Chapter 2 · 10 hours
Power/Frequency Control in Hydro Generator System
IOE past exam questions
Past questions and answers
32 questions set from this chapter, 12 of them more than once. Most asked first.
- Asked 6 times
- 2081 Baisakh · 5 marks
- 2080 Baisakh · 4 marks
- 2078 Bhadra · 4 marks
- 2071 Chaitra · 4 marks
- 2073 Shrawan · 3 marks
- 2071 Shrawan · 8 marks
What is isochronous governor? Explain with its closed loop control system. Why it is not suitable for two generating units operating in parallel?
Answer
An isochronous governor is a speed governor that keeps the turbine speed (frequency) exactly constant at the set value for every load. "Isochronous" means "same speed". It uses integral action: the gate keeps moving as long as there is a speed error.
Closed loop control system
w_ref + error +------+ dY +-------+ dPm
---->(+)-------->| K/s |--->|turbine|---+
^ - +------+ +-------+ |
| v
| -dPL -->(+)
| +-----------+ |
+------| 1/(2Hs+D) |<--------------+
speed +-----------+
Governor law:
Operation:
- Load increases, , so the rotor slows down.
- The speed error is integrated; the integrator output opens the gate.
- increases; once it exceeds the rotor accelerates back.
- The integrator stops changing only when the error is zero. So in steady state and : zero steady-state frequency error.
speed
w0 |-----. .---------- w0 (restored)
| \ /
| '.___.'
+-------------------------> t
Pm rises until Pm = Pe
Why it is not suitable for units in parallel
- Units in parallel are tied to the same frequency. Each isochronous governor tries to hold the frequency at its own set value.
- The set points can never be exactly equal. If unit 1 is set at 50.01 Hz and unit 2 at 50.00 Hz, unit 1 keeps opening its gate to raise frequency while unit 2 keeps closing, so they fight each other. One unit is driven to full load and the other to zero (or motoring).
- With integral control there is no unique load sharing: the load can be divided in any ratio and drifts. The operating point is not stable.
- Therefore only one unit in a system (or an isolated unit) may run isochronous. Other units use a speed droop characteristic, which gives a definite sharing of load in proportion to .
- Asked 6 times
- 2076 Asoj · 8 marks
- 2079 Bhadra · 5 marks
- 2070 Asar · 8 marks
- 2078 Bhadra · 5 marks
- 2075 Chaitra · 6 marks
- 2071 Chaitra · 6 marks
Below figure shows the block diagram of water turbine driving an electric generator without speed governor. Explain how the inertia and load damping constant can control the speed of the system against small change in load. Derive the transfer function showing the effect of inertia and load damping constant. [Figure: turbine coupled by a shaft to a generator, which supplies a composite load]
Answer
Without a governor, the gate (and so mechanical power ) stays fixed. When load changes, speed is held back only by two natural effects: the inertia of the rotating masses, which slows the rate of speed change, and the load damping, which reduces the load as frequency falls so that a new balance is reached.
Derivation of the transfer function
Inertia (rotating mass): for small changes, in per unit, the swing equation is
where = inertia constant (s), = speed deviation (pu). Taking the Laplace transform,
Load damping: a composite load has frequency-insensitive parts (lighting, heating) and frequency-sensitive parts (motors). So
where = non-frequency-sensitive load change and = load damping constant (% change in load per % change in frequency, typically 1–2).
Substituting,
Without a governor , so
dPm=0 + +--------------+
------>(+)->| 1 |----+--> d(omega)
^ - | 2Hs + D | |
| +--------------+ |
dPL
Response to a small step change in load
For a step :
d(omega)
0 |-----.
| \
| '-.
| '--.______ -dPL/D
+------------------------> t
T = 2H/D
Role of inertia and load damping
- Inertia (H): At the first instant is unchanged, so the extra load is supplied from the kinetic energy of the rotor. Speed starts to fall at a rate . Larger gives a slower fall and a larger time constant . Inertia does not change the final value; it only slows the change.
- Load damping (D): As frequency falls, motor loads take less power (). The fall stops when this reduction equals , giving steady-state deviation . Larger gives a smaller final speed error and a faster settling.
- Since is small (1–2), the steady speed error is large: e.g. pu and gives a 1 % drop in frequency. So a governor is needed to restore speed; inertia and damping only make the system self-regulating for small changes.
- Asked 3 times
- 2070 Chaitra · 10 marks
- 2081 Baisakh · 5 marks
- 2074 Asoj · 8 marks
The figure below shows a turbine-generator coupled system with speed governor. Explain the transient responses of electrical power output (Pe), mechanical power input (Pm) and speed due to sudden increase in electrical load by an amount of ΔPL. [Figure: water enters the turbine through a valve controlled by the governor; the turbine (Pm) is coupled to the generator, which delivers Pe to the load]
Answer
With a speed governor, the turbine-generator responds to a sudden load increase by first giving up stored kinetic energy and then, through governor action, increasing the water flow until mechanical input again equals electrical output.
System model
Inertia (rotating mass): for small changes, in per unit, the swing equation is
where = inertia constant (s), = speed deviation (pu). Taking the Laplace transform,
Load damping: a composite load has frequency-insensitive parts (lighting, heating) and frequency-sensitive parts (motors). So
where = non-frequency-sensitive load change and = load damping constant (% change in load per % change in frequency, typically 1–2).
Substituting,
The governor with speed droop gives
and the hydraulic turbine gives
dPref + +-------+ dPv +-------+ dPm
---->(+)---->| 1 |---->|turbine|---+
^ - |1+sTg | | Gt(s) | |
| +-------+ +-------+ v
+-----+ -dPL --->(+)
| 1/R | |
+-----+ +-----------+ |
^ dw | 1 | |
+---------| 2Hs + D |<---------+
+-----------+
Transient response to a sudden load increase
When a load is suddenly added:
- Instant : the electrical output rises at once by , because the generator must supply the connected load immediately. The mechanical input cannot change instantly (gate and water need time).
