the conservator takes up this change, so the main tank always stays completely full of oil.
  • Only the small oil surface in the conservator touches air, which reduces oxidation and moisture absorption.
  • Its oil level indicator shows the oil level.

ii) Explosion vent

A bent pipe on top of the main tank, closed by a thin diaphragm (bakelite/glass), or a modern spring-loaded pressure relief valve.

  • During a severe internal fault, arcing decomposes oil into gas and pressure rises suddenly.
  • The diaphragm bursts and releases the pressure, preventing the tank from bursting or exploding.

iii) Breather

A small container filled with silica gel, with an oil seal cup, fitted on the conservator air pipe.

  • When the oil contracts, air is drawn into the conservator through the breather.
  • Silica gel absorbs moisture (blue colour turns pink when saturated); the oil cup traps dust.
  • This keeps the oil dry and maintains its dielectric strength.
  • 2081 Baisakh · 6 marks

The given figure shows three generators operating in parallel. Find the fault current and fault level if three phase to ground fault occurs in the outgoing feeder. What should be the value of feeder reactor to be added to reduce the fault level by 40%? [Figure: G1 20 MVA, 11 kV, X1 = 0.1 pu; G2 30 MVA, 11 kV, X2 = 0.2 pu; G3 40 MVA, 11 kV, X3 = 0.3 pu; all three connected to a common busbar (points A, B, C); an outgoing feeder from the busbar through a circuit breaker, with the fault point on the feeder beyond the C.B.]

Answer

Convert all reactances to one base, combine the three parallel generators, and use Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}. The feeder reactance is not given, so it is taken as zero (fault just beyond the C.B.).

Base: 100 MVA, 11 kV. Xnew=XoldMVAnewMVAoldX_{new} = X_{old}\dfrac{\text{MVA}_{new}}{\text{MVA}_{old}}; Zbase=112/100=1.21 ΩZ_{base} = 11^2/100 = 1.21\ \Omega.

 G1 20MVA   G2 30MVA   G3 40MVA
  0.1pu      0.2pu      0.3pu
   |A         |B         |C
 ==+==========+==========+=== 11 kV
              |
             C.B.
              |---- F

Reactances on 100 MVA base

GeneratorCalculationXX (pu)
G10.1×100/200.1\times100/200.5
G20.2×100/300.2\times100/300.6667
G30.3×100/400.3\times100/400.75
1Xeq=10.5+10.6667+10.75=2+1.5+1.3333=4.8333Xeq=0.20690 pu\begin{aligned} \frac{1}{X_{eq}} &= \frac{1}{0.5}+\frac{1}{0.6667}+\frac{1}{0.75} = 2+1.5+1.3333 = 4.8333 \\ X_{eq} &= 0.20690\ \text{pu} \end{aligned}

Fault level and fault current

Fault MVA=1000.2069=483.33 MVAIf=483.33×1063×11×103=25,368 A≈25.37 kA\begin{aligned} \text{Fault MVA} &= \frac{100}{0.2069} = 483.33\ \text{MVA} \\ I_f &= \frac{483.33\times10^6}{\sqrt3\times11\times10^3} = 25{,}368\ \text{A} \approx 25.37\ \text{kA} \end{aligned}

Feeder reactor for 40 % reduction

New fault MVA =0.6×483.33=290= 0.6\times483.33 = 290 MVA.

Xeq,new=100290=0.34483 puXreactor=0.34483−0.20690=0.13793 puXreactor(Ω)=0.13793×1.21=0.1669 Ω\begin{aligned} X_{eq,new} &= \frac{100}{290} = 0.34483\ \text{pu} \\ X_{reactor} &= 0.34483 - 0.20690 = 0.13793\ \text{pu} \\ X_{reactor}(\Omega) &= 0.13793\times1.21 = 0.1669\ \Omega \end{aligned}

Answer: Fault level = 483.33 MVA, fault current ≈ 25.37 kA; feeder reactor ≈ 0.167 Ω (0.1379 pu on 100 MVA) brings the level down to 290 MVA.

  • 2080 Bhadra · 8 marks

For the power system network given below, calculate the fault level in MVA at the outgoing feeder for a 3 phase to ground fault on the feeder. Calculate the value of reactance to be connected in the feeder in order to reduce the fault level by 50%. Ratings of the generators are: G1 = 50 MVA, 11 kV, Xg1 = 0.15 p.u.; G2 = 50 MVA, 11 kV, Xg2 = 0.3 p.u. [Figure: G1 and G2 connected to a common busbar with a single outgoing feeder]

Answer

Generators in parallel feed the fault through the bus. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}. Feeder reactance (not given) is taken as zero before adding the reactor.

Base: 50 MVA, 11 kV; Zbase=112/50=2.42 ΩZ_{base} = 11^2/50 = 2.42\ \Omega. Both generators are already on 50 MVA.

 G1 50MVA,0.15   G2 50MVA,0.3
      |               |
 =====+=======+=======+==== 11 kV
              |  feeder (+X)
              F

Fault level

Xeq=0.15×0.30.15+0.3=0.1 puFault MVA=500.1=500 MVAIf=500×1063×11×103=26.24 kA\begin{aligned} X_{eq} &= \frac{0.15\times0.3}{0.15+0.3} = 0.1\ \text{pu} \\ \text{Fault MVA} &= \frac{50}{0.1} = 500\ \text{MVA} \\ I_f &= \frac{500\times10^6}{\sqrt3\times11\times10^3} = 26.24\ \text{kA} \end{aligned}

Reactance for 50 % reduction

New fault MVA = 250 MVA, so

Xeq,new=50250=0.2 puX=0.2−0.1=0.1 puX(Ω)=0.1×2.42=0.242 Ω\begin{aligned} X_{eq,new} &= \frac{50}{250} = 0.2\ \text{pu} \\ X &= 0.2 - 0.1 = 0.1\ \text{pu} \\ X(\Omega) &= 0.1\times2.42 = 0.242\ \Omega \end{aligned}

(Halving the fault level needs the total reactance to double, so the added reactance equals the existing XeqX_{eq}.)

Answer: Fault level = 500 MVA; feeder reactance = 0.1 pu = 0.242 Ω (fault level becomes 250 MVA).

  • 2080 Baisakh · 6 marks

Following figure shows two generators operating parallel. i) If a 3-phase to ground fault occurs on the outgoing feeder, calculate the fault current and fault level on the feeder. ii) If a 3rd generator (G3: 10MVA, 11kV, X3=0.2 pu) is added at point 'C', calculate the value of reactor to be added on the outgoing feeder so that the fault level remains same as before. [Figure: G1 20 MVA, 11 kV, X1 = 0.1 pu (path-1) and G2 20 MVA, 11 kV, X2 = 0.1 pu (path-2) connected to a common busbar at points A and B; busbar extends to point C; outgoing feeder from the busbar through a C.B., fault point 'F' on the outgoing feeder]

Answer

Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}. The feeder has no reactance at first (none given).

Base: 20 MVA, 11 kV; Zbase=112/20=6.05 ΩZ_{base} = 11^2/20 = 6.05\ \Omega; Ibase=20×1063×11×103=1049.7 AI_{base} = \dfrac{20\times10^6}{\sqrt3\times11\times10^3} = 1049.7\ \text{A}.

 G1 20MVA   G2 20MVA   G3 10MVA (added)
  0.1pu      0.1pu      0.2pu
   |A         |B         |C
 ==+==========+==========+=== 11 kV
         |
        C.B.--[X]-- F

(i) Fault current and fault level (two generators)

Xeq=0.12=0.05 puFault MVA=200.05=400 MVAIf=10.05×1049.7=20,995 A≈20.99 kA\begin{aligned} X_{eq} &= \frac{0.1}{2} = 0.05\ \text{pu} \\ \text{Fault MVA} &= \frac{20}{0.05} = 400\ \text{MVA} \\ I_f &= \frac{1}{0.05}\times1049.7 = 20{,}995\ \text{A} \approx 20.99\ \text{kA} \end{aligned}

(ii) Reactor after adding G3

G3 on 20 MVA base: X3=0.2×2010=0.4 puX_3 = 0.2\times\dfrac{20}{10} = 0.4\ \text{pu}.

1Xeq′=10.1+10.1+10.4=22.5Xeq′=0.04444 pu  ⇒  Fault MVA=450 MVA (too high)\begin{aligned} \frac{1}{X_{eq}'} &= \frac{1}{0.1}+\frac{1}{0.1}+\frac{1}{0.4} = 22.5 \\ X_{eq}' &= 0.04444\ \text{pu} \;\Rightarrow\; \text{Fault MVA} = 450\ \text{MVA (too high)} \end{aligned}

To keep 400 MVA the total must stay at 0.05 pu:

Xreactor=0.05−0.04444=0.005556 puXreactor(Ω)=0.005556×6.05=0.0336 Ω\begin{aligned} X_{reactor} &= 0.05 - 0.04444 = 0.005556\ \text{pu} \\ X_{reactor}(\Omega) &= 0.005556\times6.05 = 0.0336\ \Omega \end{aligned}

Answer: (i) Fault level = 400 MVA, If≈I_f \approx 20.99 kA. (ii) Feeder reactor ≈ 0.00556 pu = 0.0336 Ω keeps the fault level at 400 MVA after G3 is added.

  • 2079 Bhadra · 5 marks

What is the function of reactor in Power system network? Explain the ring type bus bar reactor scheme.

Answer

Function of reactor

A current-limiting reactor is a coil with high inductive reactance and negligible resistance. It limits the short-circuit current to a value that circuit breakers can interrupt, localises the fault so the rest of the bus keeps its voltage, and reduces mechanical and thermal stress on equipment.

Ring type bus-bar reactor scheme

The bus-bar is split into sections, one generator per section, and adjacent sections are joined through reactors so that the sections form a closed ring. Feeders are taken from each section.

      G1            G2            G3
      |             |             |
  ==[S1]===[X]===[S2]===[X]===[S3]==
    |  |          |  |          |  |
    |  feeders    feeders     feeders
    |                              |
    +-------------[X]--------------+
         (reactor closing the ring)

Working:

  • In normal operation each generator mainly feeds the load on its own section. Only small balancing currents flow through the reactors, so their voltage drop and power loss are small.
  • When a fault occurs on a feeder of, say, section S2, generator G2 feeds it directly, but G1 and G3 feed it only through the reactors. The fault current from the other sections is therefore limited.
  • Since each section is fed from two sides, the current through each reactor is lower than in a simple tie-bar scheme with the same reactor value.

Advantages:

  • Good fault-current limitation with low losses in normal running.
  • A fault is confined to one section; the voltage on other sections stays fairly high.
  • Each section is supplied from both directions, so supply is more reliable than in a plain series (in-line) scheme.

Disadvantages:

  • More reactors and more complex layout than the simple series bus-bar scheme.
  • Load sharing between sections depends on the loads being balanced.
  • 2079 Bhadra · 5 marks

For the system shown in figure below, calculate the fault level in MVA at out going feeder for a three phase to ground fault on this feeder. Calculate the value of reactance to be connected in the feeder in order to reduce the fault level by 50%. [Figure: G1 25 MVA, 11 kV, E = 1 pu, X1 = 0.15 pu and G2 25 MVA, 11 kV, E = 1 pu, X2 = 0.3 pu connected to a common busbar; outgoing feeder through a C.B. with fault point 'F' on the feeder]

Answer

Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}, with E=1E = 1 pu. Feeder reactance (not given) is taken as zero before adding the reactor.

Base: 25 MVA, 11 kV; Zbase=112/25=4.84 ΩZ_{base} = 11^2/25 = 4.84\ \Omega.

 G1 25MVA,0.15   G2 25MVA,0.3
      |               |
 =====+=======+=======+==== 11 kV
              |
             C.B.--[X]-- F

Fault level

Xeq=0.15×0.30.15+0.3=0.1 puFault MVA=250.1=250 MVAIf=250×1063×11×103=13.12 kA\begin{aligned} X_{eq} &= \frac{0.15\times0.3}{0.15+0.3} = 0.1\ \text{pu} \\ \text{Fault MVA} &= \frac{25}{0.1} = 250\ \text{MVA} \\ I_f &= \frac{250\times10^6}{\sqrt3\times11\times10^3} = 13.12\ \text{kA} \end{aligned}

Reactance for 50 % reduction

New fault MVA = 125 MVA.

Xeq,new=25125=0.2 puX=0.2−0.1=0.1 puX(Ω)=0.1×4.84=0.484 Ω\begin{aligned} X_{eq,new} &= \frac{25}{125} = 0.2\ \text{pu} \\ X &= 0.2 - 0.1 = 0.1\ \text{pu} \\ X(\Omega) &= 0.1\times4.84 = 0.484\ \Omega \end{aligned}

Answer: Fault level = 250 MVA; feeder reactance = 0.1 pu = 0.484 Ω (fault level becomes 125 MVA).

  • 2079 Baisakh · 6 marks

A 100 MVA generator with 10% reactance and a 200 MVA generator with 8% reactance are connected to a common bus. The fault level on bus 1 is to be restricted to 1500 MVA. If a reactor is added in between these two generators in the bus bar, then on 100 MVA base Calculate the value of reactance added.