- Deceleration: the deficit is supplied from the kinetic energy of the rotor, so speed starts to fall with slope .
- Load damping: as speed falls, frequency-sensitive load drops by , so comes down slightly from its initial jump.
- Governor action: the speed fall is sensed; through the droop the governor opens the gate. For a hydro turbine, first dips (water inertia, non-minimum phase) and then rises.
- Recovery: when exceeds , the rotor accelerates and the fall in speed is arrested. After some oscillation, and speed settles at a new, lower value.
Steady state, from the block diagram ():
power
| Pe
P0+ | ._____
dPL | | '--.________ Pm = Pe (final)
| | _.-'
| | _.' Pm
P0 |---'. .'
| '.' (hydro: Pm dips first)
+---------------------------> t
speed
|----.
| \ .--------
| '._ _.' dw_ss = -dPL/(D+1/R)
| ''
+---------------------------> t
- Electrical power : jumps by at once, then reduces slightly as frequency falls (load damping) and settles at .
- Mechanical power : starts at the old value (dips first in a hydro unit), rises with the governor and turbine time constants, overshoots slightly, and settles equal to .
- Speed: falls, reaches a minimum (frequency nadir), recovers partly and settles at a lower value fixed by the droop. With an isochronous governor () speed would return to nominal. Supplementary control (load reference change) is then used to bring the frequency back to 50 Hz.
Conclusion: inertia limits the initial rate of fall, the governor limits the depth of the fall and brings up to match , and the droop leaves a small steady frequency error which is removed by changing the load reference.
- Asked 3 times
- 2071 Shrawan · 8 marks
- 2079 Baisakh · 8 marks
- 2073 Shrawan · 4 marks
Explain with neat diagram, the P-F loop and Q-V loop in hydro generating system.
Answer
A hydro generating unit has two main control loops. The P-f loop (automatic load frequency control, ALFC) controls real power and frequency through the turbine gate. The Q-V loop (automatic voltage regulator, AVR) controls reactive power and terminal voltage through the field excitation.
P-f loop (ALFC)
f_ref -->(+)--> speed governor --> hydraulic
^ - amplifier
| |
| v
frequency sensor wicket gates
^ |
| v
+----- speed ------ turbine-generator
Q-V loop (AVR)
V_ref -->(+)--> amplifier --> exciter
^ - |
| v
PT + rectifier generator field
^ |
| v
+------ Vt ----- generator terminals
P-f loop
- A speed (frequency) sensor measures the shaft speed.
- The speed governor compares it with the reference and, through the speed droop, gives a command to the hydraulic amplifier (pilot valve and servomotor).
- The servomotor moves the wicket gates (or needle), changing the water flow and the turbine power .
- Real power balance decides frequency: if frequency falls. The loop restores balance. Primary control uses droop; secondary control changes the load reference to restore 50 Hz.
- It is slow (seconds) because of large mechanical and water time constants.
Q-V loop
- A potential transformer measures terminal voltage; it is rectified and filtered.
- The comparator finds the error .
- The amplifier boosts it and drives the exciter, which changes the field current of the generator.
- Field current changes the generated emf and hence the reactive power output and terminal voltage.
- It is fast (fraction of a second) because electrical time constants are small. Stabilising feedback is used to avoid oscillations.
Interaction
Real power depends mainly on rotor angle and frequency, while reactive power depends mainly on voltage magnitude. Also, the AVR loop is much faster than the P-f loop. So the two loops are weakly coupled and are analysed and designed separately (decoupled control).
- Asked 2 times
- 2082 Baisakh · 8 marks
- 2072 Chaitra · 8 marks
Two generating units rated as 250 MW and 500 MW have speed droop regulation of 20% and 10% respectively based on their rating. They are operated in parallel and each is half loaded at a common frequency of 50 Hz. If the load is increased by 60 MW, calculate: i) New frequency at which operates ii) New loading of each generating units
Answer
When load rises, both units move down their droop lines to a common lower frequency; each picks up load in proportion to its stiffness .
Method: with droop (pu, on its own rating ) and rated frequency , the droop line of each unit gives
where is the stiffness of the unit in MW/Hz. For the units together, .
Data: MW, ; MW, ; Hz. Initial loading: 125 MW and 250 MW. MW.
Stiffness of each unit:
i) New frequency
ii) New loading of each unit
Check: MW.
| Unit | Rating (MW) | Droop | Initial (MW) | Increase (MW) | New load (MW) |
|---|---|---|---|---|---|
| 1 | 250 | 20 % | 125 | 12 | 137 |
| 2 | 500 | 10 % | 250 | 48 | 298 |
Answer: New frequency = 49.52 Hz; unit 1 carries 137 MW and unit 2 carries 298 MW. The 500 MW unit, with the smaller droop (stiffer), takes 80 % of the increase.
- Asked 2 times
- 2082 Baisakh · 8 marks
- 2072 Chaitra · 6 marks
Derive the transfer function for speed response for load change in turbine-generator set in the absence of governor. Also, explain how isochronous governor can be incorporated together with turbine-generator with block diagram.
Answer
Transfer function without governor
Without a governor, the turbine gate is fixed, so and the speed is decided only by rotor inertia and load damping.
Inertia (rotating mass): for small changes, in per unit, the swing equation is
where = inertia constant (s), = speed deviation (pu). Taking the Laplace transform,
Load damping: a composite load has frequency-insensitive parts (lighting, heating) and frequency-sensitive parts (motors). So
where = non-frequency-sensitive load change and = load damping constant (% change in load per % change in frequency, typically 1–2).
Substituting,
With :
dPm=0 + +--------------+
------>(+)->| 1 |----+--> d(omega)
^ - | 2Hs + D | |
| +--------------+ |
dPL
For a step load :
The speed falls exponentially with time constant and settles at , which is a large error because is small.
Incorporating an isochronous governor
An isochronous (constant speed) governor uses integral control. It measures speed, compares with the reference, and integrates the error to move the gate:
The gate keeps moving as long as there is any speed error, so speed returns exactly to the set value.
dPL
| -
+-------+ dPm v +-----------+
|turbine|--------------->(+)---->| 1/(2Hs+D) |--+--> dw
| Gt(s) | + +-----------+ |
+-------+ |
^ dY |
+-------+ - |
| K/s |<---(+)<-------------------------------+
+-------+ ^ +
| dw_ref = 0
Here is the turbine transfer function (for hydro, ).
Working: a load rise makes speed fall; the integrator output grows, gates open, rises above , the rotor accelerates and speed comes back to the reference. In steady state and .
The isochronous governor works well for a single unit supplying an isolated load. It cannot be used on several units in parallel, because each would try to fix the frequency at its own set point and they would fight for the load; for that, speed droop is added.
- Asked 2 times
- 2081 Bhadra · 6 marks
- 2072 Kartik · 8 marks
Derive the transfer function of water turbine relating gate position and mechanical power output. Explain the special characteristic of hydraulic turbine.
Answer
The water turbine transfer function relates a small change in gate position to the change in mechanical power. Because the water column in the penstock has inertia, the turbine is a non-minimum phase system.
Derivation
Assumptions: lossless turbine, incompressible water, rigid penstock, and small changes about an operating point.
Velocity of water in the penstock: , where = gate opening and = head at the gate.
Turbine power: .
Linearising and normalising by initial values (), with bar for per-unit change:
Eliminating :
Acceleration of the water column (length , area ): the net force from the head change accelerates the water mass,
where the water starting time is
In Laplace form: , so
Substituting in :
Special characteristics of a hydraulic turbine
- Non-minimum phase response: the transfer function has a zero in the right-half plane at . Power initially changes opposite to the gate movement. For a unit step in gate opening, power first falls to pu and then rises to pu with time constant :
- Water inertia decides the response. is typically 0.5–4 s and changes with load, because and change.
- Governor needs transient droop: a fast governor with normal droop would be unstable. So hydro governors have a large temporary droop with a reset time (or slow integral action), making hydro units slower to respond than steam units.
- Water hammer: quick gate closing causes pressure rise; gate speed must be limited.
- Hydro turbines can start and pick up load quickly from standstill, so they are good for peaking and frequency control once the above is allowed for.
- Asked 2 times
- 2080 Bhadra · 10 marks
- 2076 Chaitra · 5 marks
Two generating units has following rating and droop characteristics: Unit – 1: 600 MVA, R1 = 4%; Unit – 2: 500 MVA, R2 = 6%. These two units are operating in parallel and sharing a total load of 900 MW at nominal frequency of 60 Hz. Unit – 1 supplies 500 MW and unit – 2 supplies 400 MW. If the load increases by 90 MW, calculate the new frequency and new generation of each generator.
Answer
Both units share the load increase in proportion to , and the frequency falls to a common new value.
Method: with droop (pu, on its own rating ) and rated frequency , the droop line of each unit gives
where is the stiffness of the unit in MW/Hz. For the units together, .
Data: Unit 1: 600 MVA, ; Unit 2: 500 MVA, ; Hz. Initial: MW, MW. MW. (MVA ratings are used as the MW base, i.e. unity power factor rating.)
Stiffness:
New frequency:
(In per unit, pu.)
New generation:
| Unit | Rating | Droop | Initial (MW) | Increase (MW) | New (MW) |
|---|---|---|---|---|---|
| 1 | 600 MVA | 4 % | 500 | 57.86 | 557.86 |
| 2 | 500 MVA | 6 % | 400 | 32.14 | 432.14 |
Check: MW.
Answer: New frequency ≈ 59.77 Hz (drop of 0.231 Hz); unit 1 generates 557.86 MW and unit 2 generates 432.14 MW.
- Asked 2 times
- 2078 Bhadra · 6 marks
- 2072 Chaitra · 6 marks
Derive the transfer function of a water turbine and explain the response against unit step change in gate opening.
Answer
The water turbine transfer function relates a small change in gate opening to the change in mechanical power output. Due to the inertia of water in the penstock, power first moves in the wrong direction when the gate is moved.
Derivation of the transfer function
Assumptions: lossless turbine, incompressible water, rigid penstock, and small changes about an operating point.
Velocity of water in the penstock: , where = gate opening and = head at the gate.
Turbine power: .
Linearising and normalising by initial values (), with bar for per-unit change:
Eliminating :
Acceleration of the water column (length , area ): the net force from the head change accelerates the water mass,
where the water starting time is
In Laplace form: , so
Substituting in :
Response to a unit step change in gate opening
For a unit step :
Initial value ():
Final value ():
Time response:
dPm
1 | ____________
| _.-'
0 |----. _-'
| | .'
| | / time constant Tw/2
-2 | |_/
+----+-------------------------> t
gate step at t = 0
Explanation: when the gate opens suddenly, the flow cannot increase at once because the water column has inertia. The larger opening with the same flow lowers the pressure (head) at the turbine, so power first drops to times the gate change. As the water accelerates, flow and power rise, and power settles at times the gate change with time constant . Similarly, closing the gate first gives a power rise (with pressure rise, i.e. water hammer).
This behaviour (zero in the right-half plane) is why hydro governors are given a large transient droop and a slower response.
- Asked 2 times
- 2076 Chaitra · 5 marks
- 2074 Asoj · 8 marks
Explain the importance of speed droop in sharing common load by two alternator operating in parallel with suitable block diagram and derivation.
Answer
Speed droop is the drop in speed (frequency) of a governed unit as its load goes from no load to full load, expressed in per unit of rated speed. It is defined by
A 4 % droop means the frequency falls by 4 % (2 Hz at 50 Hz) from no load to full load. Droop gives every governor a definite speed–load line, so parallel units share a load change in a fixed, stable ratio. Without droop (isochronous governors), parallel units fight each other and the load division is undefined.