Answer

The bus-bar is split into two sections joined by a reactor XX: G1 on bus 1 and G2 on bus 2. For a fault on bus 1, G1 feeds directly and G2 feeds through XX. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}.

Base: 100 MVA.

XG1=0.10 pu,XG2=0.08×100200=0.04 puX_{G1} = 0.10\ \text{pu},\qquad X_{G2} = 0.08\times\frac{100}{200} = 0.04\ \text{pu}
  G1 100MVA,10%        G2 200MVA,8%
       |                     |
  ===[Bus 1]=====[ X ]=====[Bus 2]===
       |
       F (fault on bus 1)

Without reactor: Xeq=0.1∥0.04=0.02857X_{eq} = 0.1\parallel0.04 = 0.02857 pu, fault MVA =100/0.02857=3500= 100/0.02857 = 3500 MVA (too high).

With reactor: required

Xeq=1001500=0.06667 puX_{eq} = \frac{100}{1500} = 0.06667\ \text{pu}

The two paths are in parallel:

1Xeq=1XG1+1XG2+X15=10+10.04+X0.04+X=15=0.2X=0.16 pu\begin{aligned} \frac{1}{X_{eq}} &= \frac{1}{X_{G1}} + \frac{1}{X_{G2}+X} \\ 15 &= 10 + \frac{1}{0.04+X} \\ 0.04 + X &= \frac{1}{5} = 0.2 \\ X &= 0.16\ \text{pu} \end{aligned}

Answer: Bus-bar reactor XX = 0.16 pu (16 %) on 100 MVA base. (If the bus voltage VV kV is known, XΩ=0.16 V2/100X_\Omega = 0.16\,V^2/100; e.g. at 11 kV, 0.194 Ω.)

  • 2078 Bhadra · 5 marks

Two generators of capacities 40MVA, 11kV and 30MVA, 11kV having their sub transient reactance of 5% and 4% respectively operating in parallel and supplying to a common load by single feeder of reactance 2Ω. Calculate the value of reactor to be connected in series with feeder so as to reduce the fault level at the end of the feeder by 50%.

Answer

Work in per unit on a common base. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}; ohms to pu: Xpu=XΩ MVAb/kV2X_{pu} = X_\Omega\,\text{MVA}_b/\text{kV}^2.

Base: 40 MVA, 11 kV; Zbase=112/40=3.025 ΩZ_{base} = 11^2/40 = 3.025\ \Omega.

 G1 40MVA,5%   G2 30MVA,4%
     |             |
 ====+=====+=======+==== 11 kV
           |
          2 ohm feeder + X
           |
           F

Present fault level

XG1=0.05 pu,XG2=0.04×4030=0.05333 puXG1∥XG2=0.05×0.053330.10333=0.025806 puXfeeder=23.025=0.66116 puXeq=0.025806+0.66116=0.68696 puFault MVA=400.68696=58.23 MVA\begin{aligned} X_{G1} &= 0.05\ \text{pu},\quad X_{G2} = 0.04\times\frac{40}{30} = 0.05333\ \text{pu} \\ X_{G1}\parallel X_{G2} &= \frac{0.05\times0.05333}{0.10333} = 0.025806\ \text{pu} \\ X_{feeder} &= \frac{2}{3.025} = 0.66116\ \text{pu} \\ X_{eq} &= 0.025806 + 0.66116 = 0.68696\ \text{pu} \\ \text{Fault MVA} &= \frac{40}{0.68696} = 58.23\ \text{MVA} \end{aligned}

Reactor for 50 % reduction

New fault MVA =29.11= 29.11 MVA, so the total reactance must double:

Xeq,new=2×0.68696=1.37393 puX=1.37393−0.68696=0.68696 puX(Ω)=0.68696×3.025=2.078 Ω\begin{aligned} X_{eq,new} &= 2\times0.68696 = 1.37393\ \text{pu} \\ X &= 1.37393 - 0.68696 = 0.68696\ \text{pu} \\ X(\Omega) &= 0.68696\times3.025 = 2.078\ \Omega \end{aligned}

Answer: Present fault level = 58.23 MVA; series reactor = 0.687 pu ≈ 2.078 Ω (fault level becomes 29.11 MVA).

  • 2076 Chaitra · 5 marks

A small generating station has two alternators of 2500KVA and 500KVA with percentage reactance of 8 & 6 percentage respectively. The circuit breakers are rated at 150,000kVA. Due to increase in system load it is intended to add a third generator of 10,000kVA rating and 7.5% reactance. If the system voltage is 3300volts, find the reactance X necessary to protect the C.B. [Figure: alternators A and B connected directly to the busbar, which feeds an outgoing circuit through the CB rated 150,000 kVA; the third generator C (10,000 kVA, 7.5%) is connected to the busbar through the reactor X]

Answer

The C.B. must not see a fault level above its rating (150,000 kVA). G3 is connected to the bus through reactor XX. For a fault on the outgoing circuit just beyond the C.B., all three machines feed the fault.

Base: 10,000 kVA, 3.3 kV; Zbase=3.3210=1.089 ΩZ_{base} = \dfrac{3.3^2}{10} = 1.089\ \Omega. Percentage reactance on new base: %Xnew=%X×kVAbkVA\%X_{new} = \%X\times\dfrac{\text{kVA}_b}{\text{kVA}}.

   A 2500kVA   B 500kVA    C 10000kVA,7.5%
     8%          6%          |
     |           |          [X]
 ====+===========+===========+==== 3.3 kV
           |
          CB 150,000 kVA
           |--- F

Reactances on 10,000 kVA base

MachineCalculation%X
A8×10000/25008\times10000/250032 %
B6×10000/5006\times10000/500120 %
Cgiven7.5 %

A∥BA\parallel B: 32×120152=25.263 %\dfrac{32\times120}{152} = 25.263\ \%, giving fault kVA =10000×100/25.263=39,583= 10000\times100/25.263 = 39{,}583 kVA (safe).

If C were connected directly: 25.263∥7.5=5.783 %25.263\parallel7.5 = 5.783\ \%, fault kVA =172,917= 172{,}917 kVA > 150,000 kVA. So a reactor is needed.