Block diagram (two units on a common bus)
+-->[1/R1]--+
| v -
| dPref1->(+)->[Gov1]->[Turb1]--dPm1--+
| v
| -dPL ------->(S)--+
| ^ |
| dPref2->(+)->[Gov2]->[Turb2]--dPm2--+ |
| ^ - v
+-->[1/R2]--+ [1/(2Hs+D)]
| |
+--------------- d(omega) -----------------+
S = summing point: .
Both units see the same frequency deviation because they are synchronised.
Derivation
In steady state, the governor of unit obeys its droop line:
With fixed references ():
The total change must supply the load change:
and the ratio of sharing is
If (same per-unit droop), , i.e. load is shared in proportion to ratings.
f f
f0|\ unit 1 |\ unit 2
| \ | \
f'|--*-----common f'--|---*
| \ | \
+----+---> P1 +-----+---> P2
P1' P2'
Importance
- Gives a unique, stable division of load among parallel units.
- A smaller droop makes a unit "stiffer", so it takes a bigger share of any change.
- Equal per-unit droop on all units makes each carry load proportional to its rating, avoiding overload of small units.
- The frequency drop needed is small (typically 4–5 % droop), and the load reference setting is then used to bring frequency back to nominal.
- Asked 2 times
- 2073 Shrawan · 6 marks
- 2070 Asar · 8 marks
Describe the steady state and transient behavior of a turbine generator coupled system with governor.
Answer
A turbine-generator with a speed governor is a closed loop: the governor senses speed and adjusts the gate so that mechanical input matches electrical load.
Model and block diagram
Rotor and load:
Governor with droop:
Turbine: with for hydro.
dPref + +-------+ dPv +-------+ dPm
---->(+)---->| 1 |---->|turbine|---+
^ - |1+sTg | | Gt(s) | |
| +-------+ +-------+ v
+-----+ -dPL --->(+)
| 1/R | |
+-----+ +-----------+ |
^ dw | 1 | |
+---------| 2Hs + D |<---------+
+-----------+
Steady state behaviour
With and a step load , the closed loop gives
Using the final value theorem ():
where is the area frequency response characteristic. Since (e.g. gives ), the governor reduces the frequency error about 20 times compared with no governor.
- Speed-power relation: . This is the droop line: as load rises, speed falls in proportion.
- Units in parallel share a load change in proportion to (i.e. to rating, if all have the same per-unit droop).
- Changing shifts the droop line up or down; this restores frequency to nominal (secondary control).
Transient behaviour
When a load is suddenly added:
- Instant : the electrical output rises at once by , because the generator must supply the connected load immediately. The mechanical input cannot change instantly (gate and water need time).
- Deceleration: the deficit is supplied from the kinetic energy of the rotor, so speed starts to fall with slope .
- Load damping: as speed falls, frequency-sensitive load drops by , so comes down slightly from its initial jump.
- Governor action: the speed fall is sensed; through the droop the governor opens the gate. For a hydro turbine, first dips (water inertia, non-minimum phase) and then rises.
- Recovery: when exceeds , the rotor accelerates and the fall in speed is arrested. After some oscillation, and speed settles at a new, lower value.
Steady state, from the block diagram ():
power
| Pe
P0+ | ._____
dPL | | '--.________ Pm = Pe (final)
| | _.-'
| | _.' Pm
P0 |---'. .'
| '.' (hydro: Pm dips first)
+---------------------------> t
speed
|----.
| \ .--------
| '._ _.' dw_ss = -dPL/(D+1/R)
| ''
+---------------------------> t
- Electrical power : jumps by at once, then reduces slightly as frequency falls (load damping) and settles at .
- Mechanical power : starts at the old value (dips first in a hydro unit), rises with the governor and turbine time constants, overshoots slightly, and settles equal to .
- Speed: falls, reaches a minimum (frequency nadir), recovers partly and settles at a lower value fixed by the droop. With an isochronous governor () speed would return to nominal. Supplementary control (load reference change) is then used to bring the frequency back to 50 Hz.
- Asked 2 times
- 2070 Chaitra · 8 marks
- 2071 Chaitra · 5 marks
Two generators of 250 MW and 500 MW capacities respectively are operating in parallel and connected to a common bus. When Each generator is half loaded, they operates at a common frequency of 50 Hz. Their droops characteristics are 4% and 2% respectively based on their respective capacities. When the system load is increased, the frequency decreases to 49.5 Hz. Calculate the increase in system load and load shared by each generator.
Answer
Both generators move down their droop lines to the common frequency of 49.5 Hz; the load increase is the sum of what each picks up.
Method: with droop (pu, on its own rating ) and rated frequency , the droop line of each unit gives
where is the stiffness of the unit in MW/Hz. For the units together, .
Data: MW, ; MW, ; Hz. Initial loads: 125 MW and 250 MW (half load). Hz.
Stiffness:
Increase in load on each generator:
Increase in system load:
| Generator | Rating (MW) | Droop | Initial (MW) | Increase (MW) | New (MW) |
|---|---|---|---|---|---|
| G1 | 250 | 4 % | 125 | 62.5 | 187.5 |
| G2 | 500 | 2 % | 250 | 250 | 500 |
| Total | 750 | – | 375 | 312.5 | 687.5 |
Answer: The system load increased by 312.5 MW. G1 shares 62.5 MW (now 187.5 MW) and G2 shares 250 MW (now 500 MW, i.e. fully loaded). Any further load increase would overload G2.
- 2081 Baisakh · 10 marks
Two generators of capacities 600MW and 300MW are connected in parallel to supply a common load of 600 MW. Their droop regulations are 3% and 6% respectively w.r.t. their respective ratings. At no-load, they operates at a common frequency of 51 Hz. How they will share the common load of 600MW? When the load is increased by 200 MW, at which frequency they will operate and calculate the power supplied by each generator?