Required reactor

Allowed total reactance:

%Xeq=10000×100150000=6.667 %\%X_{eq} = \frac{10000\times100}{150000} = 6.667\ \% 16.667=125.263+17.5+X0.15−0.039583=0.110417=17.5+X7.5+X=9.0566X=1.5566 %\begin{aligned} \frac{1}{6.667} &= \frac{1}{25.263} + \frac{1}{7.5+X} \\ 0.15 - 0.039583 &= 0.110417 = \frac{1}{7.5+X} \\ 7.5 + X &= 9.0566 \\ X &= 1.5566\ \% \end{aligned}

In ohms:

XΩ=1.5566100×1.089=0.01695 ΩX_\Omega = \frac{1.5566}{100}\times1.089 = 0.01695\ \Omega

Answer: Reactor XX ≈ 1.557 % on 10,000 kVA base ≈ 0.017 Ω in series with the new generator keeps the fault level at 150,000 kVA.

  • 2076 Asoj · 8 marks

Below figure show the single line diagram of parallel operated generators. Their ratings are: G1: capacity = 50 MW, 11kV, X1 = 0.16 pu based on its rating; G2: capacity = 40 MW, 11kV, X2 = 0.12 pu based on its rating; XL = 2 ohms. [Figure: G1 (through X1) and G2 (through X2), both star-grounded, connected to a common busbar; the outgoing feeder leaves the busbar through XL] a) If a three-phase to ground fault occurs at outgoing feeder, calculate the fault current and fault power at the outgoing feeder and fault current supplied by each generator. b) Calculate the value of inductor (in mH) of the reactor to be connected in series with X2 so that both generators delivers equal amp of fault current during 3 phase to ground fault on the feeder.

Answer

Generator ratings are given in MW; they are taken as MVA (unity power factor assumed). Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}; ohms to pu: Xpu=XΩ MVAb/kV2X_{pu} = X_\Omega\,\text{MVA}_b/\text{kV}^2.

Base: 50 MVA, 11 kV. Zbase=112/50=2.42 ΩZ_{base} = 11^2/50 = 2.42\ \Omega; Ibase=50×1063×11×103=2624.3 AI_{base} = \dfrac{50\times10^6}{\sqrt3\times11\times10^3} = 2624.3\ \text{A}.

  G1 50MW,0.16    G2 40MW,0.12
      |               |
     X1              X2 (+ Xr in part b)
      |               |
  ====+=======+=======+==== 11 kV bus
              |
             XL = 2 ohm
              |
              F (3-ph to ground)

a) Fault current, fault power and generator currents

X1=0.16 pu,X2=0.12×5040=0.15 puX1∥X2=0.16×0.150.31=0.077419 puXL=22.42=0.82645 puXeq=0.077419+0.82645=0.90387 puIf=2624.30.90387=2903.4 AFault power=500.90387=55.32 MVA\begin{aligned} X_1 &= 0.16\ \text{pu},\quad X_2 = 0.12\times\frac{50}{40} = 0.15\ \text{pu} \\ X_1\parallel X_2 &= \frac{0.16\times0.15}{0.31} = 0.077419\ \text{pu} \\ X_L &= \frac{2}{2.42} = 0.82645\ \text{pu} \\ X_{eq} &= 0.077419 + 0.82645 = 0.90387\ \text{pu} \\ I_f &= \frac{2624.3}{0.90387} = 2903.4\ \text{A} \\ \text{Fault power} &= \frac{50}{0.90387} = 55.32\ \text{MVA} \end{aligned}

Current divides inversely as the branch reactances:

IG1=2903.4×0.150.31=1404.9 AIG2=2903.4×0.160.31=1498.5 A\begin{aligned} I_{G1} &= 2903.4\times\frac{0.15}{0.31} = 1404.9\ \text{A} \\ I_{G2} &= 2903.4\times\frac{0.16}{0.31} = 1498.5\ \text{A} \end{aligned}

b) Reactor in series with X2X_2 for equal currents

Both generators feed the same bus, so they deliver equal current only when their branch reactances are equal:

X2+Xr=X1  ⇒  Xr=0.16−0.15=0.01 puXr(Ω)=0.01×2.42=0.0242 ΩL=Xr2πf=0.02422π×50=7.70×10−5 H=0.0770 mH\begin{aligned} X_2 + X_r &= X_1 \;\Rightarrow\; X_r = 0.16 - 0.15 = 0.01\ \text{pu} \\ X_r(\Omega) &= 0.01\times2.42 = 0.0242\ \Omega \\ L &= \frac{X_r}{2\pi f} = \frac{0.0242}{2\pi\times50} = 7.70\times10^{-5}\ \text{H} = 0.0770\ \text{mH} \end{aligned}

Check: new Xeq=0.08+0.82645=0.90645X_{eq} = 0.08 + 0.82645 = 0.90645 pu, If=2895.2I_f = 2895.2 A, each generator supplies 1447.6 A.

Answer: (a) IfI_f ≈ 2903 A, fault power ≈ 55.32 MVA, IG1I_{G1} ≈ 1405 A, IG2I_{G2} ≈ 1499 A. (b) LL ≈ 0.077 mH (0.0242 Ω).

  • 2074 Chaitra · 6 marks

Two generators of capacities 40MVA, 11kV and 30 MVA, 11kV having their sub transient reactance of 5% and 4% respectively operating in parallel and supplying to a common load by single feeder of reactance 2 ohm. Calculate the value of reactor to be connected in series with feeder so as to reduce the fault level at the end of the feeder by 40%.

Answer

Work in per unit on a common base. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}; ohms to pu: Xpu=XΩ MVAb/kV2X_{pu} = X_\Omega\,\text{MVA}_b/\text{kV}^2.

Base: 40 MVA, 11 kV; Zbase=112/40=3.025 ΩZ_{base} = 11^2/40 = 3.025\ \Omega.

 G1 40MVA,5%   G2 30MVA,4%
     |             |
 ====+=====+=======+==== 11 kV
           |
          2 ohm feeder + X
           |
           F

Present fault level

XG1=0.05 pu,XG2=0.04×4030=0.05333 puXG1∥XG2=0.05×0.053330.10333=0.025806 puXfeeder=23.025=0.66116 puXeq=0.68696 puFault MVA=400.68696=58.23 MVA\begin{aligned} X_{G1} &= 0.05\ \text{pu},\quad X_{G2} = 0.04\times\frac{40}{30} = 0.05333\ \text{pu} \\ X_{G1}\parallel X_{G2} &= \frac{0.05\times0.05333}{0.10333} = 0.025806\ \text{pu} \\ X_{feeder} &= \frac{2}{3.025} = 0.66116\ \text{pu} \\ X_{eq} &= 0.68696\ \text{pu} \\ \text{Fault MVA} &= \frac{40}{0.68696} = 58.23\ \text{MVA} \end{aligned}

Reactor for 40 % reduction

New fault MVA =0.6×58.23=34.94= 0.6\times58.23 = 34.94 MVA.