Answer
Both generators start from the same no-load frequency (51 Hz) and move down their droop lines until their outputs add up to the load. Rated frequency is taken as Hz.
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Stiffness:
(Full-load frequency drop: G1 Hz, G2 Hz.)
Sharing of 600 MW
Load increased by 200 MW (total 800 MW)
(Equivalently, the extra 200 MW is shared as MW and MW.)
| Case | Frequency | G1 (MW) | G2 (MW) |
|---|---|---|---|
| Load 600 MW | 49.8 Hz | 480 | 120 |
| Load 800 MW | 49.4 Hz | 640 | 160 |
Answer: At 600 MW: 49.8 Hz, G1 = 480 MW, G2 = 120 MW. At 800 MW: 49.4 Hz, G1 = 640 MW, G2 = 160 MW.
Note: 640 MW is above G1's 600 MW rating. In practice G1's governor would stop at full gate (600 MW) and G2 would carry the remaining 200 MW, so the frequency would settle on G2's line at Hz. Load reference settings should be changed to avoid this overload.
- 2081 Bhadra · 8 marks
Two generating units of 600 MW and 300 MW capacities respectively are operating in parallel and supplying power to common load. When each generator is half loaded, they operate at a common frequency of 50 Hz. The droop regulations are 7% and 8% respectively based on their respective ratings. If the load is increased by 150 MW, Calculate: a) New frequency at which they operate. b) Power supplied by each generator.
Answer
Both units drop along their droop lines to a common new frequency, each taking a share of the extra 150 MW in proportion to .
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: G1: 600 MW, , initial 300 MW; G2: 300 MW, , initial 150 MW; Hz; MW.
Stiffness:
a) New frequency
b) Power supplied by each generator
| Generator | Initial (MW) | Increase (MW) | New (MW) |
|---|---|---|---|
| G1 (600 MW, 7 %) | 300 | 104.35 | 404.35 |
| G2 (300 MW, 8 %) | 150 | 45.65 | 195.65 |
| Total | 450 | 150 | 600 |
Answer: New frequency ≈ 49.39 Hz; G1 supplies 404.35 MW and G2 supplies 195.65 MW.
- 2080 Baisakh · 5 marks
Explain the special characteristics of a hydraulic turbine and what is water starting time?
Answer
A hydraulic turbine responds to gate movement in an unusual way because of the inertia of the water column in the penstock.
Special characteristics
- Non-minimum phase behaviour: the turbine transfer function
has a zero in the right half of the s-plane (). So the power first changes in the opposite direction to the gate movement. 2. Initial reverse power: when the gate is suddenly opened, the flow cannot rise at once because of water inertia, so the head (pressure) at the turbine falls and power first drops to −2 times the gate change. It then rises to +1 times the gate change with time constant : . Closing the gate first gives a power (and pressure) rise. 3. Water inertia governs the response: the response speed is set by the water starting time , which is not constant; it rises with load because increases. 4. Need for transient droop: a governor with only permanent droop would be unstable. Hydro governors use a large temporary (transient) droop with a reset time, so they respond slowly at first and are slower than steam unit governors. 5. Water hammer and gate rate limits: gate movements must be slow enough to keep pressure rise in the penstock safe.
dPm
1 | ____________
| _.-'
0 |---. _-'
| | .'
-2 | |_/ (unit step in gate)
+---+----------------------> t
Water starting time
Water starting time is the time needed for the head to accelerate the water in the penstock from standstill to the velocity :
where = length of penstock (m), = water velocity (m/s), = head at the gate (m), m/s². It varies with load and is typically 0.5–4 s at full load. A large means a stronger reverse-power effect and harder speed control. A surge tank close to the power house reduces and so reduces .
- 2080 Baisakh · 10 marks
Two generators of 500 MW 11kV, 4% and 250 MW 11kV, 2% are supplying to a common load. When each generator is fully loaded, they operate at common frequency of 50 Hz. If the system load of 100 MW is reduced, what will be frequency deviation and find load shared by each unit?
Answer
When load falls, both units move up their droop lines; the frequency rises and each unit sheds load in proportion to .
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: G1: 500 MW, ; G2: 250 MW, ; both fully loaded at 50 Hz (total 750 MW). Load reduced: MW. Rated frequency 50 Hz.
Stiffness:
Frequency deviation:
New frequency Hz.
Load reduction on each unit:
| Unit | Initial (MW) | Change (MW) | New (MW) |
|---|---|---|---|
| G1 (500 MW, 4 %) | 500 | −50 | 450 |
| G2 (250 MW, 2 %) | 250 | −50 | 200 |
| Total | 750 | −100 | 650 |
Answer: Frequency rises by 0.2 Hz (to 50.2 Hz). G1 now supplies 450 MW and G2 200 MW; both have equal stiffness, so they shed the load equally. The 11 kV rating does not affect the result.
- 2079 Bhadra · 10 marks
Shows figure below two generators operating in parallel and supplying a load of 800 MW. G1 is rated as 800 MW and G2 is rated as 300 MW. G1 supplies 600 MW and G2 supplies 200 MW and system frequency is 50 Hz. At no-load, they operate at a common frequency of 51 Hz. Calculate droop regulations R1 and R2 of G1 and G2 with respect their ratings. Assume base power = 1000 MW. When the load is decreased below 800 MW, the frequency increases to 50.2 Hz. Calculate the power supplied by each generator at reduced load. [Figure: G1 (800 MW, R1 = ?) supplying P1 = 600 MW and G2 (300 MW, R2 = ?) supplying P2 = 200 MW to a common bus feeding load PL = 800 MW]
Answer
The droop line of each unit passes through its no-load point (51 Hz, 0 MW) and its present operating point (50 Hz, given MW). Extending the line to rated output gives the droop.
Frequency drop from no load to present load: Hz.
Stiffness of each unit:
Droop on own ratings
Frequency drop at rated output: G1: Hz; G2: Hz.