Xeq,new=0.686960.6=1.14494 puX=1.14494−0.68696=0.45798 puX(Ω)=0.45798×3.025=1.385 Ω\begin{aligned} X_{eq,new} &= \frac{0.68696}{0.6} = 1.14494\ \text{pu} \\ X &= 1.14494 - 0.68696 = 0.45798\ \text{pu} \\ X(\Omega) &= 0.45798\times3.025 = 1.385\ \Omega \end{aligned}

Answer: Present fault level = 58.23 MVA; series reactor ≈ 0.458 pu = 1.385 Ω (fault level becomes 34.94 MVA).

  • 2074 Asoj · 4+4 marks

Below figure shows 4 Nos of identical generators operating in parallel. Each generator is rated as 1600 kVA, 11kV, Xg = 0.2 pu. [Figure: G1, G2, G3, G4, each through Xg, connected to an 11 kV busbar at points A, B, C, D; an outgoing feeder from the busbar between B and C through a circuit breaker and a reactor X = 10 Ω, with a 3-phase to ground fault at its end] (i) Calculate fault current in outgoing feeder and fault current supplied by each generator. (ii) If reactors of 5 ohm each are connected between point A and B, point C and D respectively. Calculate fault current in outgoing feeder and fault current supplied by each generator.

Answer

Work in ohms at 11 kV. Phase voltage Vph=11000/3=6350.85V_{ph} = 11000/\sqrt3 = 6350.85 V. Fault current If=Vph/XtotalI_f = V_{ph}/X_{total}.

Zbase=1121.6=75.625 ΩXg=0.2×75.625=15.125 Ω\begin{aligned} Z_{base} &= \frac{11^2}{1.6} = 75.625\ \Omega \\ X_g &= 0.2\times75.625 = 15.125\ \Omega \end{aligned}
  G1      G2       G3      G4
  |Xg     |Xg      |Xg     |Xg
  A--[5]--B----+---C--[5]--D   11 kV bus
               |       ([5] only in part ii)
              CB
               |
            X=10 ohm
               |
               F

(i) Without bus reactors

All four generators are directly in parallel:

Xpar=15.1254=3.781 ΩXtotal=3.781+10=13.781 ΩIf=6350.8513.781=460.83 A\begin{aligned} X_{par} &= \frac{15.125}{4} = 3.781\ \Omega \\ X_{total} &= 3.781 + 10 = 13.781\ \Omega \\ I_f &= \frac{6350.85}{13.781} = 460.83\ \text{A} \end{aligned}

Each generator supplies 460.83/4=115.21460.83/4 = 115.21 A. (Fault MVA =3×11×0.46083=8.78=\sqrt3\times11\times0.46083 = 8.78 MVA.)

(ii) With 5 Ω reactors between A–B and C–D

G1 and G4 now reach the feeder through 5 Ω; G2 and G3 connect directly.

XG1=XG4=15.125+5=20.125 Ω1Xpar=220.125+215.125=0.23161Xpar=4.3176 ΩXtotal=4.3176+10=14.3176 ΩIf=6350.8514.3176=443.57 A\begin{aligned} X_{G1} = X_{G4} &= 15.125 + 5 = 20.125\ \Omega \\ \frac{1}{X_{par}} &= \frac{2}{20.125} + \frac{2}{15.125} = 0.23161 \\ X_{par} &= 4.3176\ \Omega \\ X_{total} &= 4.3176 + 10 = 14.3176\ \Omega \\ I_f &= \frac{6350.85}{14.3176} = 443.57\ \text{A} \end{aligned}

The bus voltage behind the reactors is IfXpar=443.57×4.3176=1915.2I_f X_{par} = 443.57\times4.3176 = 1915.2 V, so

IG1=IG4=1915.220.125=95.16 AIG2=IG3=1915.215.125=126.62 A\begin{aligned} I_{G1} = I_{G4} &= \frac{1915.2}{20.125} = 95.16\ \text{A} \\ I_{G2} = I_{G3} &= \frac{1915.2}{15.125} = 126.62\ \text{A} \end{aligned}

Check: 2(95.16)+2(126.62)=443.572(95.16) + 2(126.62) = 443.57 A.

Answer: (i) IfI_f = 460.83 A, each generator 115.21 A. (ii) IfI_f = 443.57 A; G1 and G4 supply 95.16 A each, G2 and G3 supply 126.62 A each.

  • 2073 Shrawan · 5 marks

The figure below shows four identical generators, each rated 11 kV, 25 MVA and each having sub-transient reactance of 16% on its own rating. Find 3-ϕ fault level at one of the outgoing feeder. Also calculate the value of reactance to be connected in the bus bar between "B" and "C" so that fault level reduces by 40%. [Figure: four generators connected to a busbar at points A, B, C, D; outgoing feeders leave the busbar, with a 3-ϕ fault on the feeder between C and D]

Answer

All four generators are identical, so work on their own base. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}.

Base: 25 MVA, 11 kV; Xg=0.16X_g = 0.16 pu; Zbase=112/25=4.84 ΩZ_{base} = 11^2/25 = 4.84\ \Omega.

  G1      G2         G3      G4
  |       |          |       |
  A-------B---[X]----C-------D   bus
                         |
                         F (feeder between C and D)

Fault level without reactor

Xeq=0.164=0.04 puFault MVA=250.04=625 MVA\begin{aligned} X_{eq} &= \frac{0.16}{4} = 0.04\ \text{pu} \\ \text{Fault MVA} &= \frac{25}{0.04} = 625\ \text{MVA} \end{aligned}

(If=625/(3×11)=32.80I_f = 625/(\sqrt3\times11) = 32.80 kA.)

Reactor between B and C for 40 % reduction

New fault MVA =0.6×625=375= 0.6\times625 = 375 MVA, so Xeq,new=25/375=0.06667X_{eq,new} = 25/375 = 0.06667 pu.

With the reactor, G3 and G4 feed the fault directly (0.16∥0.16=0.080.16\parallel0.16 = 0.08 pu) and G1, G2 feed it through XX (0.08+X0.08 + X):

10.06667=10.08+10.08+X15=12.5+10.08+X0.08+X=0.4X=0.32 pu\begin{aligned} \frac{1}{0.06667} &= \frac{1}{0.08} + \frac{1}{0.08+X} \\ 15 &= 12.5 + \frac{1}{0.08+X} \\ 0.08 + X &= 0.4 \\ X &= 0.32\ \text{pu} \end{aligned} X(Ω)=0.32×4.84=1.549 ΩX(\Omega) = 0.32\times4.84 = 1.549\ \Omega

Answer: Fault level = 625 MVA; bus-bar reactor between B and C = 0.32 pu (32 %) on 25 MVA ≈ 1.549 Ω, giving 375 MVA.

  • 2073 Shrawan · 5 marks

Why is reactor used in power system? Explain different types of reactor.

Answer

Reactors are coils with large inductive reactance and very small resistance. They are used in power systems mainly to limit short-circuit current so that circuit breakers and equipment are not over-stressed, and to localise faults.

Why reactors are used

  • Fault current If=V/XI_f = V/X; adding reactance cuts IfI_f and the fault MVA, so cheaper breakers can be used.
  • Keep the voltage on healthy sections from collapsing during a fault.
  • Reduce mechanical forces and heating in windings during short circuits.
  • Shunt reactors absorb surplus VAr on long, lightly loaded lines.

Types by construction

TypeFeature
Air-core (dry)Cement/concrete former, no iron; constant reactance, no saturation; used up to about 33 kV
Oil-immersed, air-coreCoil in oil tank; better insulation and cooling; for high voltage
Oil-immersed, iron-core (gapped)Smaller size; reactance may fall at high current due to saturation

Types by location (reactor schemes)

  1. Generator reactor: in series with each generator. Protects the generator, but is in circuit all the time, so causes constant voltage drop and loss. Modern generators have enough internal reactance, so it is seldom used.
  2. Feeder reactor: in series with each outgoing feeder. A fault on one feeder does not disturb the bus voltage much. But it gives no protection for bus faults, and causes drop and loss on each feeder.
  3. Bus-bar reactor: connects sections of the bus.
    • Ring system: sections joined in a ring through reactors.
    • Tie-bar system: each section connects through a reactor to a common tie-bar; fault current from other sections passes through two reactors.

Shunt reactor

Connected between line and earth at the end of long EHV lines to absorb charging current and limit the rise of receiving-end voltage (Ferranti effect).

  • 2073 Chaitra · 6 marks

Below figure shows two Alternators operating in parallel. [Figure: G1 500 kVA, X1 = 15%, connected through a breaker to point A; G2 500 kVA, X2 = 15%, connected through a breaker to point C; points A, B, C lie on the 11 kV busbar; the feeder leaves from point B through a breaker and a reactor X = 20 ohms, with a 3 phase to ground fault on the feeder] (i) Calculate the fault current in outgoing feeder and fault current supplied by each alternator. (ii) If a reactor of 10 ohm is connected between point A and point B, calculate new fault current in outgoing feeder and fault current supplied by each alternator.

Answer

Work in ohms. Phase voltage Vph=11000/3=6350.85V_{ph} = 11000/\sqrt3 = 6350.85 V, and If=Vph/XtotalI_f = V_{ph}/X_{total}.

Zbase=1120.5=242 ΩXG1=XG2=0.15×242=36.3 Ω\begin{aligned} Z_{base} &= \frac{11^2}{0.5} = 242\ \Omega \\ X_{G1} = X_{G2} &= 0.15\times242 = 36.3\ \Omega \end{aligned}
   G1 500kVA        G2 500kVA
    15%              15%
     |                |
    CB               CB
     |                |
  ===A==[10]===B======C=== 11 kV
              |   ([10] only in part ii)
             CB
              |
            X=20 ohm
              |
              F

(i) Without reactor between A and B

Xpar=36.32=18.15 ΩXtotal=18.15+20=38.15 ΩIf=6350.8538.15=166.47 A\begin{aligned} X_{par} &= \frac{36.3}{2} = 18.15\ \Omega \\ X_{total} &= 18.15 + 20 = 38.15\ \Omega \\ I_f &= \frac{6350.85}{38.15} = 166.47\ \text{A} \end{aligned}

Each alternator supplies 166.47/2=83.24166.47/2 = 83.24 A.

(ii) With 10 Ω between A and B

XG1,path=36.3+10=46.3 ΩXpar=46.3×36.346.3+36.3=20.347 ΩXtotal=20.347+20=40.347 ΩIf=6350.8540.347=157.40 A\begin{aligned} X_{G1,path} &= 36.3 + 10 = 46.3\ \Omega \\ X_{par} &= \frac{46.3\times36.3}{46.3+36.3} = 20.347\ \Omega \\ X_{total} &= 20.347 + 20 = 40.347\ \Omega \\ I_f &= \frac{6350.85}{40.347} = 157.40\ \text{A} \end{aligned}

Sharing (inversely as path reactance):

IG1=157.40×36.382.6=69.17 AIG2=157.40×46.382.6=88.23 A\begin{aligned} I_{G1} &= 157.40\times\frac{36.3}{82.6} = 69.17\ \text{A} \\ I_{G2} &= 157.40\times\frac{46.3}{82.6} = 88.23\ \text{A} \end{aligned}

Answer: (i) IfI_f = 166.47 A, each alternator 83.24 A. (ii) IfI_f = 157.40 A; G1 supplies 69.17 A, G2 supplies 88.23 A.

  • 2072 Kartik · 8 marks

Explain reactors used in generating stations and substations with diagram. Also discuss their merits and demerits along with field of application.

Answer

A reactor is an inductive coil with high reactance and negligible resistance. In generating stations and substations it is used to limit short-circuit current, localise faults and keep bus voltage up on healthy sections. Air-core (dry, concrete-supported) reactors are common because their reactance does not fall by saturation at high fault current.

1. Generator reactors

  G1      G2      G3
  |       |       |
 [X]     [X]     [X]
  |       |       |
 =+=======+=======+===  bus
     |       |
  feeders
  • Merits: protects each generator from heavy fault current; useful for old machines with low reactance.
  • Demerits: always carries full load current, so constant voltage drop and I2RI^2R loss; a bus or feeder fault still affects all generators; gives no protection between feeders.
  • Application: rarely used now, since modern generators have enough leakage reactance.

2. Feeder reactors

  G1      G2
  |       |
 =+===+===+===+===  bus
      |       |
     [X]     [X]
      |       |
   feeder1  feeder2
  • Merits: a fault on one feeder hardly affects bus voltage, so other feeders keep supplying; breaker ratings of feeders reduced.
  • Demerits: no protection for bus-bar faults; constant drop and loss on every feeder; poor regulation.
  • Application: distribution substations with many radial feeders.