Droop on the common base of 1000 MW
Check: : G1 MW ✓, G2 MW ✓.
Load sharing at 50.2 Hz
Frequency drop from no load Hz.
Total load MW, i.e. the load has decreased by 160 MW (G1 sheds 120 MW, G2 sheds 40 MW).
Answer: and on own ratings (3.33 % and 10 % on 1000 MW base). At 50.2 Hz, G1 = 480 MW, G2 = 160 MW (total 640 MW).
- 2079 Baisakh · 6 marks
Two generators of 1000 MW, 2% and 500 MW, 4% are supplying to a common load. When each generator is fully loaded, they operate at common frequency of 49.5 Hz. Calculate the system load shared by each unit when frequency increased to 50 Hz.
Answer
When frequency rises, both units move up their droop lines and reduce output in proportion to . Rated frequency is taken as Hz.
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: G1: 1000 MW, 2 %; G2: 500 MW, 4 %; fully loaded at 49.5 Hz; frequency rises to 50 Hz, so Hz.
| Unit | At 49.5 Hz (MW) | Change (MW) | At 50 Hz (MW) |
|---|---|---|---|
| G1 | 1000 | −500 | 500 |
| G2 | 500 | −125 | 375 |
| Total | 1500 | −625 | 875 |
Answer: At 50 Hz, G1 supplies 500 MW and G2 supplies 375 MW; the system load is 875 MW (a reduction of 625 MW).
- 2078 Bhadra · 5 marks
Three generators of 500MW, 2% drop, 250MW, 4% drop and 200MW, 3% drop are supplying to a common load. When each generator is fully loaded, they operate at common frequency of 49Hz. Calculate the system load shared by each unit when frequency increased to 50Hz.
Answer
All three units are fully loaded at 49 Hz. As frequency rises to 50 Hz, each moves up its droop line and sheds load equal to its stiffness times the rise ( Hz).
| Unit | Rating (MW) | Droop | (MW/Hz) | Reduction (MW) | Load at 50 Hz (MW) |
|---|---|---|---|---|---|
| G1 | 500 | 2 % | 500/(0.02×50) = 500 | 500 | 0 |
| G2 | 250 | 4 % | 250/(0.04×50) = 125 | 125 | 125 |
| G3 | 200 | 3 % | 200/(0.03×50) = 133.33 | 133.33 | 66.67 |
| Total | 950 | – | 758.33 | 758.33 | 191.67 |
Answer: At 50 Hz, G1 = 0 MW (it reaches its no-load point, Hz), G2 = 125 MW, G3 = 66.67 MW; total system load ≈ 191.67 MW.
- 2076 Chaitra · 5 marks
What are the special characteristics of hydraulic turbine? Explain in brief.
Answer
A hydraulic turbine behaves differently from a steam turbine because of the inertia of water in the penstock; its power output does not follow the gate opening directly.
- Non-minimum phase behaviour: the turbine transfer function
has a zero in the right half of the s-plane (). So the power first changes in the opposite direction to the gate movement. 2. Initial reverse power: when the gate is suddenly opened, the flow cannot rise at once because of water inertia, so the head (pressure) at the turbine falls and power first drops to −2 times the gate change. It then rises to +1 times the gate change with time constant : . Closing the gate first gives a power (and pressure) rise. 3. Water inertia governs the response: the response speed is set by the water starting time , which is not constant; it rises with load because increases. 4. Need for transient droop: a governor with only permanent droop would be unstable. Hydro governors use a large temporary (transient) droop with a reset time, so they respond slowly at first and are slower than steam unit governors. 5. Water hammer and gate rate limits: gate movements must be slow enough to keep pressure rise in the penstock safe.
dPm
1 | ____________
| _.-'
0 |---. _-'
| | .'
-2 | |_/ (unit step in gate)
+---+----------------------> t
Here is the water starting time, the time needed by the head to accelerate the water to its rated velocity (0.5–4 s).
- 2076 Asoj · 8 marks
Two generating units of 500MW and 250MW capacities respectively are operating in parallel and supplying power to a common load. When each generator is half loaded, they operate at a common frequency of 50Hz. The droop regulations are 5% and 6% respectively based on their respective ratings. If the load is increased by 100 MW, Calculate: a) New frequency at which they operates b) Power supplied by each generator
Answer
The two units move down their droop lines to a common lower frequency, sharing the 100 MW in proportion to .
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: G1: 500 MW, 5 %, initial 250 MW; G2: 250 MW, 6 %, initial 125 MW; Hz; MW.
a) New frequency
b) Power supplied by each generator
| Generator | Initial (MW) | Increase (MW) | New (MW) |
|---|---|---|---|
| G1 | 250 | 70.59 | 320.59 |
| G2 | 125 | 29.41 | 154.41 |
| Total | 375 | 100 | 475 |
Answer: New frequency ≈ 49.65 Hz; G1 supplies 320.59 MW, G2 supplies 154.41 MW.
- 2075 Chaitra · 8 marks
Two generators of 600MW, 2% and 300 MW, 4% are supplying to a common load. When each generator is fully loaded, they operate at common frequency of 49 Hz. Calculate the system load shared by each unit when frequency increased to 50Hz.
Answer
Both units are fully loaded at 49 Hz. When frequency rises to 50 Hz, each sheds load equal to its stiffness times the frequency rise ( Hz).
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
| Unit | At 49 Hz (MW) | Change (MW) | At 50 Hz (MW) |
|---|---|---|---|
| G1 (600 MW, 2 %) | 600 | −600 | 0 |
| G2 (300 MW, 4 %) | 300 | −150 | 150 |
| Total | 900 | −750 | 150 |
Answer: At 50 Hz, G1 = 0 MW (its no-load frequency is Hz) and G2 = 150 MW; the system load is 150 MW.
- 2074 Chaitra · 4 marks
What do you mean by Isochronous generator? Describe its transient response for a step increase in load.