3. Bus-bar reactors

(a) Ring system

  G1          G2          G3
  |           |           |
 =S1===[X]===S2===[X]===S3=
  |                        |
  +----------[X]-----------+

(b) Tie-bar system

  G1      G2      G3
  |       |       |
 =S1=    =S2=    =S3=   sections
  |       |       |
 [X]     [X]     [X]
  |       |       |
 =+=======+=======+=  tie-bar
  • Merits: in normal operation little current flows through bus reactors, so loss and drop are small; a fault is confined to one section; tie-bar system lets sections be added easily, and fault current from other sections passes through two reactors in series.
  • Demerits: a fault on a section gets full fault current from its own generator; tie-bar needs an extra bus; large voltage difference between sections if loads are unbalanced.
  • Application: large generating stations with several sections and many generators.

Summary

SchemeNormal lossProtects against
Generator reactorHighGenerator faults
Feeder reactorHighFeeder faults
Bus-bar (ring/tie-bar)LowFaults within a section
  • 2071 Shrawan · 8 marks

Figure below shows a bus-bar reactor scheme. If a 3 phase to ground fault occurs on the outgoing feeder, calculate the fault current (in kA) supplied by each generator and fault MVA required for the circuit breaker (CB) on the feeder. Rating of generators are given as follow: G1: 30MVA, 11kV, Xg1" = 0.1 pu; G2: 50MVA, 11kV, Xg2" = 0.1 pu. [Figure: G1 (0.1 pu) and G2 (0.1 pu) on two bus-bar sections joined by a bus-bar reactor X = 0.2 ohm; the feeder leaves the G1 section through the CB]

Answer

G1 and G2 are on two bus sections joined by a bus-bar reactor. The feeder is on the G1 section; its reactance is not given, so the fault is taken just beyond the CB. G1 feeds directly; G2 feeds through the bus reactor. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}.

Base: 50 MVA, 11 kV; Zbase=112/50=2.42 ΩZ_{base} = 11^2/50 = 2.42\ \Omega; Ibase=50×1063×11×103=2624.3 AI_{base} = \dfrac{50\times10^6}{\sqrt3\times11\times10^3} = 2624.3\ \text{A}.

  G1 30MVA,0.1        G2 50MVA,0.1
      |                    |
 ===[Sec 1]====[X=0.2 ohm]====[Sec 2]===
      |
     CB
      |--- F

Reactances on 50 MVA base

XG1=0.1×5030=0.16667 puXG2=0.1 puXR=0.22.42=0.08264 puXG2+XR=0.18264 pu\begin{aligned} X_{G1} &= 0.1\times\frac{50}{30} = 0.16667\ \text{pu} \\ X_{G2} &= 0.1\ \text{pu} \\ X_R &= \frac{0.2}{2.42} = 0.08264\ \text{pu} \\ X_{G2}+X_R &= 0.18264\ \text{pu} \end{aligned}

Fault current and fault MVA

Xeq=0.16667×0.182640.16667+0.18264=0.087145 puIf=2624.30.087145=30,114 A=30.11 kAFault MVA=500.087145=573.76 MVA\begin{aligned} X_{eq} &= \frac{0.16667\times0.18264}{0.16667+0.18264} = 0.087145\ \text{pu} \\ I_f &= \frac{2624.3}{0.087145} = 30{,}114\ \text{A} = 30.11\ \text{kA} \\ \text{Fault MVA} &= \frac{50}{0.087145} = 573.76\ \text{MVA} \end{aligned}

Current from each generator

IG1=30.114×0.182640.34931=15.75 kAIG2=30.114×0.166670.34931=14.37 kA\begin{aligned} I_{G1} &= 30.114\times\frac{0.18264}{0.34931} = 15.75\ \text{kA} \\ I_{G2} &= 30.114\times\frac{0.16667}{0.34931} = 14.37\ \text{kA} \end{aligned}

Answer: G1 supplies ≈ 15.75 kA, G2 ≈ 14.37 kA (total 30.11 kA); the feeder CB must be rated for about 574 MVA.

  • 2071 Chaitra · 5 marks

In figure below a bus-bar reactor scheme with four generators. If a 3 phase to ground fault occurs on the outgoing feeder, calculate the fault current (in kA) supplied by each generator and fault MVA required for the circuit breaker (CB) on the feeder. Rating of generators are given as follow: G1/G2: [?]MVA, 11kV, Xg1" = 0.2 pu; G3/G4: [?]MVA, 11kV, Xg2" = 0.1 pu. [Figure: G1 (0.2 pu) and G2 (0.2 pu) on one bus-bar section, G3 (0.1 pu) and G4 (0.1 pu) on the other, the two sections joined by a bus-bar reactor X = 0.2 ohms; the feeders leave the G1/G2 section through the CB] (Generator MVA ratings are unreadable in the scan.)

Answer

The generator MVA ratings are not readable, so assume G1 = G2 = 30 MVA and G3 = G4 = 50 MVA, all 11 kV (the method is the same for any rating). The feeder reactance is not given, so the fault is taken just beyond the CB. G1 and G2 feed directly; G3 and G4 feed through the bus-bar reactor.

Base: 50 MVA, 11 kV; Zbase=2.42 ΩZ_{base} = 2.42\ \Omega; Ibase=2624.3 AI_{base} = 2624.3\ \text{A}.

  G1     G2            G3     G4
  0.2    0.2           0.1    0.1
  |      |             |      |
 ==[Section 1]==[X=0.2 ohm]==[Section 2]==
       |
      CB
       |--- F

Reactances on 50 MVA base

XG1=XG2=0.2×5030=0.33333 pu  ⇒  X12=0.16667 puXG3=XG4=0.1 pu  ⇒  X34=0.05 puXR=0.22.42=0.08264 puX34+XR=0.13264 pu\begin{aligned} X_{G1} = X_{G2} &= 0.2\times\frac{50}{30} = 0.33333\ \text{pu} \;\Rightarrow\; X_{12} = 0.16667\ \text{pu} \\ X_{G3} = X_{G4} &= 0.1\ \text{pu} \;\Rightarrow\; X_{34} = 0.05\ \text{pu} \\ X_R &= \frac{0.2}{2.42} = 0.08264\ \text{pu} \\ X_{34} + X_R &= 0.13264\ \text{pu} \end{aligned}

Fault MVA and fault current

Xeq=0.16667×0.132640.16667+0.13264=0.073861 puFault MVA=500.073861=676.95 MVAIf=2624.30.073861=35,531 A=35.53 kA\begin{aligned} X_{eq} &= \frac{0.16667\times0.13264}{0.16667+0.13264} = 0.073861\ \text{pu} \\ \text{Fault MVA} &= \frac{50}{0.073861} = 676.95\ \text{MVA} \\ I_f &= \frac{2624.3}{0.073861} = 35{,}531\ \text{A} = 35.53\ \text{kA} \end{aligned}

Current from each generator

IG1+G2=35.53×0.132640.29931=15.75 kA⇒IG1=IG2=7.87 kAIG3+G4=35.53×0.166670.29931=19.78 kA⇒IG3=IG4=9.89 kA\begin{aligned} I_{G1+G2} &= 35.53\times\frac{0.13264}{0.29931} = 15.75\ \text{kA} \Rightarrow I_{G1} = I_{G2} = 7.87\ \text{kA} \\ I_{G3+G4} &= 35.53\times\frac{0.16667}{0.29931} = 19.78\ \text{kA} \Rightarrow I_{G3} = I_{G4} = 9.89\ \text{kA} \end{aligned}

Answer (with the assumed ratings): G1, G2 ≈ 7.87 kA each; G3, G4 ≈ 9.89 kA each; total 35.53 kA; CB fault rating ≈ 677 MVA.