Answer
An isochronous generator is a generating unit whose governor is isochronous (integral type, zero droop). It keeps the speed and frequency exactly at the set value for any load within its rating. It is used for a single unit supplying an isolated load, or for one unit that controls frequency in a small system.
Governor law: , so the gate keeps moving as long as there is any speed error.
Transient response to a step increase in load
power
P0+dPL .________________ Pe
| __.-- Pm -> Pe
| _.'
P0 ______|__/ (Pm)
t = 0
speed
w0 ______. .---- w0 (restored)
\ .'
'.____.-'
t = 0 time
- At the electrical output jumps by ; is unchanged, so the rotor decelerates and speed falls (slope ).
- The integral governor opens the gate; rises (a hydro turbine first dips a little).
- When the rotor speeds up again. Because the integrator acts until the error is zero, the speed returns exactly to .
- Final state: and . Frequency error is zero, unlike a droop governor which leaves .
- 2074 Chaitra · 8 marks
A power system consist of two generators operating in parallel and supplying a load of 1200 MW. Generator G1 is rated as 900 MW with 2% drop regulation and generator G2 is rated as 450MW with 3% drop regulation. G1 supplied 750 MW and G2 supplies 450 MW and frequency is 60 Hz. When the load is increased by 150 MW, Calculate the new operating frequency and additional power generated by each generator.
Answer
Both generators move down their droop lines to a common lower frequency; the 150 MW is shared in proportion to .
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: G1: 900 MW, 2 %, supplying 750 MW; G2: 450 MW, 3 %, supplying 450 MW; Hz; MW.
| Generator | Initial (MW) | Additional (MW) | New (MW) |
|---|---|---|---|
| G1 | 750 | 112.5 | 862.5 |
| G2 | 450 | 37.5 | 487.5 |
| Total | 1200 | 150 | 1350 |
Answer: New frequency = 59.85 Hz; G1 generates 112.5 MW extra and G2 37.5 MW extra.
Note: G2 is already at its 450 MW rating, so 487.5 MW is an overload. If G2 is held at its limit (gate fully open), G1 must take all 150 MW: Hz, giving 59.8 Hz and G1 = 900 MW.
- 2074 Asoj · 8 marks
Two generating units of capacity 600MVA and 500MVA having droop of 4% and 6% are supplying 500MVA and 400MVA respectively to a common load of 900MVA at 60Hz. Calculate the new frequency and the new generation on each unit if load is increased to 100MVA.
Answer
Taking "increased to 100 MVA" as increased by 100 MVA (total 1000 MVA), and treating MVA as MW (unity power factor), both units share the increase in proportion to .
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: Unit 1: 600 MVA, 4 %, supplying 500; Unit 2: 500 MVA, 6 %, supplying 400; Hz; .
| Unit | Initial | Increase | New |
|---|---|---|---|
| 1 (600 MVA, 4 %) | 500 | 64.29 | 564.29 |
| 2 (500 MVA, 6 %) | 400 | 35.71 | 435.71 |
| Total | 900 | 100 | 1000 |
Answer: New frequency ≈ 59.74 Hz; Unit 1 generates 564.29 MVA (MW) and Unit 2 435.71 MVA (MW).
- 2073 Shrawan · 5 marks
Two generators are supplying power to a system. Their rating are 250 MW and 500 MW respectively. Each generator is half loaded and operating at a frequency of 60 Hz. If the system load is increased by 100 MW, the frequency drops to 59.5 Hz. What must be the individual droop of these generators so that they share the load according to their capacity?
Answer
To share a load change in proportion to capacity, the change on each unit must be the same fraction of its rating. Then from , both droops come out equal.
Sharing by capacity: total capacity MW, MW.
Frequency change: Hz, so pu.
Droop of each unit (pu on own rating):
Answer: Each generator needs a droop of 6.25 % on its own rating. G1 then goes from 125 to 158.33 MW and G2 from 250 to 316.67 MW, both at 63.3 % load, at 59.5 Hz.
- 2073 Chaitra · 8 marks
What do you understand by frequency dependent and independent load? What are the roles of these load on change in frequency? Deduce the transfer function of speed deviation due to load change, including effect of these type of load and inertia.
Answer
Loads are of two types according to how their power depends on frequency:
- Frequency independent loads take the same power at any frequency. Examples: resistive loads such as lighting and heating.
- Frequency dependent loads change their power with frequency. Example: motor loads (fans, pumps, compressors), whose power varies with speed. For small changes their effect is written as .
So the total electrical load change is
where = frequency-independent load change and = load damping constant (% change in load for 1 % change in frequency, typically 1–2).
Role on frequency change
- A rise in frequency-independent load creates an unbalance , which causes the frequency to fall.
- The frequency-dependent load opposes the change: as frequency falls, motor loads take less power. This "self-regulation" reduces the unbalance and helps the system reach a new steady frequency even without a governor.
- Larger gives a smaller frequency deviation and faster settling.
Transfer function of speed deviation
Inertia (rotating mass): for small changes, in per unit, the swing equation is
where = inertia constant (s), = speed deviation (pu). Taking the Laplace transform,
Load damping: a composite load has frequency-insensitive parts (lighting, heating) and frequency-sensitive parts (motors). So
where = non-frequency-sensitive load change and = load damping constant (% change in load per % change in frequency, typically 1–2).
Substituting,
With the turbine power constant (, no governor action):
dPm=0 + +--------------+
------>(+)->| 1 |----+--> d(omega)
^ - | 2Hs + D | |
| +--------------+ |
dPL
For a step load :
- Inertia sets the initial rate of fall () and the time constant .
- Damping sets the final deviation . If all load were frequency independent (), : speed would keep falling linearly without limit.
- 2073 Chaitra · 8 marks
Two generator of 250 MW and 500 MW capacities respectively are operating in parallel and connected to common bus. When each generator is half loaded, they operate at a common frequency of 50 Hz. Their drop characteristics are 4% and 3% respectively based on respective ratings. (i) What will be the common frequency if the common load is increased by 100 MW and calculate the new generation of each units.