  • 2070 Chaitra · 8 marks

Explain different reactor schemes used in generating station and substations.

Answer

Current-limiting reactors are placed at chosen points of a station so that the short-circuit current is limited and a fault in one part does not collapse the voltage of the whole station. The main schemes are below.

1. Generator reactor scheme

Reactor in series with each generator, between the generator and the bus.

  G1      G2      G3
 [X]     [X]     [X]
  |       |       |
 =+===+===+===+===+=  bus
      |       |
   feeders
  • Protects the generator against faults beyond it.
  • Disadvantage: full load current always flows, so constant voltage drop and loss; a feeder fault still lowers the whole bus voltage. Now seldom used, as modern machines have high reactance.

2. Feeder reactor scheme

Reactor in series with each outgoing feeder.

  G1      G2
  |       |
 =+===+===+===+=  bus
     [X]     [X]
      |       |
   feeder   feeder
  • A feeder fault is limited by its own reactor; the bus voltage stays nearly normal, so other feeders are not disturbed.
  • Disadvantage: no protection against bus faults; constant drop and loss in each feeder.

3. Bus-bar reactor schemes

The bus is divided into sections, each with a generator; sections are joined through reactors. In normal operation little current passes between sections, so losses are small.

(a) Ring system: each section connected to the next through a reactor, forming a ring.

  G1          G2          G3
 =S1===[X]===S2===[X]===S3=
  |                        |
  +----------[X]-----------+

A fault on one section is fed by the other generators only through reactors. Each section is fed from both sides, so it is more reliable than a straight in-line arrangement.

(b) Tie-bar system: each section is connected through its own reactor to a common tie-bar.

 =S1=    =S2=    =S3=   sections
 [X]     [X]     [X]
  |       |       |
 =+=======+=======+=  tie-bar

Fault current from any other section passes through two reactors in series, so each reactor can be about half the value needed in a ring system. New sections are added easily. It needs an additional bus-bar.

Comparison

SchemeNormal loss/dropMain meritMain demerit
GeneratorHighProtects generatorConstant loss
FeederHighBus voltage held on feeder faultNo bus-fault protection
Ring busLowFault confined to sectionUnbalanced loads cause section voltage difference
Tie-barLowTwo reactors in fault path; easy extensionExtra tie-bar cost
  • 2069 Chaitra · 8 marks

Figure below shows the single line diagram of parallel operated generators. Their ratings are: G1: capacity = 50 MW, 11kV, X1 = 0.16 pu based on its rating; G2: capacity = 50MW, 11kV, X2 = 0.16 pu based on its rating; Xl = 2 ohms. [Figure: G1 (through X1) and G2 (through X2), both star-grounded, connected to a common busbar; the feeder leaves the busbar through Xl] Calculate the fault current in the feeder during 3 phases to ground fault on the feeder. Calculate the value of inductance (in mH) of the reactor to be connected in series with Xl so that the fault current decreases by 40%.

Answer

Ratings in MW are taken as MVA (unity power factor). Fault current If=Ibase/XeqI_f = I_{base}/X_{eq}; ohms to pu: Xpu=XΩ MVAb/kV2X_{pu} = X_\Omega\,\text{MVA}_b/\text{kV}^2.

Base: 50 MVA, 11 kV; Zbase=112/50=2.42 ΩZ_{base} = 11^2/50 = 2.42\ \Omega; Ibase=50×1063×11×103=2624.3 AI_{base} = \dfrac{50\times10^6}{\sqrt3\times11\times10^3} = 2624.3\ \text{A}.

  G1 50MW,0.16   G2 50MW,0.16
      |              |
  ====+======+=======+==== 11 kV
             |
           Xl=2 ohm + new L
             |
             F

Fault current

X1∥X2=0.162=0.08 puXl=22.42=0.82645 puXeq=0.08+0.82645=0.90645 puIf=2624.30.90645=2895.2 A\begin{aligned} X_1\parallel X_2 &= \frac{0.16}{2} = 0.08\ \text{pu} \\ X_l &= \frac{2}{2.42} = 0.82645\ \text{pu} \\ X_{eq} &= 0.08 + 0.82645 = 0.90645\ \text{pu} \\ I_f &= \frac{2624.3}{0.90645} = 2895.2\ \text{A} \end{aligned}

(Fault MVA =50/0.90645=55.16= 50/0.90645 = 55.16 MVA.)

Reactor for 40 % reduction in fault current

New If=0.6×2895.2=1737.1I_f = 0.6\times2895.2 = 1737.1 A, so the total reactance must become Xeq/0.6X_{eq}/0.6:

Xeq,new=0.906450.6=1.51074 puXadd=1.51074−0.90645=0.60430 puXadd(Ω)=0.60430×2.42=1.4624 ΩL=1.46242π×50=4.655×10−3 H\begin{aligned} X_{eq,new} &= \frac{0.90645}{0.6} = 1.51074\ \text{pu} \\ X_{add} &= 1.51074 - 0.90645 = 0.60430\ \text{pu} \\ X_{add}(\Omega) &= 0.60430\times2.42 = 1.4624\ \Omega \\ L &= \frac{1.4624}{2\pi\times50} = 4.655\times10^{-3}\ \text{H} \end{aligned}

Answer: IfI_f ≈ 2895 A; series reactor ≈ 1.462 Ω, i.e. L ≈ 4.65 mH (fault current falls to about 1737 A).

Questions from Old Question Collection (EE 703) (IOE EE 703 exam papers from 2073 Shrawan to 2082 Baisakh) and Question bank (ioesolutions) (IOE EE 703 exam papers from 2069 Chaitra to 2073 Chaitra). Answers are written for this site; check them against your class notes.

Chapter titles and hours from the IOE syllabus ↗