Answer
Both units move down their droop lines to a common lower frequency, sharing the extra 100 MW in proportion to .
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: G1: 250 MW, 4 %, initial 125 MW; G2: 500 MW, 3 %, initial 250 MW; Hz; MW.
| Generator | Initial (MW) | Increase (MW) | New (MW) |
|---|---|---|---|
| G1 (250 MW, 4 %) | 125 | 27.27 | 152.27 |
| G2 (500 MW, 3 %) | 250 | 72.73 | 322.73 |
| Total | 375 | 100 | 475 |
Answer: Common frequency ≈ 49.78 Hz; G1 generates 152.27 MW and G2 322.73 MW.
- 2072 Kartik · 8 marks
Two generating units have following ratings and droop: Unit 1: 600MVA, R1 = 6%; Unit 2: 500MVA, R2 = 4%. The units are operating in parallel sharing a load of 900 MW at the normal frequency of 60Hz. Unit 1 supplies 500 MW and unit 2 supplies 400MW. If the load is increased by 90MW calculate the steady state frequency deviation and new generation on each unit.
Answer
Both units drop along their droop lines to a common frequency; the 90 MW is shared in proportion to . MVA ratings are used as the MW base.
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
Data: Unit 1: 600 MVA, , 500 MW; Unit 2: 500 MVA, , 400 MW; Hz; MW.
In per unit: pu. New frequency Hz.
Per-unit cross-check (base 1000 MVA): , ; pu ✓.
| Unit | Initial (MW) | Increase (MW) | New (MW) |
|---|---|---|---|
| 1 | 500 | 40 | 540 |
| 2 | 400 | 50 | 450 |
Answer: Steady-state frequency deviation = −0.24 Hz (−0.004 pu), i.e. 59.76 Hz; Unit 1 = 540 MW, Unit 2 = 450 MW.
- 2070 Asar · 8 marks
Two generating units of 500MW and 250 MW capacities respectively are operating in parallel and supplying power to a common load. When each generator is half loaded, they operate at a common frequency of 50 Hz. If the droop regulation of 500MW generating set is 5% based on its rating, what must be the droop regulation of 250 MW generating unit based on its own rating so that they share the change in load according to their capacities.
Answer
For two units to share any change in load according to their capacities, each must change by the same fraction of its rating for the same frequency change.
From the droop definition, for a common :
Sharing by capacity requires
So .
Check with numbers: for, say, a 75 MW increase,
Ratio , i.e. in proportion to capacity ✓.
Answer: The 250 MW unit must have a droop of 5 % on its own rating (the same per-unit droop as the 500 MW unit).
- 2069 Chaitra · 8 marks
What do you mean by isochronous governor and explain its operation? Why it is not suitable for multiple number of generating units operating in parallel. Derive the mathematical model of governor with speed droop characteristics.
Answer
An isochronous governor keeps the turbine speed constant at its set value for all loads ("isochronous" = same speed). It uses integral control: the gate keeps moving until the speed error is zero.
Operation
w_ref + error +------+ dY +-------+ dPm
---->(+)-------->| K/s |--->|turbine|---+
^ - +------+ +-------+ |
| v
| -dPL -->(+)
| +-----------+ |
+------| 1/(2Hs+D) |<--------------+
speed +-----------+
- A load increase makes , so speed falls.
- The speed error is integrated: . The gate opens and rises.
- The rotor accelerates back. The integrator stops only when the error is zero, so speed returns exactly to , with .
Why not for several units in parallel
- Parallel units run at one common frequency. Each isochronous governor tries to hold the frequency at its own set point.
- Set points are never exactly equal, so the units fight: the one with the higher set point keeps opening and the other keeps closing, until one is at full load and the other at zero or motoring.
- Integral control has no fixed relation between speed and load, so the load sharing is not defined and is unstable. Only one unit in a system can be isochronous; others need droop.
Mathematical model of a governor with speed droop
Droop is obtained by feeding the gate position back through a gain around the integrator (steady-state feedback):
+------+ dY
-dw ---->(+)--->| K/s |---+---> to turbine
^ - +------+ |
| +-----+ |
+-----| R |<---+
+-----+
With no change in load reference:
where is the governor time constant. Including the load reference,
Steady state (): , i.e. (pu). This is the speed droop characteristic: speed falls linearly as output rises. A 5 % droop means a 5 % speed drop gives a 100 % change in gate (output). It gives a unique and stable load sharing between parallel units in proportion to .
- 2069 Chaitra · 8 marks
Two generators of 250 MW and 500 MW capacities respectively are operating in parallel and supplying power to a common load. When each generator is fully loaded, they operate at a common frequency of 49 Hz. Their droop characteristics are 2% and 4% respectively based on their respective ratings. When the system load is decreased, the frequency increases to 50Hz. calculate the decrease in system load shared by each generator.
Answer
Both units are fully loaded at 49 Hz. As the load falls, frequency rises to 50 Hz and each unit sheds load equal to its stiffness times the rise ( Hz).
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
| Generator | At 49 Hz (MW) | Decrease (MW) | At 50 Hz (MW) |
|---|---|---|---|
| G1 (250 MW, 2 %) | 250 | 250 | 0 |
| G2 (500 MW, 4 %) | 500 | 250 | 250 |
| Total | 750 | 500 | 250 |
Answer: The system load decreases by 500 MW, shared equally: 250 MW by G1 (which falls to no load) and 250 MW by G2 (which now supplies 250 MW).
Questions from Old Question Collection (EE 703) (IOE EE 703 exam papers from 2073 Shrawan to 2082 Baisakh) and Question bank (ioesolutions) (IOE EE 703 exam papers from 2069 Chaitra to 2073 Chaitra). Answers are written for this site; check them against your class notes.
Chapter titles and hours from the IOE syllabus ↗